Certificate holders

Subtype

TTF 27 HT

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0187
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 27 HT
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R134a
Mass of Refrigerant

6,000 kg

Certification Date
04.09.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

TTF 27 HT
Configure model
Model name
TTF 27 HT
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

27.41 kW

25.10 kW

El input

6.32 kW

8.49 kW

COP

4.34

2.95

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

60 dB(A)

64 dB(A)

Sound power level outdoor

60 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

131 %

Prated

27.00 kW

25.00 kW

SCOP

4.58

4.58

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

27.50 kW

25.30 kW

COP Tj = -7°C

4.38

3.06

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

27.70 kW

26.10 kW

COP Tj = +2°C

4.59

3.48

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

27.90 kW

26.60 kW

COP Tj = +7°C

4.80

3.78

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

28.20 kW

27.10 kW

COP Tj = 12°C

5.03

4.12

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

27.40 kW

25.10 kW

COP Tj = Tbiv

4.34

2.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

27.40 kW

25.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.34

2.96

WTOL

75 °C

75 °C

Poff

0 W

0 W

PTO

3 W

3 W

PSB

3 W

3 W

PCK

46 W

46 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

12359 kWh

14872 kWh

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

174 %

131 %

Prated

27.00 kW

25.00 kW

SCOP

4.58

4.58

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

27.40 kW

25.10 kW

COP Tj = +2°C

4.34

2.96

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

27.70 kW

25.80 kW

COP Tj = +7°C

4.55

3.29

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

28.00 kW

26.80 kW

COP Tj = 12°C

4.88

3.89

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

27.40 kW

25.10 kW

COP Tj = Tbiv

4.34

2.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

27.40 kW

25.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.34

2.96

WTOL

75 °C

75 °C

Poff

0 W

0 W

PTO

3 W

3 W

PSB

3 W

3 W

PCK

46 W

46 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

8031 kWh

9675 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

180 %

136 %

Prated

34.00 kW

32.00 kW

SCOP

4.58

4.58

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

27.80 kW

26.10 kW

COP Tj = -7°C

4.70

3.46

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

28.00 kW

26.60 kW

COP Tj = +2°C

4.86

3.77

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

28.10 kW

27.00 kW

COP Tj = +7°C

5.00

4.05

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

28.20 kW

27.30 kW

COP Tj = 12°C

5.02

4.28

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

27.80 kW

25.00 kW

COP Tj = Tbiv

4.63

3.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

27.40 kW

25.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.34

2.96

WTOL

75 °C

75 °C

Poff

0 W

0 W

PTO

3 W

3 W

PSB

3 W

3 W

PCK

46 W

46 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

6.61 kW

6.52 kW

Annual energy consumption Qhe

17849 kWh

21670 kWh

Pdh Tj = -15°C (if TOL<-20°C)

27.80

25.00

COP Tj = -15°C (if TOL<-20°C)

4.63

3.29

Cdh Tj = -15 °C

0.90

0.90