15,000 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
106.90 kW
105.79 kW
Entrada EI
20.09 kW
30.58 kW
COP
5.32
3.46
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
44.16 kW
26.05 kW
Cooling capacity
121.01
120.33
EER
2.74
4.62
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
121.00 kW
120.00 kW
SEER
5.50
8.18
Pdc Tj = 35°C
121.01 kW
120.33 kW
EER Tj = 35°C
2.74
4.62
Cdc Tj = 35 °C
0.999
0.998
Pdc Tj = 30°C
89.30 kW
88.48 kW
EER Tj = 30°C
4.22
6.47
Cdc Tj = 30 °C
0.998
0.996
Pdc Tj = 25°C
57.17 kW
57.47 kW
EER Tj = 25°C
6.09
9.10
Cdc Tj = 25 °C
0.995
0.992
Pdc Tj = 20°C
38.00 kW
43.79 kW
EER Tj = 20°C
8.52
11.25
Cdc Tj = 20 °C
0.988
0.987
Poff
52 W
52 W
PTO
52 W
52 W
PSB
52 W
52 W
PCK
52 W
52 W
Consumo annual de enertía QCE
13423 kWh
9018 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
56 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
302 %
216 %
Prated
129.00 kW
128.00 kW
SCOP
7.64
5.48
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
128.72 kW
127.94 kW
COP Tj = +2°C
3.43
2.48
Cdh Tj = +2 °C
0.999
0.999
Pdh Tj = +7°C
82.90 kW
82.19 kW
COP Tj = +7°C
6.23
4.45
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
41.52 kW
39.57 kW
COP Tj = 12°C
10.53
7.55
Cdh Tj = +12 °C
0.987
0.990
Pdh Tj = Tbiv
128.72 kW
127.94 kW
COP Tj = Tbiv
3.43
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
128.72 kW
127.94 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.43
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
52 W
52 W
PTO
52 W
52 W
PSB
52 W
52 W
PCK
52 W
52 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
22623 kWh
31288 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
56 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
193 %
149 %
Prated
124.70 kW
125.00 kW
SCOP
4.89
3.80
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
75.65 kW
74.97 kW
COP Tj = -7°C
3.99
3.06
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
45.46 kW
45.57 kW
COP Tj = +2°C
6.13
4.76
Cdh Tj = +2 °C
0.993
0.995
Pdh Tj = +7°C
37.73 kW
37.22 kW
COP Tj = +7°C
8.56
6.56
Cdh Tj = +7 °C
0.988
0.991
Pdh Tj = 12°C
41.39 kW
40.41 kW
COP Tj = 12°C
10.04
8.53
Cdh Tj = +12 °C
0.987
0.989
Pdh Tj = Tbiv
101.74 kW
103.83 kW
COP Tj = Tbiv
2.70
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
81.26 kW
84.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.66
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
52 W
52 W
PTO
52 W
52 W
PSB
52 W
52 W
PCK
52 W
52 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
43.40 kW
40.20 kW
Consumo annual de energia QHE
62827 kWh
81016 kWh
Pdh Tj = -15°C (if TOL<-20°C)
101.74
103.83
COP Tj = -15°C (if TOL<-20°C)
2.70
2.05
Cdh Tj = -15 °C
0.999
0.999
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
55 dB(A)
56 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
229 %
171 %
Prated
106.00 kW
106.70 kW
SCOP
5.80
4.34
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
93.52 kW
93.91 kW
COP Tj = -7°C
3.38
2.47
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
57.58 kW
57.55 kW
COP Tj = +2°C
5.48
4.22
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
38.03 kW
37.20 kW
COP Tj = +7°C
8.34
5.90
Cdh Tj = +7 °C
0.989
0.992
Pdh Tj = 12°C
41.83 kW
40.27 kW
COP Tj = 12°C
10.27
7.90
Cdh Tj = +12 °C
0.987
0.990
Pdh Tj = Tbiv
106.04 kW
106.73 kW
COP Tj = Tbiv
2.87
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
106.04 kW
106.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
52 W
52 W
PTO
52 W
52 W
PSB
52 W
52 W
PCK
52 W
52 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE