Certificate holders

Subtype

SWCV 62 Inverter

Certificate Holder
ait-deutschland GmbH
Industriestr. 3
95359 Kasendorf
Germany
Registration number
041-K001-12
Certification Body
BRE Global Limited
Subtype title
SWCV 62 Inverter
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R407c
Mass of Refrigerant

1,160 kg

Certification Date
12.05.2017
Testing basis
HP Keymark Scheme Transition Rules
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

SWCV 62(H)(K)3
Configure model
Model name
SWCV 62(H)(K)3
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh

SWCV 62H1
Configure model
Model name
SWCV 62H1
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh

WZSV 62(H)(K)3M
Configure model
Model name
WZSV 62(H)(K)3M
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh

PWZSV 62H3S
Configure model
Model name
PWZSV 62H3S
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh

PWZSV 62H2S
Configure model
Model name
PWZSV 62H2S
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh

PWZSV 62H1S
Configure model
Model name
PWZSV 62H1S
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

2.95 kW

El input

0.68 kW

0.94 kW

COP

4.86

3.13

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

151 %

Prated

5.50 kW

5.50 kW

SCOP

5.24

3.97

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

5.40 kW

5.40 kW

COP Tj = +2°C

4.15

2.84

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

3.60 kW

3.60 kW

COP Tj = +7°C

5.00

3.59

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.70 kW

1.70 kW

COP Tj = 12°C

6.15

4.86

Cdh Tj = +12 °C

1.00

1.00

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1402 kWh

1851 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

157 %

Prated

5.50 kW

5.50 kW

SCOP

5.46

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

3.40 kW

3.40 kW

COP Tj = -7°C

5.17

3.77

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

2.10 kW

2.10 kW

COP Tj = +2°C

5.91

4.51

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

1.40 kW

1.40 kW

COP Tj = +7°C

6.36

5.12

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.54

4.81

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2482 kWh

3288 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

150 %

Prated

5.50 kW

5.50 kW

SCOP

5.18

3.95

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.00 kW

5.00 kW

COP Tj = -7°C

4.37

3.06

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

3.10 kW

3.00 kW

COP Tj = +2°C

5.24

3.97

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

2.00 kW

2.00 kW

COP Tj = +7°C

5.92

4.63

Cdh Tj = +7 °C

1.00

1.00

Pdh Tj = 12°C

1.30 kW

1.20 kW

COP Tj = 12°C

5.95

4.86

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

5.40 kW

5.40 kW

COP Tj = Tbiv

4.15

2.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.40 kW

5.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.15

2.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.00

1.00

WTOL

65 °C

65 °C

Poff

2 W

2 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

9 W

9 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2192 kWh

2878 kWh