1,130 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.4 kW
4.09 kW
El input
0.68 kW
1.47 kW
COP
4.99
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
160 %
Prated
4 kW
4 kW
SCOP
6.04
4.08
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.9 kW
4 kW
COP Tj = +2°C
4.18
2.64
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.7 kW
2.4 kW
COP Tj = +7°C
5.62
3.56
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
1.7 kW
2.1 kW
COP Tj = 12°C
7.2
5.18
Cdh Tj = +12 °C
0.93
0.96
Pdh Tj = Tbiv
3.9 kW
4 kW
COP Tj = Tbiv
4.18
2.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.9 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.18
2.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
885 kWh
1309 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
122 %
Prated
4 kW
4 kW
SCOP
4.26
3.13
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.3 kW
2.3 kW
COP Tj = -7°C
3.64
2.64
Cdh Tj = -7 °C
0.97
0.98
Pdh Tj = +2°C
1.9 kW
2.1 kW
COP Tj = +2°C
5.08
3.71
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.18
4.66
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.1
5.6
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
3.5 kW
3.5 kW
COP Tj = Tbiv
2.63
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1 kW
1.1 kW
Annual energy consumption Qhe
2316 kWh
3147 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.2
3.2
COP Tj = -15°C (if TOL<-20°C)
2.83
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
141 %
Prated
4.00 kW
4.00 kW
SCOP
4.99
3.60
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.40 kW
3.60 kW
COP Tj = -7°C
3.22
2.38
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
2.40 kW
2.20 kW
COP Tj = +2°C
5.00
3.52
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.25
4.51
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
7.67
5.92
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
4.30 kW
4.40 kW
COP Tj = Tbiv
2.98
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1699 kWh
2298 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.6 kW
El input
1.04 kW
1.96 kW
COP
4.83
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255 %
172 %
Prated
6 kW
6 kW
SCOP
6.45
4.38
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.6 kW
6.6 kW
COP Tj = +2°C
3.63
2.5
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.9 kW
3.9 kW
COP Tj = +7°C
5.64
3.73
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
1.8 kW
2.1 kW
COP Tj = 12°C
8.22
5.65
Cdh Tj = +12 °C
0.92
0.96
Pdh Tj = Tbiv
5.8 kW
6.6 kW
COP Tj = Tbiv
3.8
2.5
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.5
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0 kW
Annual energy consumption Qhe
1244 kWh
1889 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
129 %
Prated
6 kW
6 kW
SCOP
4.37
3.3
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.6 kW
3.6 kW
COP Tj = -7°C
3.64
2.74
Cdh Tj = -7 °C
0.98
0.99
Pdh Tj = +2°C
2 kW
2.2 kW
COP Tj = +2°C
5.29
4
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.57
4.95
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.48
5.83
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
5.1 kW
5 kW
COP Tj = Tbiv
2.5
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.34 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.7 kW
2 kW
Annual energy consumption Qhe
3386 kWh
4476 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.8
5
COP Tj = -15°C (if TOL<-20°C)
2.7
2.04
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
143 %
Prated
6.00 kW
6.00 kW
SCOP
4.98
3.64
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.00 kW
5.50 kW
COP Tj = -7°C
3.20
2.28
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.10 kW
3.10 kW
COP Tj = +2°C
4.85
3.56
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.41
4.73
Cdh Tj = +7 °C
0.900
1.000
Pdh Tj = 12°C
1.80 kW
2.20 kW
COP Tj = 12°C
8.00
5.94
Cdh Tj = +12 °C
0.900
1.000
Pdh Tj = Tbiv
6.00 kW
5.80 kW
COP Tj = Tbiv
2.77
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.40 kW
Annual energy consumption Qhe
2490 kWh
3406 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.28 kW
6.33 kW
El input
1.42 kW
2.29 kW
COP
4.41
2.77
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
251 %
176 %
Prated
8.00 kW
8.00 kW
SCOP
6.34
4.47
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.60 kW
7.90 kW
COP Tj = +2°C
2.80
2.25
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
5.20 kW
5.30 kW
COP Tj = +7°C
5.51
3.73
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
2.40 kW
2.10 kW
COP Tj = 12°C
8.33
5.94
Cdh Tj = +12 °C
0.94
0.95
Pdh Tj = Tbiv
7.60 kW
7.90 kW
COP Tj = Tbiv
2.80
2.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1685 kWh
2390 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
128 %
Prated
8 kW
8 kW
SCOP
4.27
3.29
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.7 kW
4.8 kW
COP Tj = -7°C
3.52
2.7
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.8 kW
3 kW
COP Tj = +2°C
5.27
4.04
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.1 kW
2.2 kW
COP Tj = +7°C
6.98
5.25
Cdh Tj = +7 °C
0.94
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.86
6.08
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
6.4 kW
6.2 kW
COP Tj = Tbiv
2.49
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.1
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.8 kW
3.1 kW
Annual energy consumption Qhe
4617 kWh
6002 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.4
6.1
COP Tj = -15°C (if TOL<-20°C)
2.49
1.97
