1,200 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
2.60 kW
2.16 kW
Cooling capacity
9.10
10.80
EER
3.50
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
9.10 kW
10.80 kW
SEER
5.45
6.97
Pdc Tj = 35°C
9.10 kW
10.80 kW
EER Tj = 35°C
3.53
5.14
Cdc Tj = 35 °C
0.995
0.994
Pdc Tj = 30°C
6.78 kW
8.05 kW
EER Tj = 30°C
4.65
6.37
Cdc Tj = 30 °C
0.991
0.990
Pdc Tj = 25°C
4.41 kW
5.02 kW
EER Tj = 25°C
6.18
7.55
Cdc Tj = 25 °C
0.982
0.980
Pdc Tj = 20°C
3.56 kW
4.18 kW
EER Tj = 20°C
7.04
8.56
Cdc Tj = 20 °C
0.974
0.973
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1001 kWh
930 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
234 %
180 %
Prated
9.73 kW
8.33 kW
SCOP
5.93
4.57
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.62
3.06
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.45
3.96
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.62
3.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.62
3.06
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2190 kWh
2433 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
150 %
127 %
Prated
16.08 kW
13.76 kW
SCOP
3.83
3.25
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
5.11
4.14
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.61
5.42
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10350 kWh
10442 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
191 %
152 %
Prated
11.00 kW
9.42 kW
SCOP
4.86
3.87
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.73 kW
8.33 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.72
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
6.16
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4694 kWh
5022 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:55 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
35 dB(A)
35 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
3.55 kW
2.60 kW
Cooling capacity
11.00
12.20
EER
3.10
4.70
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
11.00 kW
12.20 kW
SEER
5.43
6.82
Pdc Tj = 35°C
11.00 kW
12.20 kW
EER Tj = 35°C
3.21
4.71
Cdc Tj = 35 °C
0.996
0.995
Pdc Tj = 30°C
8.16 kW
9.20 kW
EER Tj = 30°C
4.67
6.03
Cdc Tj = 30 °C
0.993
0.991
Pdc Tj = 25°C
5.29 kW
5.82 kW
EER Tj = 25°C
6.10
7.58
Cdc Tj = 25 °C
0.985
0.983
Pdc Tj = 20°C
3.62 kW
4.18 kW
EER Tj = 20°C
7.18
8.34
Cdc Tj = 20 °C
0.974
0.974
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Consumo annual de enertía QCE
1215 kWh
1074 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
168 %
Prated
11.06 kW
10.25 kW
SCOP
5.56
4.28
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.32
2.47
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
5.19
3.80
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.32
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.32
2.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2655 kWh
3201 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
144 %
122 %
Prated
18.27 kW
16.93 kW
SCOP
3.67
3.13
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
5.01
4.13
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
6.15
5.15
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12270 kWh
13340 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
42 dB(A)
42 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
184 %
151 %
Prated
12.50 kW
11.59 kW
SCOP
4.67
3.86
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.06 kW
10.25 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.54
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
6.15
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5533 kWh
6195 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
L
Eficiencia ηdhw
131 %
COP
3.10
Tiempo de calentamiento
00:50 h:min
Entrada de alimentación ( stand By )
38.0 W
Temperatura de referencia ACS
52.5 °C
Mezcla de agua a 40ºC
233 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
222 %
171 %
Prated
9.73 kW
8.33 kW
SCOP
5.63
4.35
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.44
2.91
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.18
3.76
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.44
