10,000 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
70.20 kW
65.90 kW
Entrada EI
17.95 kW
24.05 kW
COP
3.91
2.74
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
69 dB(A)
69 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
185 %
142 %
Prated
52.45 kW
49.63 kW
SCOP
4.70
3.63
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
46.40 kW
43.90 kW
COP Tj = -7°C
2.67
1.97
Cdh Tj = -7 °C
Pdh Tj = +2°C
28.10 kW
26.70 kW
COP Tj = +2°C
4.74
3.63
Cdh Tj = +2 °C
Pdh Tj = +7°C
24.20 kW
22.80 kW
COP Tj = +7°C
6.68
5.30
Cdh Tj = +7 °C
Pdh Tj = 12°C
27.20 kW
26.00 kW
COP Tj = 12°C
8.02
7.04
Cdh Tj = +12 °C
Pdh Tj = Tbiv
46.40 kW
43.90 kW
COP Tj = Tbiv
2.67
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.30 kW
48.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.53
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
35 °C
55 °C
Poff
180 W
180 W
PTO
310 W
310 W
PSB
180 W
180 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
2.15 kW
1.63 kW
Consumo annual de energia QHE
23112 kWh
28300 kWh
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
84.40 kW
76.50 kW
Entrada EI
22.57 kW
29.77 kW
COP
3.74
2.57
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
69 dB(A)
69 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
179 %
141 %
Prated
61.27 kW
55.05 kW
SCOP
4.54
3.60
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
54.20 kW
48.70 kW
COP Tj = -7°C
2.53
1.90
Cdh Tj = -7 °C
Pdh Tj = +2°C
34.40 kW
29.00 kW
COP Tj = +2°C
4.51
3.59
Cdh Tj = +2 °C
Pdh Tj = +7°C
24.20 kW
22.80 kW
COP Tj = +7°C
6.68
5.30
Cdh Tj = +7 °C
Pdh Tj = 12°C
27.20 kW
26.00 kW
COP Tj = 12°C
8.02
7.04
Cdh Tj = +12 °C
Pdh Tj = Tbiv
54.20 kW
48.70 kW
COP Tj = Tbiv
2.53
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.30 kW
48.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.53
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
35 °C
55 °C
Poff
180 W
180 W
PTO
370 W
370 W
PSB
180 W
180 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
10.97 kW
7.05 kW
Consumo annual de energia QHE
27948 kWh
31660 kWh