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
144 %
Prated
8.00 kW
8.00 kW
SCOP
4.96
3.67
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.70 kW
6.80 kW
COP Tj = -7°C
3.03
2.24
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.90 kW
2.60 kW
COP Tj = +7°C
6.69
4.84
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
8.01
6.27
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
7.70 kW
6.80 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.70 kW
1.30 kW
Annual energy consumption Qhe
3334 kWh
4504 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.4 kW
4.09 kW
El input
0.68 kW
1.47 kW
COP
4.99
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
160 %
Prated
4 kW
4 kW
SCOP
6.04
4.08
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.9 kW
4 kW
COP Tj = +2°C
4.18
2.64
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.7 kW
2.4 kW
COP Tj = +7°C
5.62
3.56
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
1.7 kW
2.1 kW
COP Tj = 12°C
7.2
5.18
Cdh Tj = +12 °C
0.93
0.96
Pdh Tj = Tbiv
3.9 kW
4 kW
COP Tj = Tbiv
4.18
2.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.9 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.18
2.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
885 kWh
1309 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
122 %
Prated
4 kW
4 kW
SCOP
4.26
3.13
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.3 kW
2.3 kW
COP Tj = -7°C
3.64
2.64
Cdh Tj = -7 °C
0.97
0.98
Pdh Tj = +2°C
1.9 kW
2.1 kW
COP Tj = +2°C
5.08
3.71
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.18
4.66
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.1
5.6
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
3.5 kW
3.5 kW
COP Tj = Tbiv
2.63
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1 kW
1.1 kW
Annual energy consumption Qhe
2316 kWh
3147 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.2
3.2
COP Tj = -15°C (if TOL<-20°C)
2.83
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
141 %
Prated
4.00 kW
4.00 kW
SCOP
4.99
3.60
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.40 kW
3.60 kW
COP Tj = -7°C
3.22
2.38
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
2.40 kW
2.20 kW
COP Tj = +2°C
5.00
3.52
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.25
4.51
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
7.67
5.92
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
4.30 kW
4.40 kW
COP Tj = Tbiv
2.98
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1699 kWh
2298 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.6 kW
El input
1.04 kW
1.96 kW
COP
4.83
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255 %
172 %
Prated
6 kW
6 kW
SCOP
6.45
4.38
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.6 kW
6.6 kW
COP Tj = +2°C
3.63
2.5
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.9 kW
3.9 kW
COP Tj = +7°C
5.64
3.73
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
1.8 kW
2.1 kW
COP Tj = 12°C
8.22
5.65
Cdh Tj = +12 °C
0.92
0.96
Pdh Tj = Tbiv
5.8 kW
6.6 kW
COP Tj = Tbiv
3.8
2.5
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.5
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0 kW
Annual energy consumption Qhe
1244 kWh
1889 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
129 %
Prated
6 kW
6 kW
SCOP
4.37
3.3
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.6 kW
3.6 kW
COP Tj = -7°C
3.64
2.74
Cdh Tj = -7 °C
0.98
0.99
Pdh Tj = +2°C
2 kW
2.2 kW
COP Tj = +2°C
5.29
4
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.57
4.95
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.48
5.83
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
5.1 kW
5 kW
COP Tj = Tbiv
2.5
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.34 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.7 kW
2 kW
Annual energy consumption Qhe
3386 kWh
4476 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.8
5
COP Tj = -15°C (if TOL<-20°C)
2.7
2.04
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
143 %
Prated
6.00 kW
6.00 kW
SCOP
4.98
3.64
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.00 kW
5.50 kW
COP Tj = -7°C
3.20
2.28
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.10 kW
3.10 kW
COP Tj = +2°C
4.85
3.56
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.41
4.73
Cdh Tj = +7 °C
0.900
1.000
Pdh Tj = 12°C
1.80 kW
2.20 kW
COP Tj = 12°C
8.00
5.94
Cdh Tj = +12 °C
0.900
1.000
Pdh Tj = Tbiv
6.00 kW
5.80 kW
COP Tj = Tbiv
2.77
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.40 kW
Annual energy consumption Qhe
2490 kWh
3406 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.28 kW
6.33 kW
El input
1.42 kW
2.29 kW
COP
4.41
2.77
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
251 %
176 %
Prated
8.00 kW
8.00 kW
SCOP
6.34
4.47
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.60 kW
7.90 kW
COP Tj = +2°C
2.80
2.25
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
5.20 kW
5.30 kW
COP Tj = +7°C
5.51
3.73
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
2.40 kW
2.10 kW
COP Tj = 12°C
8.33
5.94
Cdh Tj = +12 °C
0.94
0.95
Pdh Tj = Tbiv
7.60 kW
7.90 kW
COP Tj = Tbiv
2.80
2.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1685 kWh
2390 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
128 %
Prated
8 kW
8 kW
SCOP
4.27
3.29
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.7 kW
4.8 kW
COP Tj = -7°C
3.52
2.7
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.8 kW
3 kW
COP Tj = +2°C
5.27
4.04
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.1 kW
