1,300 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
12.00 kW
Entrada EI
2.53 kW
3.64 kW
COP
4.75
3.30
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
55 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
265 %
192 %
Prated
12.20 kW
12.40 kW
SCOP
6.71
4.87
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.04 kW
11.84 kW
COP Tj = +2°C
3.54
2.64
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.90 kW
7.97 kW
COP Tj = +7°C
5.66
4.07
Cdh Tj = +7 °C
0.989
0.992
Pdh Tj = 12°C
4.32 kW
4.11 kW
COP Tj = 12°C
8.90
6.57
Cdh Tj = +12 °C
0.969
0.976
Pdh Tj = Tbiv
7.90 kW
7.97 kW
COP Tj = Tbiv
5.66
4.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.04 kW
11.84 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.54
2.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.16 kW
0.60 kW
Consumo annual de energia QHE
2431 kWh
3400 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
55 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
167 %
132 %
Prated
11.40 kW
11.20 kW
SCOP
4.25
3.38
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.95 kW
6.71 kW
COP Tj = -7°C
3.41
2.83
Cdh Tj = -7 °C
0.993
0.994
Pdh Tj = +2°C
4.11 kW
4.13 kW
COP Tj = +2°C
5.00
3.89
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
3.74 kW
3.55 kW
COP Tj = +7°C
7.26
5.48
Cdh Tj = +7 °C
0.971
0.977
Pdh Tj = 12°C
4.25 kW
4.15 kW
COP Tj = 12°C
8.24
7.32
Cdh Tj = +12 °C
0.971
0.974
Pdh Tj = Tbiv
9.33 kW
9.14 kW
COP Tj = Tbiv
2.67
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.68 kW
9.44 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.12
1.75
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.70 kW
1.80 kW
Consumo annual de energia QHE
6610 kWh
8168 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.33
9.14
COP Tj = -15°C (if TOL<-20°C)
2.67
2.07
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
55 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
187 %
147 %
Prated
11.70 kW
11.20 kW
SCOP
4.75
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.37 kW
9.91 kW
COP Tj = -7°C
3.11
2.37
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
6.20 kW
6.23 kW
COP Tj = +2°C
4.25
3.47
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
4.22 kW
3.99 kW
COP Tj = +7°C
7.04
5.21
Cdh Tj = +7 °C
0.975
0.980
Pdh Tj = 12°C
4.31 kW
4.20 kW
COP Tj = 12°C
8.81
6.85
Cdh Tj = +12 °C
0.969
0.976
Pdh Tj = Tbiv
10.37 kW
9.91 kW
COP Tj = Tbiv
3.11
2.37
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.83 kW
10.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.90 kW
0.80 kW
Consumo annual de energia QHE
5093 kWh
6177 kWh
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
14.00 kW
14.00 kW
Entrada EI
3.01 kW
4.38 kW
COP
4.65
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
253 %
188 %
Prated
14.60 kW
14.30 kW
SCOP
6.40
4.78
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.45 kW
12.98 kW
COP Tj = +2°C
3.59
2.58
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
9.40 kW
9.25 kW
COP Tj = +7°C
5.72
4.01
Cdh Tj = +7 °C
0.991
0.993
Pdh Tj = 12°C
4.29 kW
4.16 kW
COP Tj = 12°C
9.01
6.60
Cdh Tj = +12 °C
0.968
0.976
Pdh Tj = Tbiv
9.40 kW
9.25 kW
COP Tj = Tbiv
5.72
4.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.45 kW
12.98 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
2.20 kW
1.30 kW
Consumo annual de energia QHE
3046 kWh
3994 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
164 %
132 %
Prated
13.50 kW
13.10 kW
SCOP
4.18
3.37
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.04 kW
8.02 kW
COP Tj = -7°C
3.43
2.76
Cdh Tj = -7 °C
0.994
0.995
Pdh Tj = +2°C
5.05 kW
4.88 kW
COP Tj = +2°C
4.94
3.91
