0,700 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
4.40 kW
4.40 kW
Entrada EI
0.85 kW
1.36 kW
COP
5.17
3.24
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima medio
EN 14825
Baja temperatura
Media temperatura
ηs
210.4 %
156.7 %
Prated
5.30 kW
4.90 kW
SCOP
5.34
3.99
Tbiv
-7.00 °C
-7.00 °C
TOL
-10.00 °C
-10.00 °C
Pdh Tj = -7°C
4.64 kW
4.42 kW
COP Tj = -7°C
3.40
2.59
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
2.89 kW
2.72 kW
COP Tj = +2°C
5.29
3.94
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
2.73 kW
2.55 kW
COP Tj = +7°C
6.74
4.94
Cdh Tj = +7 °C
0.98
1.00
Pdh Tj = 12°C
3.14 kW
3.01 kW
COP Tj = 12°C
8.54
6.44
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
4.64 kW
4.42 kW
COP Tj = Tbiv
3.40
2.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
4.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.01
2.27
WTOL
75.00 °C
75.00 °C
Poff
8.70 W
8.70 W
PTO
10.00 W
10.00 W
PSB
8.70 W
8.70 W
PCK
0.00 W
0.00 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.10 kW
Consumo annual de energia QHE
2052 kWh
2535 kWh
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
6.26 kW
6.10 kW
Entrada EI
1.28 kW
1.91 kW
COP
4.89
3.20
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Clima medio
EN 14825
Baja temperatura
Media temperatura
ηs
205.8 %
152.9 %
Prated
6.40 kW
6.10 kW
SCOP
5.22
3.90
Tbiv
-7.00 °C
-7.00 °C
TOL
-10.00 °C
-10.00 °C
Pdh Tj = -7°C
5.63 kW
5.40 kW
COP Tj = -7°C
3.04
2.40
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.70 kW
3.13 kW
COP Tj = +2°C
5.20
3.79
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
2.74 kW
2.58 kW
COP Tj = +7°C
6.95
5.15
Cdh Tj = +7 °C
0.98
1.00
Pdh Tj = 12°C
3.14 kW
3.02 kW
COP Tj = 12°C
8.64
6.53
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.63 kW
5.40 kW
COP Tj = Tbiv
3.04
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.76 kW
5.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.25
WTOL
75.00 °C
75.00 °C
Poff
8.70 W
8.70 W
PTO
10.00 W
10.00 W
PSB
8.70 W
8.70 W
PCK
0.00 W
0.00 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.64 kW
0.73 kW
Consumo annual de energia QHE
2533 kWh
3233 kWh