Certificate holders

Subtype

TTL 4.5 ICS, TTL 4.5 IKCS

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0225
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTL 4.5 ICS, TTL 4.5 IKCS
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,200 kg

Certification Date
03.04.2018
Testing basis
HP KEYMARK certification scheme rules rev. no. 3
Generate PDF Export model CSV
  • Number of models 2

Models

TTL 4.5 IKCS
Configure model
Model name
TTL 4.5 IKCS
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

2.06 kW

2.09 kW

El input

0.44 kW

0.81 kW

COP

4.68

2.59

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

128 %

Prated

4.70 kW

4.50 kW

SCOP

4.46

3.28

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.17 kW

3.94 kW

COP Tj = -7°C

3.09

2.22

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.86 kW

2.54 kW

COP Tj = +2°C

4.29

3.10

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.08 kW

2.04 kW

COP Tj = +7°C

6.24

4.53

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.02 kW

1.97 kW

COP Tj = 12°C

8.31

6.44

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.17 kW

3.94 kW

COP Tj = Tbiv

3.09

2.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.06 kW

2.96 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.71

1.94

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.64 kW

1.54 kW

Annual energy consumption Qhe

2187 kWh

2837 kWh

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

198 %

136 %

Prated

2.62 kW

2.40 kW

SCOP

5.01

3.47

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.62 kW

2.37 kW

COP Tj = +2°C

3.76

2.28

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.07 kW

1.84 kW

COP Tj = +7°C

5.19

3.35

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.00 kW

1.94 kW

COP Tj = 12°C

7.92

5.39

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

2.62 kW

2.37 kW

COP Tj = Tbiv

3.76

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.62 kW

2.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.76

2.28

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.03 kW

Annual energy consumption Qhe

698 kWh

923 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

150 %

116 %

Prated

6.80 kW

6.70 kW

SCOP

3.83

2.98

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.11 kW

4.05 kW

COP Tj = -7°C

3.37

2.57

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

3.01 kW

2.60 kW

COP Tj = +2°C

5.17

3.55

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.09 kW

2.07 kW

COP Tj = +7°C

7.26

5.31

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.02 kW

1.99 kW

COP Tj = 12°C

8.96

7.11

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.11 kW

4.05 kW

COP Tj = Tbiv

3.37

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.35 kW

6.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

1.00

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.45 kW

3.50 kW

Annual energy consumption Qhe

4382 kWh

5547 kWh

Pdh Tj = -15°C (if TOL<-20°C)

4.11

4.05

COP Tj = -15°C (if TOL<-20°C)

3.37

2.57

Cdh Tj = -15 °C

0.90

0.90

TTL 4.5 ICS
Configure model
Model name
TTL 4.5 ICS
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

2.06 kW

2.10 kW

El input

0.44 kW

0.80 kW

COP

4.68

2.64

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

130 %

Prated

4.80 kW

4.50 kW

SCOP

4.53

3.32

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.22 kW

3.98 kW

COP Tj = -7°C

3.22

2.27

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.88 kW

2.55 kW

COP Tj = +2°C

4.33

3.16

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.08 kW

2.04 kW

COP Tj = +7°C

6.28

4.53

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.02 kW

1.97 kW

COP Tj = 12°C

8.35

6.44

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.22 kW

3.98 kW

COP Tj = Tbiv

3.22

2.27

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.11 kW

3.79 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.84

1.85

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.69 kW

0.71 kW

Annual energy consumption Qhe

2187 kWh

2804 kWh

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

198 %

136 %

Prated

2.64 kW

2.40 kW

SCOP

5.03

3.48

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

2.64 kW

2.39 kW

COP Tj = +2°C

3.83

2.33

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.07 kW

1.84 kW

COP Tj = +7°C

5.19

3.35

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.00 kW

1.94 kW

COP Tj = 12°C

7.92

5.39

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

2.64 kW

2.39 kW

COP Tj = Tbiv

3.83

2.33

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.64 kW

2.39 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.83

2.33

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.01 kW

Annual energy consumption Qhe

70 kWh

921 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

155 %

119 %

Prated

6.90 kW

6.80 kW

SCOP

3.94

3.04

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

4.16 kW

4.10 kW

COP Tj = -7°C

3.48

2.63

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

3.03 kW

2.62 kW

COP Tj = +2°C

5.34

3.64

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.09 kW

2.07 kW

COP Tj = +7°C

7.26

5.31

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.02 kW

1.99 kW

COP Tj = 12°C

8.96

7.11

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.16 kW

4.10 kW

COP Tj = Tbiv

3.48

2.63

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.00 kW

3.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.00

2.50

WTOL

60 °C

60 °C

Poff

56 W

56 W

PTO

21 W

21 W

PSB

56 W

56 W

PCK

26 W

26 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.54 kW

3.28 kW

Annual energy consumption Qhe

4321 kWh

5515 kWh

Pdh Tj = -15°C (if TOL<-20°C)

4.16

4.10

COP Tj = -15°C (if TOL<-20°C)

3.48

2.63

Cdh Tj = -15 °C

0.90

0.90