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.71 kW
3.55 kW
COP Tj = +7°C
7.28
5.65
Cdh Tj = +7 °C
0.971
0.976
Pdh Tj = 12°C
4.35 kW
4.15 kW
COP Tj = 12°C
8.64
7.05
Cdh Tj = +12 °C
0.970
0.975
Pdh Tj = Tbiv
11.13 kW
10.75 kW
COP Tj = Tbiv
2.49
2.17
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.59 kW
9.29 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.20
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
2.90 kW
3.80 kW
Consumo annual de energia QHE
7952 kWh
9569 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.13
10.75
COP Tj = -15°C (if TOL<-20°C)
2.49
2.17
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
146 %
Prated
13.60 kW
13.10 kW
SCOP
4.68
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.09 kW
11.66 kW
COP Tj = -7°C
2.82
2.33
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
7.28 kW
7.34 kW
COP Tj = +2°C
4.33
3.44
Cdh Tj = +2 °C
0.991
0.993
Pdh Tj = +7°C
4.89 kW
4.72 kW
COP Tj = +7°C
7.07
5.46
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
4.28 kW
4.18 kW
COP Tj = 12°C
8.43
6.82
Cdh Tj = +12 °C
0.970
0.976
Pdh Tj = Tbiv
12.09 kW
11.66 kW
COP Tj = Tbiv
2.82
2.33
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.51 kW
9.26 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
4.10 kW
3.80 kW
Consumo annual de energia QHE
6010 kWh
7248 kWh
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
15.00 kW
Entrada EI
3.33 kW
4.76 kW
COP
4.50
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
247 %
187 %
Prated
14.80 kW
14.60 kW
SCOP
6.24
4.76
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.53 kW
12.93 kW
COP Tj = +2°C
3.46
2.56
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
9.52 kW
9.43 kW
COP Tj = +7°C
5.62
3.96
Cdh Tj = +7 °C
0.991
0.994
Pdh Tj = 12°C
4.27 kW
4.17 kW
COP Tj = 12°C
8.72
6.70
Cdh Tj = +12 °C
0.969
0.976
Pdh Tj = Tbiv
9.52 kW
9.43 kW
COP Tj = Tbiv
5.62
3.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.53 kW
12.93 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.46
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
2.30 kW
1.70 kW
Consumo annual de energia QHE
3170 kWh
4102 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
167 %
130 %
Prated
13.50 kW
13.30 kW
SCOP
4.26
3.32
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.10 kW
8.08 kW
COP Tj = -7°C
3.41
2.81
Cdh Tj = -7 °C
0.994
0.995
Pdh Tj = +2°C
5.12 kW
4.72 kW
COP Tj = +2°C
5.23
3.83
Cdh Tj = +2 °C
0.985
0.988
Pdh Tj = +7°C
3.63 kW
3.49 kW
COP Tj = +7°C
6.94
5.41
Cdh Tj = +7 °C
0.971
0.977
Pdh Tj = 12°C
4.29 kW
4.24 kW
COP Tj = 12°C
8.63
7.39
Cdh Tj = +12 °C
0.970
0.974
Pdh Tj = Tbiv
11.14 kW
10.99 kW
COP Tj = Tbiv
2.53
2.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.52 kW
9.44 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
3.00 kW
3.90 kW
Consumo annual de energia QHE
7813 kWh
9867 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.14
10.99
COP Tj = -15°C (if TOL<-20°C)
2.53
2.00
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
189 %
145 %
Prated
13.90 kW
13.50 kW
SCOP
4.79
3.69
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.36 kW
11.97 kW
COP Tj = -7°C
2.88
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
8.14 kW
7.50 kW
COP Tj = +2°C
4.49
3.44
Cdh Tj = +2 °C
0.992
0.993
Pdh Tj = +7°C
5.11 kW
4.90 kW
COP Tj = +7°C
7.06
5.17
Cdh Tj = +7 °C
0.979
0.984
Pdh Tj = 12°C
4.33 kW
4.23 kW
COP Tj = 12°C
8.80
7.04
Cdh Tj = +12 °C
0.970
0.975
Pdh Tj = Tbiv
12.36 kW
11.97 kW
COP Tj = Tbiv
2.88
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.87 kW
9.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
4.00 kW
3.90 kW
Consumo annual de energia QHE
5989 kWh
7561 kWh