4,100 kg
Brine/Water Heat Pump
Chauffage
EN 14511-2
Basse température
Moyenne température
COP
4.60
2.90
Climat plus chaud
EN 14825
Basse température
Moyenne température
ηs
202 %
169 %
Prated
21.00 kW
20.40 kW
SCOP
5.25
4.42
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
21.00 kW
20.40 kW
COP Tj = +2°C
4.60
2.90
Cdh Tj = +2 °C
Pdh Tj = +7°C
21.63 kW
21.83 kW
COP Tj = +7°C
5.06
3.86
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.26 kW
23.87 kW
COP Tj = 12°C
5.57
5.37
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.00 kW
20.40 kW
COP Tj = Tbiv
4.60
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.00 kW
20.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.60
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Climat plus froid
EN 14825
Basse température
Moyenne température
ηs
206 %
174 %
Prated
21.00 kW
20.40 kW
SCOP
5.35
4.54
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
21.84 kW
22.24 kW
COP Tj = -7°C
5.24
4.09
Cdh Tj = -7 °C
Pdh Tj = +2°C
22.26 kW
23.46 kW
COP Tj = +2°C
5.47
4.96
Cdh Tj = +2 °C
Pdh Tj = +7°C
22.47 kW
24.28 kW
COP Tj = +7°C
5.70
5.63
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.68 kW
24.89 kW
COP Tj = 12°C
5.80
6.09
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.00 kW
20.40 kW
COP Tj = Tbiv
4.60
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.00 kW
20.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.60
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Climat moyen
EN 14825
Basse température
Moyenne température
ηs
201 %
167 %
Prated
21.00 kW
20.40 kW
SCOP
5.23
4.38
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
21.21 kW
21.01 kW
COP Tj = -7°C
4.69
3.16
Cdh Tj = -7 °C
Pdh Tj = +2°C
21.84 kW
22.64 kW
COP Tj = +2°C
5.24
4.35
Cdh Tj = +2 °C
Pdh Tj = +7°C
22.26 kW
23.46 kW
COP Tj = +7°C
5.47
5.10
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.68 kW
24.48 kW
COP Tj = 12°C
5.80
5.97
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.00 kW
20.40 kW
COP Tj = Tbiv
4.60
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.00 kW
20.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.60
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Water/Water Heat Pump
Chauffage
EN 14511-2
Basse température
Moyenne température
COP
5.50
3.52
Climat plus chaud
EN 14825
Basse température
Moyenne température
ηs
241 %
195 %
Prated
25.90 kW
25.56 kW
SCOP
6.22
5.08
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
25.90 kW
25.56 kW
COP Tj = +2°C
5.55
3.52
Cdh Tj = +2 °C
Pdh Tj = +7°C
26.53 kW
26.99 kW
COP Tj = +7°C
6.00
4.48
Cdh Tj = +7 °C
Pdh Tj = 12°C
27.16 kW
29.03 kW
COP Tj = 12°C
6.51
5.99
Cdh Tj = +12 °C
Pdh Tj = Tbiv
25.90 kW
25.56 kW
COP Tj = Tbiv
5.55
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.90 kW
25.56 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.55
3.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Climat plus froid
EN 14825
Basse température
Moyenne température
ηs
244 %
197 %
Prated
25.90 kW
25.56 kW
SCOP
6.29
5.12
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
26.74 kW
27.40 kW
COP Tj = -7°C
6.19
4.71
Cdh Tj = -7 °C
Pdh Tj = +2°C
27.16 kW
28.62 kW
COP Tj = +2°C
6.42
5.58
Cdh Tj = +2 °C
Pdh Tj = +7°C
27.37 kW
29.44 kW
COP Tj = +7°C
6.64
6.25
Cdh Tj = +7 °C
Pdh Tj = 12°C
27.58 kW
30.05 kW
COP Tj = 12°C
6.74
6.71
Cdh Tj = +12 °C
Pdh Tj = Tbiv
25.90 kW
25.56 kW
COP Tj = Tbiv
5.55
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.90 kW
25.56 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.55
3.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Climat moyen
EN 14825
Basse température
Moyenne température
ηs
240 %
193 %
Prated
25.90 kW
25.56 kW
SCOP
6.20
5.03
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
26.11 kW
26.17 kW
COP Tj = -7°C
5.64
3.78
Cdh Tj = -7 °C
Pdh Tj = +2°C
26.74 kW
27.80 kW
COP Tj = +2°C
6.19
4.97
Cdh Tj = +2 °C
Pdh Tj = +7°C
27.16 kW
28.62 kW
COP Tj = +7°C
6.42
5.72
Cdh Tj = +7 °C
Pdh Tj = 12°C
27.58 kW
29.64 kW
COP Tj = 12°C
6.74
6.59
Cdh Tj = +12 °C
Pdh Tj = Tbiv
25.90 kW
25.56 kW
COP Tj = Tbiv
5.55
3.52
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.90 kW
25.56 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.55
3.53
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W