1,400 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
7.95 kW
8.04 kW
Entrada EI
1.57 kW
2.49 kW
COP
5.07
3.23
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
1.77 kW
1.08 kW
Cooling capacity
5.48
5.57
EER
3.10
5.14
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
5.50 kW
5.50 kW
SEER
4.80
7.09
Pdc Tj = 35°C
5.48 kW
5.57 kW
EER Tj = 35°C
3.10
5.14
Cdc Tj = 35 °C
1.000
0.990
Pdc Tj = 30°C
4.05 kW
4.02 kW
EER Tj = 30°C
4.21
6.58
Cdc Tj = 30 °C
0.990
0.990
Pdc Tj = 25°C
2.57 kW
2.60 kW
EER Tj = 25°C
5.04
7.66
Cdc Tj = 25 °C
0.980
0.980
Pdc Tj = 20°C
1.58 kW
1.94 kW
EER Tj = 20°C
6.02
7.70
Cdc Tj = 20 °C
0.970
0.970
Poff
8 W
8 W
PTO
8 W
8 W
PSB
8 W
8 W
PCK
8 W
8 W
Consumo annual de enertía QCE
720 kWh
498 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
41 dB(A)
43 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
297 %
196 %
Prated
7.00 kW
7.00 kW
SCOP
7.57
5.00
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.71 kW
6.96 kW
COP Tj = +2°C
3.79
2.76
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
4.48 kW
4.43 kW
COP Tj = +7°C
6.46
4.19
Cdh Tj = +7 °C
0.989
0.993
Pdh Tj = 12°C
2.08 kW
1.95 kW
COP Tj = 12°C
9.72
6.51
Cdh Tj = +12 °C
0.963
0.973
Pdh Tj = Tbiv
7.71 kW
6.96 kW
COP Tj = Tbiv
3.79
2.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.71 kW
6.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.79
2.76
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
8 W
8 W
PSB
8 W
8 W
PCK
8 W
8 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
1248 kWh
1883 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
41 dB(A)
43 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
196 %
144 %
Prated
7.50 kW
7.50 kW
SCOP
4.98
3.68
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.46 kW
4.61 kW
COP Tj = -7°C
3.89
2.94
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
2.78 kW
2.78 kW
COP Tj = +2°C
6.26
4.47
Cdh Tj = +2 °C
0.980
0.987
Pdh Tj = +7°C
1.90 kW
1.88 kW
COP Tj = +7°C
8.59
6.14
Cdh Tj = +7 °C
0.964
0.974
Pdh Tj = 12°C
2.11 kW
1.94 kW
COP Tj = 12°C
10.22
8.03
Cdh Tj = +12 °C
0.961
0.967
Pdh Tj = Tbiv
6.16 kW
6.10 kW
COP Tj = Tbiv
2.84
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.05 kW
5.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.38
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
8 W
8 W
PSB
8 W
8 W
PCK
8 W
8 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.45 kW
2.07 kW
Consumo annual de energia QHE
3715 kWh
5028 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.16
6.10
COP Tj = -15°C (if TOL<-20°C)
2.84
2.19
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
41 dB(A)
43 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
233 %
160 %
Prated
6.50 kW
6.50 kW
SCOP
5.91
4.08
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.44 kW
5.73 kW
COP Tj = -7°C
3.51
2.50
Cdh Tj = -7 °C
0.995
0.997
Pdh Tj = +2°C
3.37 kW
3.45 kW
COP Tj = +2°C
5.75
3.93
Cdh Tj = +2 °C
0.986
0.991
Pdh Tj = +7°C
2.23 kW
2.24 kW
COP Tj = +7°C
7.85
5.31
Cdh Tj = +7 °C
0.972
0.981
Pdh Tj = 12°C
2.11 kW
1.91 kW
COP Tj = 12°C
10.22
7.42
Cdh Tj = +12 °C
0.961
0.969
Pdh Tj = Tbiv
6.48 kW
6.43 kW
COP Tj = Tbiv
3.07
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.48 kW
6.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.07
2.19
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
8 W
8 W
PSB
8 W
8 W
PCK
8 W
8 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
2277 kWh
3295 kWh