1,900 kg
Heating
EN 14511-2
Heat output
7.60 kW
El input
1.60 kW
COP
4.76
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
204 %
Prated
8.00 kW
SCOP
5.01
Tbiv
2 °C
TOL
2 °C
Pdh Tj = +2°C
7.60 kW
COP Tj = +2°C
4.76
Cdh Tj = +2 °C
Pdh Tj = +7°C
7.70 kW
COP Tj = +7°C
5.13
Cdh Tj = +7 °C
Pdh Tj = 12°C
7.80 kW
COP Tj = 12°C
5.77
Cdh Tj = +12 °C
Pdh Tj = Tbiv
7.60 kW
COP Tj = Tbiv
4.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.76
WTOL
60 °C
Poff
0 W
PTO
55 W
PSB
10 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
1918 kWh
Colder Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
212 %
Prated
9.00 kW
SCOP
5.24
Tbiv
-15 °C
TOL
-22 °C
Pdh Tj = -7°C
7.70 kW
COP Tj = -7°C
5.42
Cdh Tj = -7 °C
Pdh Tj = +2°C
7.80 kW
COP Tj = +2°C
5.74
Cdh Tj = +2 °C
Pdh Tj = +7°C
7.80 kW
COP Tj = +7°C
6.01
Cdh Tj = +7 °C
Pdh Tj = 12°C
7.80 kW
COP Tj = 12°C
6.05
Cdh Tj = +12 °C
Pdh Tj = Tbiv
7.70 kW
COP Tj = Tbiv
5.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.29
WTOL
60 °C
Poff
0 W
PTO
55 W
PSB
10 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
1.84 kW
Annual energy consumption Qhe
4238 kWh
Average Climate
EN 12102-1
Sound power level indoor
50 dB(A)
EN 14825
ηs
204 %
Prated
8.00 kW
SCOP
5.30
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
7.60 kW
COP Tj = -7°C
4.82
Cdh Tj = -7 °C
Pdh Tj = +2°C
7.70 kW
COP Tj = +2°C
5.22
Cdh Tj = +2 °C
Pdh Tj = +7°C
7.80 kW
COP Tj = +7°C
5.62
Cdh Tj = +7 °C
Pdh Tj = 12°C
7.80 kW
COP Tj = 12°C
6.08
Cdh Tj = +12 °C
Pdh Tj = Tbiv
7.60 kW
COP Tj = Tbiv
4.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.76
WTOL
60 °C
Poff
0 W
PTO
55 W
PSB
10 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
2964 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.60 kW
6.90 kW
El input
1.60 kW
2.53 kW
COP
4.76
2.73
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
131 %
Prated
8.00 kW
7.00 kW
SCOP
5.30
3.48
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.60 kW
7.00 kW
COP Tj = -7°C
4.82
2.86
Cdh Tj = -7 °C
Pdh Tj = +2°C
7.70 kW
7.20 kW
COP Tj = +2°C
5.22
3.41
Cdh Tj = +2 °C
Pdh Tj = +7°C
7.80 kW
7.40 kW
COP Tj = +7°C
5.62
3.85
Cdh Tj = +7 °C
Pdh Tj = 12°C
7.80 kW
7.50 kW
COP Tj = 12°C
6.08
4.39
Cdh Tj = +12 °C
Pdh Tj = Tbiv
7.60 kW
6.90 kW
COP Tj = Tbiv
4.76
2.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
6.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.76
2.73
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
55 W
55 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2964 kWh
4113 kWh