Certificate holders

Single View for Model

Subtype

Bosch Compress 3000 AWS-8

Heat Pump Type: Outdoor Air/Water

Applicant

Bosch Thermotechnik GmbH
Junkersstraße 20 - 24
73249 Wernau
Germany

Certification Body

DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Alboinstr. 56
12103 Berlin
Germany

Bosch Compress 3000 AWS-8 M

Configure model
Model name
Bosch Compress 3000 AWS-8 M
Model-ID (internal)
011-1W0135-3
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz
Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.41 kW

3.99 kW

El input

1.13 kW

1.47 kW

COP

4.80

2.72

Indoor water flow rate

0.95 m³/h

0.44 m³/h

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

37 dB(A)

37 dB(A)

Sound power level outdoor

65 dB(A)

65 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

150 %

125 %

Prated

7.00 kW

6.00 kW

SCOP

3.83

3.20

Tbiv

-10 °C

-10 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

6.40 kW

5.30 kW

COP Tj = -7°C

2.65

2.11

Cdh

n/a

n/a

Pdh Tj = +2°C

3.90 kW

3.20 kW

COP Tj = +2°C

3.61

3.10

Cdh

n/a

n/a

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.71

4.70

Cdh

n/a

n/a

Pdh Tj = 12°C

3.60 kW

3.60 kW

COP Tj = 12°C

5.71

5.00

Cdh

n/a

n/a

Pdh Tj = Tbiv

7.20 kW

6.00 kW

COP Tj = Tbiv

2.51

1.90

Pdh Tj = TOL

5.70 kW

4.90 kW

COP Tj = TOL

2.41

2.00

WTOL

57 °C

57 °C

Poff

11 W

11 W

PTO

51 W

51 W

PSB

11 W

11 W

PCK

100 W

100 W

Supplementary Heater: Type of energy input

Electric

Electric

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3879 kWh

3890 kWh

Domestic Hot Water (DHW)
Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

105 %

COP

2.49

Heating up time

02:08 h:min

Standby power input

44.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

257 l

Back