2,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
13.21 kW
12.00 kW
El input
2.74 kW
3.93 kW
COP
4.82
3.05
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
142 %
Prated
13.00 kW
12.00 kW
SCOP
5.26
3.75
Tbiv
2 °C
-10 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
12.10 kW
COP Tj = -7°C
3.05
3.18
Cdh Tj = -7 °C
Pdh Tj = +2°C
12.00 kW
12.50 kW
COP Tj = +2°C
3.05
3.69
Cdh Tj = +2 °C
Pdh Tj = +7°C
12.40 kW
12.80 kW
COP Tj = +7°C
3.45
4.08
Cdh Tj = +7 °C
Pdh Tj = 12°C
12.90 kW
13.10 kW
COP Tj = 12°C
4.23
4.54
Cdh Tj = +12 °C
Pdh Tj = Tbiv
13.20 kW
12.00 kW
COP Tj = Tbiv
4.84
3.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
12.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.05
3.05
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
84 W
84 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5186 kWh
6603 kWh
Heating
EN 14511-2
Heat output
13.21 kW
El input
2.74 kW
COP
4.82
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
202 %
Prated
13.00 kW
SCOP
5.25
Tbiv
2 °C
TOL
2 °C
Pdh Tj = +2°C
13.20 kW
COP Tj = +2°C
4.84
Cdh Tj = +2 °C
Pdh Tj = +7°C
13.30 kW
COP Tj = +7°C
5.13
Cdh Tj = +7 °C
Pdh Tj = 12°C
13.50 kW
COP Tj = 12°C
5.61
Cdh Tj = +12 °C
Pdh Tj = Tbiv
13.20 kW
COP Tj = Tbiv
4.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.84
WTOL
65 °C
Poff
0 W
PTO
84 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
3361 kWh
Colder Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
208 %
Prated
16.00 kW
SCOP
5.39
Tbiv
-15 °C
TOL
-22 °C
Pdh Tj = -7°C
13.40 kW
COP Tj = -7°C
5.35
Cdh Tj = -7 °C
Pdh Tj = +2°C
13.50 kW
COP Tj = +2°C
5.59
Cdh Tj = +2 °C
Pdh Tj = +7°C
13.60 kW
COP Tj = +7°C
5.78
Cdh Tj = +7 °C
Pdh Tj = 12°C
13.60 kW
COP Tj = 12°C
5.82
Cdh Tj = +12 °C
Pdh Tj = Tbiv
13.40 kW
COP Tj = Tbiv
5.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.25
WTOL
65 °C
Poff
0 W
PTO
84 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
3.21 kW
Annual energy consumption Qhe
7507 kWh
Average Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
203 %
Prated
13.00 kW
SCOP
5.26
Tbiv
2 °C
TOL
-20 °C
Pdh Tj = -7°C
12.00 kW
COP Tj = -7°C
3.05
Cdh Tj = -7 °C
Pdh Tj = +2°C
12.00 kW
COP Tj = +2°C
3.05
Cdh Tj = +2 °C
Pdh Tj = +7°C
12.40 kW
COP Tj = +7°C
3.45
Cdh Tj = +7 °C
Pdh Tj = 12°C
12.90 kW
COP Tj = 12°C
4.23
Cdh Tj = +12 °C
Pdh Tj = Tbiv
13.20 kW
COP Tj = Tbiv
4.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.05
WTOL
65 °C
Poff
0 W
PTO
84 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
5186 kWh