Certificate holders

Subtype

AA packaged 6/8

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0001-18
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
AA packaged 6/8
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,400 kg

Certification Date
09.10.2018
Testing basis
HP Keymark scheme rules rev. no. 4
Generate PDF Export model CSV Download certificate
  • Number of models 3

Models

PUHZ-W60VAA
Configure model
Model name
PUHZ-W60VAA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

6.00 kW

6.00 kW

El input

1.24 kW

2.09 kW

COP

4.83

2.87

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

188 %

132 %

Prated

6.00 kW

6.00 kW

SCOP

4.77

3.37

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

5.30 kW

5.30 kW

COP Tj = -7°C

3.18

2.09

Cdh Tj = -7 °C

0.991

0.994

Pdh Tj = +2°C

3.20 kW

3.20 kW

COP Tj = +2°C

4.52

3.22

Cdh Tj = +2 °C

0.979

0.985

Pdh Tj = +7°C

3.20 kW

2.90 kW

COP Tj = +7°C

6.55

4.62

Cdh Tj = +7 °C

0.969

0.976

Pdh Tj = 12°C

2.90 kW

2.70 kW

COP Tj = 12°C

8.16

6.09

Cdh Tj = +12 °C

0.958

0.966

Pdh Tj = Tbiv

5.30 kW

5.30 kW

COP Tj = Tbiv

3.18

2.09

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.88 kW

4.88 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

1.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

0.960

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.12 kW

1.12 kW

Annual energy consumption Qhe

2598 kWh

3674 kWh

PUHZ-W85VAA
Configure model
Model name
PUHZ-W85VAA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

9.00 kW

9.00 kW

El input

2.00 kW

3.24 kW

COP

4.51

2.78

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

139 %

Prated

8.50 kW

8.50 kW

SCOP

4.44

3.56

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

7.50 kW

7.50 kW

COP Tj = -7°C

2.21

1.96

Cdh Tj = -7 °C

0.996

0.996

Pdh Tj = +2°C

4.60 kW

4.60 kW

COP Tj = +2°C

4.53

3.50

Cdh Tj = +2 °C

0.985

0.989

Pdh Tj = +7°C

3.40 kW

2.90 kW

COP Tj = +7°C

6.28

4.90

Cdh Tj = +7 °C

0.972

0.975

Pdh Tj = 12°C

3.20 kW

2.90 kW

COP Tj = 12°C

8.48

6.80

Cdh Tj = +12 °C

0.960

0.965

Pdh Tj = Tbiv

7.50 kW

7.50 kW

COP Tj = Tbiv

2.21

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.65 kW

6.65 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.00

1.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.950

0.960

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.85 kW

1.85 kW

Annual energy consumption Qhe

3952 kWh

4933 kWh

PUHZ-W85YAA
Configure model
Model name
PUHZ-W85YAA
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

9.00 kW

9.00 kW

El input

2.00 kW

3.24 kW

COP

4.51

2.78

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

139 %

Prated

8.50 kW

8.50 kW

SCOP

4.43

3.55

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

7.50 kW

7.50 kW

COP Tj = -7°C

2.21

1.96

Cdh Tj = -7 °C

0.994

0.994

Pdh Tj = +2°C

4.60 kW

4.60 kW

COP Tj = +2°C

4.53

3.50

Cdh Tj = +2 °C

0.978

0.983

Pdh Tj = +7°C

3.40 kW

2.90 kW

COP Tj = +7°C

6.28

4.90

Cdh Tj = +7 °C

0.959

0.963

Pdh Tj = 12°C

3.20 kW

2.90 kW

COP Tj = 12°C

8.48

6.80

Cdh Tj = +12 °C

0.942

0.948

Pdh Tj = Tbiv

7.50 kW

7.50 kW

COP Tj = Tbiv

2.21

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.65 kW

6.65 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.99

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.930

0.940

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.85 kW

1.85 kW

Annual energy consumption Qhe

3962 kWh

4941 kWh