2.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.44
2.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2307 kWh
2558 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
146 %
124 %
Prated
16.08 kW
13.76 kW
SCOP
3.73
3.17
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.10 kW
8.49 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
4.85
3.93
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.28
5.15
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
10.10 kW
8.49 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10613 kWh
10714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
182 %
151 %
Prated
11.00 kW
9.42 kW
SCOP
4.62
3.84
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.90 kW
8.58 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.49
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
5.85
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.90 kW
8.58 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4921 kWh
5065 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
XL
Eficiencia ηdhw
124 %
COP
3.00
Tiempo de calentamiento
01:13 h:min
Entrada de alimentación ( stand By )
29.0 W
Temperatura de referencia ACS
47.4 °C
Mezcla de agua a 40ºC
201 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
12.00 kW
7.70 kW
Entrada EI
2.50 kW
2.41 kW
COP
4.80
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
222 %
171 %
Prated
9.73 kW
8.33 kW
SCOP
5.63
4.35
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
9.73 kW
8.33 kW
COP Tj = +2°C
3.44
2.91
Cdh Tj = +2 °C
0.995
0.995
Pdh Tj = +7°C
6.29 kW
5.47 kW
COP Tj = +7°C
5.18
3.76
Cdh Tj = +7 °C
0.989
0.991
Pdh Tj = 12°C
3.47 kW
3.51 kW
COP Tj = 12°C
6.97
5.60
Cdh Tj = +12 °C
0.974
0.979
Pdh Tj = Tbiv
9.73 kW
8.33 kW
COP Tj = Tbiv
3.44
2.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.73 kW
8.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.44
2.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.995
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2307 kWh
2558 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
146 %
124 %
Prated
16.08 kW
13.76 kW
SCOP
3.73
3.17
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.10 kW
8.49 kW
COP Tj = -7°C
3.39
2.86
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
5.71 kW
5.15 kW
COP Tj = +2°C
4.85
3.93
Cdh Tj = +2 °C
0.988
0.990
Pdh Tj = +7°C
3.79 kW
3.37 kW
COP Tj = +7°C
6.28
5.15
Cdh Tj = +7 °C
0.977
0.979
Pdh Tj = 12°C
3.85 kW
3.69 kW
COP Tj = 12°C
8.34
7.00
Cdh Tj = +12 °C
0.972
0.975
Pdh Tj = Tbiv
10.10 kW
8.49 kW
COP Tj = Tbiv
3.39
2.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.98 kW
6.11 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
9.09 kW
7.65 kW
Consumo annual de energia QHE
10613 kWh
10714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.72
7.95
COP Tj = -15°C (if TOL<-20°C)
2.49
1.95
Cdh Tj = -15 °C
0.996
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
182 %
151 %
Prated
11.00 kW
9.42 kW
SCOP
4.62
3.84
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
9.90 kW
8.58 kW
COP Tj = -7°C
3.16
2.44
Cdh Tj = -7 °C
0.996
0.996
Pdh Tj = +2°C
6.10 kW
5.26 kW
COP Tj = +2°C
4.49
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.00 kW
3.37 kW
COP Tj = +7°C
5.85
5.09
Cdh Tj = +7 °C
0.980
0.981
Pdh Tj = 12°C
3.75 kW
3.69 kW
COP Tj = 12°C
7.65
6.48
Cdh Tj = +12 °C
0.973
0.977
Pdh Tj = Tbiv
9.90 kW
8.58 kW
COP Tj = Tbiv
3.16
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.81 kW
9.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.19 kW
0.37 kW
Consumo annual de energia QHE
4921 kWh
5065 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
XL
Eficiencia ηdhw
124 %
COP
3.00
Tiempo de calentamiento
01:13 h:min
Entrada de alimentación ( stand By )
29.0 W
Temperatura de referencia ACS
47.4 °C
Mezcla de agua a 40ºC
201 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
209 %
161 %
Prated
11.06 kW
10.25 kW
SCOP
5.30
4.09
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.16
2.35
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
4.93
3.61
