3,750 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
26.77 kW
26.49 kW
Entrada EI
5.02 kW
7.63 kW
COP
5.33
3.47
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
aprobado
Starting and operating test
aprobado
Refrigeración
EN 14511-2
+7°C/+12°C
+18°C/+23°C
Entrada EI
30.30 kW
30.13 kW
Cooling capacity
11.02
6.51
EER
2.75
4.63
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
30.00 kW
30.00 kW
SEER
5.51
8.20
Pdc Tj = 35°C
30.30 kW
30.13 kW
EER Tj = 35°C
2.75
4.63
Cdc Tj = 35 °C
0.999
0.998
Pdc Tj = 30°C
22.37 kW
22.17 kW
EER Tj = 30°C
4.23
6.48
Cdc Tj = 30 °C
0.998
0.996
Pdc Tj = 25°C
14.34 kW
14.41 kW
EER Tj = 25°C
6.11
9.13
Cdc Tj = 25 °C
0.995
0.992
Pdc Tj = 20°C
9.55 kW
11.00 kW
EER Tj = 20°C
8.56
11.30
Cdc Tj = 20 °C
0.988
0.987
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Consumo annual de enertía QCE
3316 kWh
2246 kWh
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
49 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
303 %
216 %
Prated
32.20 kW
32.00 kW
SCOP
7.66
5.50
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
32.22 kW
32.02 kW
COP Tj = +2°C
3.44
2.48
Cdh Tj = +2 °C
0.999
0.999
Pdh Tj = +7°C
20.77 kW
20.60 kW
COP Tj = +7°C
6.24
4.46
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
10.43 kW
9.94 kW
COP Tj = 12°C
10.57
7.59
Cdh Tj = +12 °C
0.987
0.990
Pdh Tj = Tbiv
32.22 kW
32.02 kW
COP Tj = Tbiv
3.44
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
32.22 kW
32.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.44
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
5632 kWh
7796 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
49 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
193 %
150 %
Prated
30.90 kW
31.00 kW
SCOP
4.91
3.82
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
18.96 kW
18.79 kW
COP Tj = -7°C
4.00
3.07
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
11.41 kW
11.44 kW
COP Tj = +2°C
6.15
4.78
Cdh Tj = +2 °C
0.993
0.995
Pdh Tj = +7°C
9.48 kW
9.35 kW
COP Tj = +7°C
8.60
6.59
Cdh Tj = +7 °C
0.988
0.991
Pdh Tj = 12°C
10.39 kW
10.15 kW
COP Tj = 12°C
10.09
8.57
Cdh Tj = +12 °C
0.987
0.989
Pdh Tj = Tbiv
25.48 kW
26.01 kW
COP Tj = Tbiv
2.71
2.06
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.36 kW
21.25 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.26
1.67
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
10.54 kW
9.75 kW
Consumo annual de energia QHE
15514 kWh
20008 kWh
Pdh Tj = -15°C (if TOL<-20°C)
25.48
26.01
COP Tj = -15°C (if TOL<-20°C)
2.71
2.06
Cdh Tj = -15 °C
0.999
0.999
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad exterior
49 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
230 %
171 %
Prated
26.50 kW
26.50 kW
SCOP
5.82
4.36
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
23.43 kW
23.52 kW
COP Tj = -7°C
3.39
2.48
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
14.44 kW
14.43 kW
COP Tj = +2°C
5.50
4.42
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
9.55 kW
9.35 kW
COP Tj = +7°C
8.38
5.93
Cdh Tj = +7 °C
0.989
0.992
Pdh Tj = 12°C
10.51 kW
10.12 kW
COP Tj = 12°C
10.31
7.94
Cdh Tj = +12 °C
0.987
0.990
Pdh Tj = Tbiv
26.56 kW
26.73 kW
COP Tj = Tbiv
2.88
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
26.56 kW
26.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
75 °C
75 °C
Poff
13 W
13 W
PTO
13 W
13 W
PSB
13 W
13 W
PCK
13 W
13 W
Calentador suplementario: tipo de energía de entrada
Electricidad
Electricidad
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
9406 kWh
12562 kWh