4,500 kg
Chauffage
EN 14511-2
Basse température
Moyenne température
Puissance thermique
35.00 kW
33.62 kW
Puissance électrique absorbée
7.11 kW
10.19 kW
COP
4.92
3.30
Climat plus froid
EN 12102-1
Basse température
Moyenne température
Puissance acoustique extérieure
61 dB(A)
61 dB(A)
EN 14825
Basse température
Moyenne température
ηs
194 %
146 %
Prated
25.52 kW
24.62 kW
SCOP
4.92
3.72
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
15.45 kW
14.90 kW
COP Tj = -7°C
4.13
3.04
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
12.60 kW
12.27 kW
COP Tj = +2°C
6.43
4.89
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
11.57 kW
11.13 kW
COP Tj = +7°C
8.04
6.22
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
11.15 kW
10.89 kW
COP Tj = 12°C
10.58
8.88
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
20.82 kW
20.09 kW
COP Tj = Tbiv
2.79
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.11 kW
16.27 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.24
1.57
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Chauffage d'appoint: type d'énergie utilisée
L'électricité
L'électricité
Chauffage d'appoint: PSUP
8.00 kW
8.00 kW
Consommation annuelle d'électricité QHE
12798 kWh
16325 kWh
Pdh Tj = -15°C (if TOL<-20°C)
20.82
20.09
COP Tj = -15°C (if TOL<-20°C)
2.79
2.06
Cdh Tj = -15 °C
0.900
0.900
Climat moyen
EN 12102-1
Basse température
Moyenne température
Puissance acoustique extérieure
61 dB(A)
61 dB(A)
EN 14825
Basse température
Moyenne température
ηs
226 %
164 %
Prated
29.00 kW
27.73 kW
SCOP
5.71
4.17
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
25.65 kW
24.53 kW
COP Tj = -7°C
3.26
2.35
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
15.61 kW
14.93 kW
COP Tj = +2°C
5.86
4.21
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
11.41 kW
10.90 kW
COP Tj = +7°C
7.43
5.53
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
11.15 kW
10.78 kW
COP Tj = 12°C
10.58
8.20
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
25.65 kW
24.53 kW
COP Tj = Tbiv
3.26
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
23.46 kW
22.36 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.95
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Chauffage d'appoint: type d'énergie utilisée
L'électricité
L'électricité
Chauffage d'appoint: PSUP
5.20 kW
5.20 kW
Consommation annuelle d'électricité QHE
10497 kWh
13736 kWh
Chauffage
EN 14511-2
Basse température
Moyenne température
Puissance thermique
40.00 kW
37.50 kW
Puissance électrique absorbée
8.48 kW
12.02 kW
COP
4.72
3.12
Climat plus froid
EN 12102-1
Basse température
Moyenne température
Puissance acoustique extérieure
61 dB(A)
61 dB(A)
EN 14825
Basse température
Moyenne température
ηs
198 %
145 %
Prated
29.25 kW
28.23 kW
SCOP
5.03
3.72
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.70 kW
17.09 kW
COP Tj = -7°C
3.97
2.98
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
12.92 kW
12.60 kW
COP Tj = +2°C
6.99
4.92
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
11.60 kW
11.10 kW
COP Tj = +7°C
8.03
6.30
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
11.12 kW
10.87 kW
COP Tj = 12°C
10.50
8.83
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
23.86 kW
23.03 kW
COP Tj = Tbiv
2.68
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
19.63 kW
18.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.16
1.53
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Chauffage d'appoint: type d'énergie utilisée
L'électricité
L'électricité
Chauffage d'appoint: PSUP
9.00 kW
9.00 kW
Consommation annuelle d'électricité QHE
14344 kWh
18728 kWh
Pdh Tj = -15°C (if TOL<-20°C)
23.86
23.03
COP Tj = -15°C (if TOL<-20°C)
2.68
1.98
Cdh Tj = -15 °C
0.900
0.900
Climat moyen
EN 12102-1
Basse température
Moyenne température
Puissance acoustique extérieure
61 dB(A)
61 dB(A)
EN 14825
Basse température
Moyenne température
ηs
219 %
162 %
Prated
33.25 kW
31.69 kW
SCOP
5.55
4.14
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
29.42 kW
28.04 kW
COP Tj = -7°C
3.10
2.23
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
17.90 kW
17.07 kW
COP Tj = +2°C
5.61
4.16
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
11.51 kW
10.97 kW
COP Tj = +7°C
7.40
5.60
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
11.12 kW
10.74 kW
COP Tj = 12°C
10.50
8.14
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
29.42 kW
28.04 kW
COP Tj = Tbiv
3.10
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
26.96 kW
25.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
65 °C
65 °C
Poff
24 W
24 W
PTO
31 W
31 W
PSB
24 W
24 W
PCK
35 W
35 W
Chauffage d'appoint: type d'énergie utilisée
L'électricité
L'électricité
Chauffage d'appoint: PSUP
5.80 kW
5.80 kW
Consommation annuelle d'électricité QHE
12369 kWh
15830 kWh