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.16
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.16
2.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2786 kWh
3345 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
140 %
119 %
Prated
18.27 kW
16.93 kW
SCOP
3.58
3.05
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.29 kW
10.17 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
4.76
3.93
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
5.85
4.89
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.29 kW
10.17 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12586 kWh
13687 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
175 %
150 %
Prated
12.50 kW
11.59 kW
SCOP
4.46
3.83
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.22 kW
10.39 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.31
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
5.84
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.22 kW
10.39 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5796 kWh
6243 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
XL
Eficiencia ηdhw
123 %
COP
3.00
Tiempo de calentamiento
01:08 h:min
Entrada de alimentación ( stand By )
29.0 W
Temperatura de referencia ACS
47.4 °C
Mezcla de agua a 40ºC
202 l
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
15.00 kW
9.50 kW
Entrada EI
3.49 kW
3.02 kW
COP
4.30
3.15
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
209 %
161 %
Prated
11.06 kW
10.25 kW
SCOP
5.30
4.09
Tbiv
2 °C
2 °C
TOL
-25 °C
-25 °C
Pdh Tj = +2°C
11.06 kW
10.25 kW
COP Tj = +2°C
3.16
2.35
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
7.03 kW
6.56 kW
COP Tj = +7°C
4.93
3.61
Cdh Tj = +7 °C
0.990
0.992
Pdh Tj = 12°C
3.47 kW
3.50 kW
COP Tj = 12°C
6.41
5.21
Cdh Tj = +12 °C
0.976
0.981
Pdh Tj = Tbiv
11.06 kW
10.25 kW
COP Tj = Tbiv
3.16
2.35
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.06 kW
10.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.16
2.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
kW
kW
Consumo annual de energia QHE
2786 kWh
3345 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
140 %
119 %
Prated
18.27 kW
16.93 kW
SCOP
3.58
3.05
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.29 kW
10.17 kW
COP Tj = -7°C
3.21
2.69
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.65 kW
6.21 kW
COP Tj = +2°C
4.76
3.93
Cdh Tj = +2 °C
0.990
0.991
Pdh Tj = +7°C
4.25 kW
3.98 kW
COP Tj = +7°C
5.85
4.89
Cdh Tj = +7 °C
0.981
0.983
Pdh Tj = 12°C
3.65 kW
3.58 kW
COP Tj = 12°C
7.16
6.22
Cdh Tj = +12 °C
0.975
0.977
Pdh Tj = Tbiv
11.29 kW
10.17 kW
COP Tj = Tbiv
3.21
2.69
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.63 kW
6.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.64 kW
10.04 kW
Consumo annual de energia QHE
12586 kWh
13687 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.60
8.99
COP Tj = -15°C (if TOL<-20°C)
2.31
1.87
Cdh Tj = -15 °C
0.997
0.997
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
45 dB(A)
45 dB(A)
Potencia sonora de la unidad exterior
57 dB(A)
57 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
175 %
150 %
Prated
12.50 kW
11.59 kW
SCOP
4.46
3.83
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
11.22 kW
10.39 kW
COP Tj = -7°C
2.96
2.30
Cdh Tj = -7 °C
0.997
0.997
Pdh Tj = +2°C
6.79 kW
6.28 kW
COP Tj = +2°C
4.31
3.84
Cdh Tj = +2 °C
0.991
0.992
Pdh Tj = +7°C
4.36 kW
3.93 kW
COP Tj = +7°C
5.84
5.10
Cdh Tj = +7 °C
0.982
0.983
Pdh Tj = 12°C
3.56 kW
3.52 kW
COP Tj = 12°C
7.33
6.09
Cdh Tj = +12 °C
0.973
0.978
Pdh Tj = Tbiv
11.22 kW
10.39 kW
COP Tj = Tbiv
2.96
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.78 kW
9.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.997
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
1.72 kW
1.64 kW
Consumo annual de energia QHE
5796 kWh
6243 kWh
Agua caliente sanitaria
Clima medio
EN 16147
Perfil de carga declarado
XL
Eficiencia ηdhw
123 %
COP
3.00
Tiempo de calentamiento
01:08 h:min
Entrada de alimentación ( stand By )
29.0 W
Temperatura de referencia ACS
47.4 °C
Mezcla de agua a 40ºC
202 l