0,950 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
150 %
Prated
4.90 kW
4.10 kW
SCOP
5.01
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
4.94 kW
4.08 kW
COP Tj = +2°C
3.04
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.07 kW
2.95 kW
COP Tj = +7°C
5.03
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.57 kW
3.31 kW
COP Tj = 12°C
5.89
5.18
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.94 kW
4.08 kW
COP Tj = Tbiv
3.04
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.94 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.04
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6552 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
86 %
Prated
4.40 kW
2.80 kW
SCOP
3.46
2.22
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.76 kW
1.85 kW
COP Tj = -7°C
2.91
1.72
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.23 kW
2.09 kW
COP Tj = +2°C
4.44
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.53 kW
3.27 kW
COP Tj = 12°C
5.46
5.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.62 kW
2.30 kW
COP Tj = Tbiv
1.65
1.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.43 kW
2.82 kW
Annual energy consumption Qhe
10662 kWh
6791 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
150 %
Prated
4.90 kW
4.10 kW
SCOP
5.01
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
4.94 kW
4.08 kW
COP Tj = +2°C
3.04
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.07 kW
2.95 kW
COP Tj = +7°C
5.03
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.57 kW
3.31 kW
COP Tj = 12°C
5.89
5.18
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.94 kW
4.08 kW
COP Tj = Tbiv
3.04
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.94 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.04
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6552 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
86 %
Prated
4.40 kW
2.80 kW
SCOP
3.46
2.22
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.76 kW
1.85 kW
COP Tj = -7°C
2.91
1.72
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.23 kW
2.09 kW
COP Tj = +2°C
4.44
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.53 kW
3.27 kW
COP Tj = 12°C
5.46
5.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.62 kW
2.30 kW
COP Tj = Tbiv
1.65
1.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.43 kW
2.82 kW
Annual energy consumption Qhe
10662 kWh
6791 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
150 %
Prated
4.90 kW
4.10 kW
SCOP
5.01
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
4.94 kW
4.08 kW
COP Tj = +2°C
3.04
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.07 kW
2.95 kW
COP Tj = +7°C
5.03
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.57 kW
3.31 kW
COP Tj = 12°C
5.89
5.18
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.94 kW
4.08 kW
COP Tj = Tbiv
3.04
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.94 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.04
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6552 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
86 %
Prated
4.40 kW
2.80 kW
SCOP
3.46
2.22
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.76 kW
1.85 kW
COP Tj = -7°C
2.91
1.72
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.23 kW
2.09 kW
COP Tj = +2°C
4.44
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.53 kW
3.27 kW
COP Tj = 12°C
5.46
5.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.62 kW
2.30 kW
COP Tj = Tbiv
1.65
1.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.43 kW
2.82 kW
Annual energy consumption Qhe
10662 kWh
6791 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
150 %
Prated
4.90 kW
4.10 kW
SCOP
5.01
3.83
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
4.94 kW
4.08 kW
COP Tj = +2°C
3.04
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.07 kW
2.95 kW
COP Tj = +7°C
5.03
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.57 kW
3.31 kW
COP Tj = 12°C
5.89
5.18
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.94 kW
4.08 kW
COP Tj = Tbiv
3.04
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.94 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.04
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6552 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
86 %
Prated
4.40 kW
2.80 kW
SCOP
3.46
2.22
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.76 kW
1.85 kW
COP Tj = -7°C
2.91
1.72
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.23 kW
2.09 kW
COP Tj = +2°C
4.44
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.53 kW
3.27 kW
COP Tj = 12°C
5.46
5.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.62 kW
2.30 kW
COP Tj = Tbiv
1.65
1.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.43 kW
2.82 kW
Annual energy consumption Qhe
10662 kWh
6791 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.2 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
5.70 kW
4.10 kW
SCOP
5.70
3.97
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
5.01 kW
4.08 kW
COP Tj = +2°C
4.30
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.28 kW
2.95 kW
COP Tj = +7°C
4.86
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.31 kW
COP Tj = 12°C
7.69
5.59
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
5.01 kW
4.08 kW
COP Tj = Tbiv
2.97
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.97
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6687 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
90 %
Prated
4.80 kW
3.30 kW
SCOP
3.46
2.32
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.10 kW
2.10 kW
COP Tj = -7°C
2.89
1.81
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.40 kW
2.09 kW
COP Tj = +2°C
4.40
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.34 kW
