6,300 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
34.97 kW
31.56 kW
El input
7.76 kW
11.04 kW
COP
4.51
2.86
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
157 %
Prated
59.64 kW
55.34 kW
SCOP
5.28
4.13
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
59.64 kW
55.34 kW
COP Tj = +2°C
3.93
2.77
Pdh Tj = +7°C
38.34 kW
35.58 kW
COP Tj = +7°C
5.00
3.69
Pdh Tj = 12°C
17.04 kW
15.81 kW
COP Tj = 12°C
5.79
4.85
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15055 kWh
17857 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
160 %
Prated
59.64 kW
55.34 kW
SCOP
5.29
4.20
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
35.77 kW
33.80 kW
COP Tj = -7°C
5.14
3.85
Pdh Tj = +2°C
21.97 kW
20.39 kW
COP Tj = +2°C
5.71
4.59
Pdh Tj = +7°C
16.74 kW
16.35 kW
COP Tj = +7°C
5.86
4.85
Pdh Tj = 12°C
16.58 kW
16.38 kW
COP Tj = 12°C
5.58
4.88
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
27759 kWh
32491 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
155 %
Prated
59.64 kW
55.34 kW
SCOP
5.19
4.07
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.76 kW
48.96 kW
COP Tj = -7°C
4.26
3.01
Pdh Tj = +2°C
32.11 kW
29.80 kW
COP Tj = +2°C
5.23
4.11
Pdh Tj = +7°C
20.64 kW
19.16 kW
COP Tj = +7°C
5.74
4.84
Pdh Tj = 12°C
16.56 kW
16.33 kW
COP Tj = 12°C
5.58
4.66
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
23714 kWh
28063 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
48.57 kW
43.13 kW
El input
8.51 kW
11.59 kW
COP
5.71
3.72
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
207 %
Prated
51.32 kW
53.23 kW
SCOP
6.83
5.38
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
51.32 kW
53.23 kW
COP Tj = +2°C
5.35
3.65
Pdh Tj = +7°C
32.99 kW
34.22 kW
COP Tj = +7°C
6.59
4.90
Pdh Tj = 12°C
21.67 kW
21.11 kW
COP Tj = 12°C
7.37
6.21
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
10032 kWh
13221 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
272 %
215 %
Prated
51.32 kW
53.23 kW
SCOP
6.99
5.57
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
31.06 kW
32.22 kW
COP Tj = -7°C
6.78
5.15
Pdh Tj = +2°C
21.66 kW
19.61 kW
COP Tj = +2°C
7.37
6.08
Pdh Tj = +7°C
21.70 kW
21.22 kW
COP Tj = +7°C
7.45
6.37
Pdh Tj = 12°C
21.65 kW
21.36 kW
COP Tj = 12°C
7.34
6.60
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
18086 kWh
23548 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
206 %
Prated
51.32 kW
53.23 kW
SCOP
6.80
5.35
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
45.39 kW
47.08 kW
COP Tj = -7°C
5.63
3.98
Pdh Tj = +2°C
27.63 kW
28.66 kW
COP Tj = +2°C
6.92
5.43
Pdh Tj = +7°C
21.64 kW
21.02 kW
COP Tj = +7°C
7.32
6.08
Pdh Tj = 12°C
21.70 kW
21.25 kW
COP Tj = 12°C
7.45
6.43
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15600 kWh
20546 kWh
Brine/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
34.97 kW
31.56 kW
El input
7.76 kW
11.04 kW
COP
4.51
2.86
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
157 %
Prated
59.64 kW
55.34 kW
SCOP
5.28
4.13
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
59.64 kW
55.34 kW
COP Tj = +2°C
3.93
2.77
Pdh Tj = +7°C
38.34 kW
35.58 kW
COP Tj = +7°C
5.00
3.69
Pdh Tj = 12°C
17.04 kW
15.81 kW
COP Tj = 12°C
5.79
4.85
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15055 kWh
17857 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
160 %
Prated
59.64 kW
55.34 kW
SCOP
5.29
4.20
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
35.77 kW
33.80 kW
COP Tj = -7°C
5.14
3.85
Pdh Tj = +2°C
21.97 kW
20.39 kW
COP Tj = +2°C
5.71
4.59
Pdh Tj = +7°C
16.74 kW
16.35 kW
COP Tj = +7°C
5.86
4.85
Pdh Tj = 12°C
16.58 kW
16.38 kW
COP Tj = 12°C
5.58
4.88
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
27759 kWh
32491 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
155 %
Prated
59.64 kW
55.34 kW
SCOP
5.19
4.07
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
52.76 kW
48.96 kW
COP Tj = -7°C
4.26
3.01
Pdh Tj = +2°C
32.11 kW
29.80 kW
COP Tj = +2°C
5.23
4.11
Pdh Tj = +7°C
20.64 kW
19.16 kW
COP Tj = +7°C
5.74
4.84
Pdh Tj = 12°C
16.56 kW
16.33 kW
COP Tj = 12°C
5.58
4.66
Pdh Tj = Tbiv
59.64 kW
55.34 kW
COP Tj = Tbiv
3.93
2.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.64 kW
55.34 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.93
2.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
23714 kWh
28063 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
48.57 kW
43.13 kW
El input
8.51 kW
11.59 kW
COP
5.71
3.72
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
265 %
207 %
Prated
51.32 kW
53.23 kW
SCOP
6.83
5.38
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
51.32 kW
53.23 kW
COP Tj = +2°C
5.35
3.65
Pdh Tj = +7°C
32.99 kW
34.22 kW
COP Tj = +7°C
6.59
4.90
Pdh Tj = 12°C
21.67 kW
21.11 kW
COP Tj = 12°C
7.37
6.21
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
10032 kWh
13221 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
272 %
215 %
Prated
51.32 kW
53.23 kW
SCOP
6.99
5.57
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
31.06 kW
32.22 kW
COP Tj = -7°C
6.78
5.15
Pdh Tj = +2°C
21.66 kW
19.61 kW
COP Tj = +2°C
7.37
6.08
Pdh Tj = +7°C
21.70 kW
21.22 kW
COP Tj = +7°C
7.45
6.37
Pdh Tj = 12°C
21.65 kW
21.36 kW
COP Tj = 12°C
7.34
6.60
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
18086 kWh
23548 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
206 %
Prated
51.32 kW
53.23 kW
SCOP
6.80
5.35
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
45.39 kW
47.08 kW
COP Tj = -7°C
5.63
3.98
Pdh Tj = +2°C
27.63 kW
28.66 kW
COP Tj = +2°C
6.92
5.43
Pdh Tj = +7°C
21.64 kW
21.02 kW
COP Tj = +7°C
7.32
6.08
Pdh Tj = 12°C
21.70 kW
21.25 kW
COP Tj = 12°C
7.45
6.43
Pdh Tj = Tbiv
51.32 kW
53.23 kW
COP Tj = Tbiv
5.35
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
51.32 kW
53.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.35
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
65 °C
65 °C
Poff
9 W
9 W
PTO
11 W
11 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15600 kWh
20546 kWh