4,400 kg
Calefacción
EN 14511-2
Baja temperatura
Media temperatura
Salida calefacción
26.71 kW
22.39 kW
Entrada EI
5.81 kW
7.52 kW
COP
4.60
2.98
EN 14511-4
cortando la trasferencia de calor de caudal medio
aprobado
Fallo completo de alimentación eléctrica
aprobado
Test de desescarche
erróneo
Starting and operating test
aprobado
Clima cálido
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
48 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
220 %
167 %
Prated
38.06 kW
35.62 kW
SCOP
5.70
4.38
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
38.06 kW
35.62 kW
COP Tj = +2°C
4.29
2.95
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
24.47 kW
22.90 kW
COP Tj = +7°C
5.35
3.89
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
12.71 kW
12.48 kW
COP Tj = 12°C
6.31
5.17
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
8920 kWh
10862 kWh
Clima frío
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
48 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
226 %
174 %
Prated
38.06 kW
35.62 kW
SCOP
5.86
4.55
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
23.04 kW
21.56 kW
COP Tj = -7°C
5.57
4.12
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
14.02 kW
13.12 kW
COP Tj = +2°C
6.27
5.02
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
12.71 kW
12.56 kW
COP Tj = +7°C
6.35
5.32
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
12.70 kW
12.65 kW
COP Tj = 12°C
6.19
5.49
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
16014 kWh
19290 kWh
Pdh Tj = -15°C (if TOL<-20°C)
38.06
35.62
COP Tj = -15°C (if TOL<-20°C)
4.29
2.95
Cdh Tj = -15 °C
0.90
0.90
Clima medio
EN 12102-1
Baja temperatura
Media temperatura
Potencia sonora de la unidad interior
48 dB(A)
50 dB(A)
EN 14825
Baja temperatura
Media temperatura
ηs
218 %
168 %
Prated
38.06 kW
35.62 kW
SCOP
5.65
4.39
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
33.67 kW
31.51 kW
COP Tj = -7°C
4.56
3.21
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
20.49 kW
19.18 kW
COP Tj = +2°C
5.68
4.39
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
13.18 kW
12.33 kW
COP Tj = +7°C
6.28
5.16
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
12.70 kW
12.57 kW
COP Tj = 12°C
6.31
5.34
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
38.06 kW
35.62 kW
COP Tj = Tbiv
4.29
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.06 kW
35.62 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.29
2.95
WTOL
65 °C
65 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Calentador suplementario: tipo de energía de entrada
n/a
n/a
Calentador suplementario: PSUP
0.00 kW
0.00 kW
Consumo annual de energia QHE
13917 kWh
16768 kWh