1,300 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
5.45 kW
4.04 kW
Entrada EI
0.98 kW
1.26 kW
COP
5.56
3.21
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 14825
Baja temperatura
Media temperatura
ηs
243 %
177 %
Prated
9.00 kW
9.00 kW
SCOP
6.16
4.51
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.30 kW
9.43 kW
COP Tj = +2°C
3.66
2.49
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
5.75 kW
5.99 kW
COP Tj = +7°C
6.19
4.07
Cdh Tj = +7 °C
0.950
0.970
Pdh Tj = 12°C
5.43 kW
5.16 kW
COP Tj = 12°C
7.99
6.23
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.30 kW
9.43 kW
COP Tj = Tbiv
3.66
2.49
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.30 kW
9.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.66
2.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
65 °C
65 °C
Poff
50 W
50 W
PTO
87 W
87 W
PSB
90 W
90 W
PCK
64 W
64 W
Calentador suplementario: tipo de energía de entrada
Electricidad
n/a
Consumo annual de energia QHE
2017 kWh
2791 kWh
Clima frío
EN 14825
Baja temperatura
Media temperatura
ηs
172 %
129 %
Prated
8.00 kW
7.00 kW
SCOP
4.38
3.31
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.53 kW
5.22 kW
COP Tj = -7°C
3.85
2.75
Cdh Tj = -7 °C
0.990
0.970
Pdh Tj = +2°C
4.68 kW
4.81 kW
COP Tj = +2°C
4.95
4.12
Cdh Tj = +2 °C
0.980
0.960
Pdh Tj = +7°C
4.75 kW
4.55 kW
COP Tj = +7°C
6.90
5.56
Cdh Tj = +7 °C
0.970
0.940
Pdh Tj = 12°C
5.37 kW
5.30 kW
COP Tj = 12°C
8.13
7.13
Cdh Tj = +12 °C
0.970
0.930
Pdh Tj = Tbiv
7.96 kW
6.77 kW
COP Tj = Tbiv
2.15
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.96 kW
6.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.15
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.980
WTOL
65 °C
65 °C
Poff
50 W
50 W
PTO
87 W
87 W
PSB
90 W
90 W
PCK
64 W
64 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Consumo annual de energia QHE
4477 kWh
5049 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.19
5.38
COP Tj = -15°C (if TOL<-20°C)
2.90
2.04
Cdh Tj = -15 °C
0.990
0.980
Clima medio
EN 14825
Baja temperatura
Media temperatura
ηs
196 %
152 %
Prated
9.00 kW
9.00 kW
SCOP
4.97
3.88
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.75 kW
8.43 kW
COP Tj = -7°C
3.41
2.28
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
4.47 kW
4.63 kW
COP Tj = +2°C
4.83
3.91
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
4.90 kW
4.64 kW
COP Tj = +7°C
6.69
5.21
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
5.58 kW
5.24 kW
COP Tj = 12°C
8.26
6.81
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
9.13 kW
9.39 kW
COP Tj = Tbiv
2.90
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.13 kW
9.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
65 °C
65 °C
Poff
50 W
50 W
PTO
87 W
87 W
PSB
90 W
90 W
PCK
64 W
64 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Consumo annual de energia QHE
3794 kWh
5003 kWh