ATRIA R32 Split 16kW

Certificate Holder
TOYOTOMI CO., LTD
5-17
467-0855 Nagoya
Japan
Registration number
041-K130-03
Certification Body
BRE
Subtype title
ATRIA R32 Split 16kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,840 kg

Certification Date
07.10.2026
Testing basis
Heat Pump Keymark Scheme Rules Rev 12
Testing laboratory
SGS-CSTC Standards Technical Services Co., Ltd. Shunde Branch, CN
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

TASOSG16/3R32EH9 / TASISG16/3R32EH9
Configure model
Model name
TASOSG16/3R32EH9 / TASISG16/3R32EH9
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16 kW

16 kW

El input

3.54 kW

5.49 kW

COP

4.52

2.91

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

239 %

171 %

Prated

13.00 kW

14.00 kW

SCOP

6.05

4.35

Tbiv

7 °C

7 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.00 kW

13.20 kW

COP Tj = +2°C

3.34

2.31

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.50 kW

9.00 kW

COP Tj = +7°C

5.20

3.69

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.80 kW

4.10 kW

COP Tj = 12°C

7.95

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

8.50 kW

9.00 kW

COP Tj = Tbiv

5.20

3.69

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.20 kW

13.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.34

2.31

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.80 kW

Annual energy consumption Qhe

2936 kWh

4331 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

121 %

Prated

14 kW

12 kW

SCOP

3.95

3.1

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

9.1 kW

7.7 kW

COP Tj = -7°C

3.3

2.61

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

5 kW

4.5 kW

COP Tj = +2°C

4.88

3.79

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

3.2 kW

3.1 kW

COP Tj = +7°C

5.75

4.87

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

3.7 kW

3.6 kW

COP Tj = 12°C

7.59

6.38

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

11.3 kW

9.6 kW

COP Tj = Tbiv

2.28

1.84

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.8 kW

5.1 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.89

1.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.9

0.9

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.2 kW

6.9 kW

Annual energy consumption Qhe

8667 kWh

9388 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.3

9.6

COP Tj = -15°C (if TOL<-20°C)

2.28

1.84

Cdh Tj = -15 °C

0.9

0.9

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

44 dB(A)

44 dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

134 %

Prated

15 kW

13 kW

SCOP

4.55

3.43

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.5 kW

11.4 kW

COP Tj = -7°C

2.7

2.05

Cdh Tj = -7 °C

0.9

0.9

Pdh Tj = +2°C

8 kW

7.1 kW

COP Tj = +2°C

4.39

3.33

Cdh Tj = +2 °C

0.9

0.9

Pdh Tj = +7°C

5.4 kW

4.5 kW

COP Tj = +7°C

6.33

4.62

Cdh Tj = +7 °C

0.9

0.9

Pdh Tj = 12°C

4.5 kW

3.4 kW

COP Tj = 12°C

8.57

6.12

Cdh Tj = +12 °C

0.9

0.9

Pdh Tj = Tbiv

13.5 kW

11.4 kW

COP Tj = Tbiv

2.7

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.2 kW

11.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.37

1.77

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.9

0.9

WTOL

65 °C

65 °C

Poff

14 W

14 W

PTO

24 W

24 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

6915 kWh

7765 kWh