2,030 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.31 kW
9.28 kW
El input
2.05 kW
3.18 kW
COP
5.02
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
48 dB(A)
Sound power level outdoor
0 dB(A)
0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
136 %
Prated
10.00 kW
9.00 kW
SCOP
5.59
3.60
Tbiv
2 °C
2 °C
TOL
0 °C
0 °C
Pdh Tj = -7°C
0.00 kW
0.00 kW
COP Tj = -7°C
0.00
0.00
Pdh Tj = +2°C
10.30 kW
9.10 kW
COP Tj = +2°C
5.03
2.83
Pdh Tj = +7°C
10.40 kW
9.50 kW
COP Tj = +7°C
5.43
3.28
Pdh Tj = 12°C
10.60 kW
10.00 kW
COP Tj = 12°C
6.10
4.21
Pdh Tj = Tbiv
10.30 kW
9.10 kW
COP Tj = Tbiv
5.03
2.83
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.30 kW
91.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.03
2.83
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
84 W
84 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2466 kWh
3367 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
48 dB(A)
Sound power level outdoor
0 dB(A)
0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
224 %
224 %
Prated
13.00 kW
13.00 kW
SCOP
5.81
5.80
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
10.50 kW
10.50 kW
COP Tj = -7°C
5.75
5.74
Pdh Tj = +2°C
10.60 kW
10.60 kW
COP Tj = +2°C
6.07
6.07
Pdh Tj = +7°C
10.70 kW
10.70 kW
COP Tj = +7°C
6.36
6.36
Pdh Tj = 12°C
10.70 kW
10.70 kW
COP Tj = 12°C
6.40
6.40
Pdh Tj = Tbiv
10.50 kW
10.50 kW
COP Tj = Tbiv
5.60
5.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.50 kW
10.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.60
5.03
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
84 W
84 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.55 kW
2.55 kW
Annual energy consumption Qhe
5457 kWh
5457 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
48 dB(A)
Sound power level outdoor
0 dB(A)
0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
216 %
137 %
Prated
10.00 kW
9.00 kW
SCOP
5.61
3.63
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
9.20 kW
9.20 kW
COP Tj = -7°C
2.97
2.97
Pdh Tj = +2°C
9.60 kW
9.60 kW
COP Tj = +2°C
3.56
3.56
Pdh Tj = +7°C
9.90 kW
9.90 kW
COP Tj = +7°C
4.03
4.03
Pdh Tj = 12°C
10.10 kW
10.10 kW
COP Tj = 12°C
4.60
4.60
Pdh Tj = Tbiv
10.30 kW
9.10 kW
COP Tj = Tbiv
5.03
2.83
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.10 kW
9.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
2.83
Rated airflow rate
0 m³/h
0 m³/h
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
84 W
84 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3799 kWh
5167 kWh