COP Tj = 12°C
8.00
6.85
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.90 kW
2.67 kW
COP Tj = Tbiv
2.11
1.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.78 kW
3.27 kW
Annual energy consumption Qhe
11493 kWh
7870 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
5.70 kW
4.10 kW
SCOP
5.70
3.97
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
5.01 kW
4.08 kW
COP Tj = +2°C
4.30
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.28 kW
2.95 kW
COP Tj = +7°C
4.86
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.31 kW
COP Tj = 12°C
7.69
5.59
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
5.01 kW
4.08 kW
COP Tj = Tbiv
2.97
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.97
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6687 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
90 %
Prated
4.80 kW
3.30 kW
SCOP
3.46
2.32
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.10 kW
2.10 kW
COP Tj = -7°C
2.89
1.81
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.40 kW
2.09 kW
COP Tj = +2°C
4.40
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.34 kW
COP Tj = 12°C
8.00
6.85
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.90 kW
2.67 kW
COP Tj = Tbiv
2.11
1.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.78 kW
3.27 kW
Annual energy consumption Qhe
11493 kWh
7870 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
5.70 kW
4.10 kW
SCOP
5.70
3.97
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
5.01 kW
4.08 kW
COP Tj = +2°C
4.30
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.28 kW
2.95 kW
COP Tj = +7°C
4.86
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.31 kW
COP Tj = 12°C
7.69
5.59
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
5.01 kW
4.08 kW
COP Tj = Tbiv
2.97
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.97
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6687 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
90 %
Prated
4.80 kW
3.30 kW
SCOP
3.46
2.32
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.10 kW
2.10 kW
COP Tj = -7°C
2.89
1.81
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.40 kW
2.09 kW
COP Tj = +2°C
4.40
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.34 kW
COP Tj = 12°C
8.00
6.85
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.90 kW
2.67 kW
COP Tj = Tbiv
2.11
1.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.78 kW
3.27 kW
Annual energy consumption Qhe
11493 kWh
7870 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
5.70 kW
4.10 kW
SCOP
5.70
3.97
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
5.01 kW
4.08 kW
COP Tj = +2°C
4.30
1.98
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.28 kW
2.95 kW
COP Tj = +7°C
4.86
3.25
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.31 kW
COP Tj = 12°C
7.69
5.59
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
5.01 kW
4.08 kW
COP Tj = Tbiv
2.97
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.08 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.97
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6687 kWh
5450 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
135 %
90 %
Prated
4.80 kW
3.30 kW
SCOP
3.46
2.32
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.10 kW
2.10 kW
COP Tj = -7°C
2.89
1.81
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.40 kW
2.09 kW
COP Tj = +2°C
4.40
2.72
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.88 kW
COP Tj = +7°C
6.20
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.43 kW
3.34 kW
COP Tj = 12°C
8.00
6.85
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.90 kW
2.67 kW
COP Tj = Tbiv
2.11
1.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.30 kW
1.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.21
0.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.78 kW
3.27 kW
Annual energy consumption Qhe
11493 kWh
7870 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.02 kW
4.36 kW
El input
1.23 kW
1.80 kW
COP
4.90
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
125 %
Prated
5.10 kW
4.10 kW
SCOP
4.45
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.53 kW
3.31 kW
COP Tj = -7°C
2.85
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
3.04 kW
2.65 kW
COP Tj = +2°C
4.30
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.11 kW
2.74 kW
COP Tj = +7°C
5.93
4.76
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.40
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
4.53 kW
3.59 kW
COP Tj = Tbiv
2.85
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.08 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.20 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
10549 kWh
8383 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.08 kW
4.36 kW
El input
0.80 kW
1.80 kW
COP
5.10
2.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
3.70 kW
ηs
175 %
126 %
Prated
4.00 kW
3.70 kW
SCOP
4.45
3.22
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.51 kW
3.31 kW
COP Tj = -7°C
2.84
1.89
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.45 kW
2.65 kW
COP Tj = +2°C
2.84
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.14 kW
2.74 kW
COP Tj = +7°C
5.97
4.36
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
3.60 kW
3.27 kW
COP Tj = 12°C
8.78
6.35
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
3.51 kW
3.31 kW
COP Tj = Tbiv
2.84
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.83 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.14 kW
0.88 kW
Backup Heater
0.00 kW
Annual energy consumption Qhe
8202 kWh
7700 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
133 %
COP
3.32
Heating up time
2:15 h:min
Standby power input
25.0 W
Reference hot water temperature
53.4 °C
Mixed water at 40°C
296.1 l