2,680 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.57 kW
5.64 kW
El input
1.50 kW
2.32 kW
COP
4.38
2.43
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
1.74 kW
Cooling capacity
5.07
EER
2.91
EN 14825
+7°C/+12°C
Pdesignc
5.07 kW
SEER
3.82
Pdc Tj = 35°C
5.07 kW
EER Tj = 35°C
2.91
Pdc Tj = 30°C
3.74 kW
EER Tj = 30°C
4.04
Cdc Tj = 30 °C
1.0
Pdc Tj = 25°C
3.40 kW
EER Tj = 25°C
4.09
Cdc Tj = 25 °C
1.0
Pdc Tj = 20°C
3.68 kW
EER Tj = 20°C
4.92
Cdc Tj = 20 °C
1.0
Poff
12 W
PTO
0 W
PSB
12 W
PCK
0 W
Annual energy consumption Qce
464 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
151 %
119 %
Prated
5.00 kW
4.00 kW
SCOP
3.86
3.06
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.30 kW
4.50 kW
COP Tj = -7°C
2.68
1.57
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.40 kW
2.70 kW
COP Tj = +2°C
4.10
2.95
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
3.60 kW
3.30 kW
COP Tj = +7°C
4.15
4.57
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
3.70 kW
3.60 kW
COP Tj = 12°C
5.11
6.02
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
5.30 kW
4.50 kW
COP Tj = Tbiv
2.68
1.57
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.00 kW
4.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.34
1.45
WTOL
39 °C
39 °C
Poff
0 W
0 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2171 kWh
2329 kWh