01. Yutaki S 2.0HP R32

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-29 / 1
Certification Body
BRE Global Limited
Subtype title
01. Yutaki S 2.0HP R32
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,200 kg

Certification Date
02.08.2019
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

01. RAS-2WHVRP RWM-2.0NRE - Heating Only
Configure model
Model name
01. RAS-2WHVRP RWM-2.0NRE - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.30 kW

4.30 kW

El input

0.82 kW

1.43 kW

COP

5.25

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

37 dB(A)

37 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

133 %

Prated

4.00 kW

4.00 kW

SCOP

4.60

3.40

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.54 kW

3.50 kW

COP Tj = -7°C

3.20

2.13

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.35 kW

2.10 kW

COP Tj = +2°C

4.80

3.35

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.20

5.15

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

8.30

6.80

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

3.54 kW

3.50 kW

COP Tj = Tbiv

3.20

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.00 kW

3.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.75

1.90

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

1798 kWh

2401 kWh

02. RAS-2WHVRP RWM-2.0NRE - with cooling kit
Configure model
Model name
02. RAS-2WHVRP RWM-2.0NRE - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.30 kW

4.30 kW

El input

0.82 kW

1.43 kW

COP

5.25

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1 kW

1.02 kW

Cooling capacity

4

5.5

EER

4

5.4

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

4 kW

5.5 kW

SEER

5.57

8.04

Pdc Tj = 35°C

4 kW

5.5 kW

EER Tj = 35°C

4

5.4

Pdc Tj = 30°C

2.95 kW

4.05 kW

EER Tj = 30°C

5

7.2

Cdc Tj = 30 °C

1

1

Pdc Tj = 25°C

2.05 kW

2.61 kW

EER Tj = 25°C

6.45

9.6

Cdc Tj = 25 °C

0.9

0.9

Pdc Tj = 20°C

2.88 kW

2.51 kW

EER Tj = 20°C

8

10.3

Cdc Tj = 20 °C

0.9

0.9

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Annual energy consumption Qce

431 kWh

410 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

37 dB(A)

37 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

136 %

Prated

4.00 kW

4.00 kW

SCOP

4.73

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.54 kW

3.50 kW

COP Tj = -7°C

3.20

2.13

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.35 kW

2.10 kW

COP Tj = +2°C

4.80

3.35

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.20

5.15

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

8.30

6.80

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

3.54 kW

3.50 kW

COP Tj = Tbiv

3.20

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.00 kW

3.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.75

1.90

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.90 kW

Annual energy consumption Qhe

1754 kWh

2357 kWh