2,350 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
17.02 kW
15.60 kW
El input
3.75 kW
4.45 kW
COP
4.54
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
53 dB(A)
53 dB(A)
Sound power level outdoor
0 dB(A)
0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
134 %
Prated
17.00 kW
16.00 kW
SCOP
4.93
3.54
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
17.00 kW
15.90 kW
COP Tj = -7°C
4.59
3.01
Pdh Tj = +2°C
17.20 kW
16.30 kW
COP Tj = +2°C
4.88
3.49
Pdh Tj = +7°C
17.30 kW
16.60 kW
COP Tj = +7°C
5.16
3.85
Pdh Tj = 12°C
17.40 kW
16.90 kW
COP Tj = 12°C
5.48
4.27
Pdh Tj = Tbiv
17.00 kW
15.80 kW
COP Tj = Tbiv
4.54
2.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.00 kW
15.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.54
2.89
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
139 W
139 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7128 kWh
9198 kWh
Heating
EN 14511-2
Heat output
17.02 kW
El input
3.75 kW
COP
4.54
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
53 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
188 %
Prated
17.00 kW
SCOP
4.91
Tbiv
2 °C
TOL
2 °C
Pdh Tj = -7°C
0.00 kW
COP Tj = -7°C
0.00
Pdh Tj = +2°C
17.00 kW
COP Tj = +2°C
4.54
Pdh Tj = +7°C
17.20 kW
COP Tj = +7°C
4.81
Pdh Tj = 12°C
17.40 kW
COP Tj = 12°C
5.26
Pdh Tj = Tbiv
17.00 kW
COP Tj = Tbiv
4.54
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.54
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
139 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
4635 kWh
Colder Climate
EN 12102-1
Sound power level indoor
53 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
194 %
Prated
21.00 kW
SCOP
5.06
Tbiv
-15 °C
TOL
-22 °C
Pdh Tj = -7°C
17.30 kW
COP Tj = -7°C
5.02
Pdh Tj = +2°C
17.30 kW
COP Tj = +2°C
5.24
Pdh Tj = +7°C
17.40 kW
COP Tj = +7°C
5.43
Pdh Tj = 12°C
17.40 kW
COP Tj = 12°C
5.46
Pdh Tj = Tbiv
17.20 kW
COP Tj = Tbiv
4.92
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.92
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
139 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
4.07 kW
Annual energy consumption Qhe
10274 kWh
Average Climate
EN 12102-1
Sound power level indoor
53 dB(A)
Sound power level outdoor
0 dB(A)
EN 14825
ηs
189 %
Prated
17.00 kW
SCOP
4.93
Tbiv
-10 °C
TOL
-20 °C
Pdh Tj = -7°C
17.00 kW
COP Tj = -7°C
4.59
Pdh Tj = +2°C
17.20 kW
COP Tj = +2°C
4.88
Pdh Tj = +7°C
17.30 kW
COP Tj = +7°C
5.16
Pdh Tj = 12°C
17.40 kW
COP Tj = 12°C
5.48
Pdh Tj = Tbiv
17.00 kW
COP Tj = Tbiv
4.54
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.54
Rated airflow rate
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
65 °C
Poff
0 W
PTO
139 W
PSB
9 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
7128 kWh