6,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
27.41 kW
25.10 kW
El input
6.32 kW
8.49 kW
COP
4.34
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
60 dB(A)
64 dB(A)
Sound power level outdoor
60 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
131 %
Prated
27.00 kW
25.00 kW
SCOP
4.58
4.58
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
27.50 kW
25.30 kW
COP Tj = -7°C
4.38
3.06
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
27.70 kW
26.10 kW
COP Tj = +2°C
4.59
3.48
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
27.90 kW
26.60 kW
COP Tj = +7°C
4.80
3.78
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
28.20 kW
27.10 kW
COP Tj = 12°C
5.03
4.12
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
27.40 kW
25.10 kW
COP Tj = Tbiv
4.34
2.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.40 kW
25.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.34
2.96
WTOL
75 °C
75 °C
Poff
0 W
0 W
PTO
3 W
3 W
PSB
3 W
3 W
PCK
46 W
46 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
12359 kWh
14872 kWh
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
174 %
131 %
Prated
27.00 kW
25.00 kW
SCOP
4.58
4.58
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
27.40 kW
25.10 kW
COP Tj = +2°C
4.34
2.96
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
27.70 kW
25.80 kW
COP Tj = +7°C
4.55
3.29
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
28.00 kW
26.80 kW
COP Tj = 12°C
4.88
3.89
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
27.40 kW
25.10 kW
COP Tj = Tbiv
4.34
2.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.40 kW
25.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.34
2.96
WTOL
75 °C
75 °C
Poff
0 W
0 W
PTO
3 W
3 W
PSB
3 W
3 W
PCK
46 W
46 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8031 kWh
9675 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
180 %
136 %
Prated
34.00 kW
32.00 kW
SCOP
4.58
4.58
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
27.80 kW
26.10 kW
COP Tj = -7°C
4.70
3.46
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
28.00 kW
26.60 kW
COP Tj = +2°C
4.86
3.77
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
28.10 kW
27.00 kW
COP Tj = +7°C
5.00
4.05
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
28.20 kW
27.30 kW
COP Tj = 12°C
5.02
4.28
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
27.80 kW
25.00 kW
COP Tj = Tbiv
4.63
3.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.40 kW
25.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.34
2.96
WTOL
75 °C
75 °C
Poff
0 W
0 W
PTO
3 W
3 W
PSB
3 W
3 W
PCK
46 W
46 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.61 kW
6.52 kW
Annual energy consumption Qhe
17849 kWh
21670 kWh
Pdh Tj = -15°C (if TOL<-20°C)
27.80
25.00
COP Tj = -15°C (if TOL<-20°C)
4.63
3.29
Cdh Tj = -15 °C
0.90
0.90