4,900 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
40.10 kW
37.00 kW
Entrada EI
10.23 kW
13.65 kW
COP
3.92
2.71
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
68 dB(A)
68 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
177 %
139 %
Prated
29.05 kW
27.02 kW
SCOP
4.51
3.54
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
25.70 kW
23.90 kW
COP Tj = -7°C
2.67
1.95
Cdh Tj = -7 °C
Pdh Tj = +2°C
15.60 kW
14.90 kW
COP Tj = +2°C
4.56
3.55
Cdh Tj = +2 °C
Pdh Tj = +7°C
12.30 kW
11.60 kW
COP Tj = +7°C
6.23
5.03
Cdh Tj = +7 °C
Pdh Tj = 12°C
13.80 kW
13.20 kW
COP Tj = 12°C
7.43
6.60
Cdh Tj = +12 °C
Pdh Tj = Tbiv
25.70 kW
23.90 kW
COP Tj = Tbiv
2.67
1.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.80 kW
24.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
35 °C
55 °C
Poff
110 W
110 W
PTO
180 W
180 W
PSB
110 W
110 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
3.25 kW
2.52 kW
Consumo annual de energia QHE
13341 kWh
15800 kWh
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
46.80 kW
42.90 kW
Entrada EI
12.60 kW
16.70 kW
COP
3.71
2.57
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
68 dB(A)
68 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
175 %
137 %
Prated
33.69 kW
30.07 kW
SCOP
4.45
3.51
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
29.80 kW
26.60 kW
COP Tj = -7°C
2.56
1.90
Cdh Tj = -7 °C
Pdh Tj = +2°C
17.70 kW
16.80 kW
COP Tj = +2°C
4.47
3.52
Cdh Tj = +2 °C
Pdh Tj = +7°C
12.30 kW
11.60 kW
COP Tj = +7°C
6.23
5.03
Cdh Tj = +7 °C
Pdh Tj = 12°C
13.80 kW
13.20 kW
COP Tj = 12°C
7.43
6.60
Cdh Tj = +12 °C
Pdh Tj = Tbiv
29.80 kW
26.60 kW
COP Tj = Tbiv
2.56
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.80 kW
24.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.52
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
35 °C
55 °C
Poff
110 W
110 W
PTO
200 W
200 W
PSB
110 W
110 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
7.89 kW
5.57 kW
Consumo annual de energia QHE
15675 kWh
17735 kWh