2.2 kW
COP Tj = +7°C
6.98
5.25
Cdh Tj = +7 °C
0.94
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.86
6.08
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
6.4 kW
6.2 kW
COP Tj = Tbiv
2.49
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.1
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.8 kW
3.1 kW
Annual energy consumption Qhe
4617 kWh
6002 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.4
6.1
COP Tj = -15°C (if TOL<-20°C)
2.49
1.97
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
144 %
Prated
8.00 kW
8.00 kW
SCOP
4.96
3.67
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.70 kW
6.80 kW
COP Tj = -7°C
3.03
2.24
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.90 kW
2.60 kW
COP Tj = +7°C
6.69
4.84
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
8.01
6.27
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
7.70 kW
6.80 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.70 kW
1.30 kW
Annual energy consumption Qhe
3334 kWh
4504 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
174 %
COP
4.10
Heating up time
2:30 h:min
Standby power input
30.0 W
Reference hot water temperature
51.4 °C
Mixed water at 40°C
240 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
111 %
COP
2.77
Heating up time
2:29 h:min
Standby power input
75.6 W
Reference hot water temperature
51.6 °C
Mixed water at 40°C
253 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
152 %
COP
3.58
Heating up time
2:36 h:min
Standby power input
33.2 W
Reference hot water temperature
51.7 °C
Mixed water at 40°C
253 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.4 kW
4.09 kW
El input
0.68 kW
1.47 kW
COP
4.99
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
160 %
Prated
4 kW
4 kW
SCOP
6.04
4.08
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.9 kW
4 kW
COP Tj = +2°C
4.18
2.64
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.7 kW
2.4 kW
COP Tj = +7°C
5.62
3.56
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
1.7 kW
2.1 kW
COP Tj = 12°C
7.2
5.18
Cdh Tj = +12 °C
0.93
0.96
Pdh Tj = Tbiv
3.9 kW
4 kW
COP Tj = Tbiv
4.18
2.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.9 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.18
2.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
885 kWh
1309 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
122 %
Prated
4 kW
4 kW
SCOP
4.26
3.13
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.3 kW
2.3 kW
COP Tj = -7°C
3.64
2.64
Cdh Tj = -7 °C
0.97
0.98
Pdh Tj = +2°C
1.9 kW
2.1 kW
COP Tj = +2°C
5.08
3.71
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.18
4.66
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.1
5.6
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
3.5 kW
3.5 kW
COP Tj = Tbiv
2.63
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1 kW
1.1 kW
Annual energy consumption Qhe
2316 kWh
3147 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.2
3.2
COP Tj = -15°C (if TOL<-20°C)
2.83
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
141 %
Prated
4.00 kW
4.00 kW
SCOP
4.99
3.60
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.40 kW
3.60 kW
COP Tj = -7°C
3.22
2.38
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
2.40 kW
2.20 kW
COP Tj = +2°C
5.00
3.52
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.25
4.51
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
7.67
5.92
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
4.30 kW
4.40 kW
COP Tj = Tbiv
2.98
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1699 kWh
2298 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.6 kW
El input
1.04 kW
1.96 kW
COP
4.83
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255 %
172 %
Prated
6 kW
6 kW
SCOP
6.45
4.38
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.6 kW
6.6 kW
COP Tj = +2°C
3.63
2.5
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.9 kW
3.9 kW
COP Tj = +7°C
5.64
3.73
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
1.8 kW
2.1 kW
COP Tj = 12°C
8.22
5.65
Cdh Tj = +12 °C
0.92
0.96
Pdh Tj = Tbiv
5.8 kW
6.6 kW
COP Tj = Tbiv
3.8
2.5
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.5
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0 kW
Annual energy consumption Qhe
1244 kWh
1889 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
129 %
Prated
6 kW
6 kW
SCOP
4.37
3.3
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.6 kW
3.6 kW
COP Tj = -7°C
3.64
2.74
Cdh Tj = -7 °C
0.98
0.99
Pdh Tj = +2°C
2 kW
2.2 kW
COP Tj = +2°C
5.29
4
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.57
4.95
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.48
5.83
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
5.1 kW
5 kW
COP Tj = Tbiv
2.5
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.34 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.7 kW
2 kW
Annual energy consumption Qhe
3386 kWh
4476 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.8
5
COP Tj = -15°C (if TOL<-20°C)
2.7
2.04
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
143 %
Prated
6.00 kW
6.00 kW
SCOP
4.98
3.64
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.00 kW
5.50 kW
COP Tj = -7°C
3.20
2.28
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.10 kW
3.10 kW
COP Tj = +2°C
4.85
3.56
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.41
4.73
Cdh Tj = +7 °C
0.900
1.000
Pdh Tj = 12°C
1.80 kW
2.20 kW
COP Tj = 12°C
8.00
5.94
Cdh Tj = +12 °C
0.900
1.000
Pdh Tj = Tbiv
6.00 kW
5.80 kW
COP Tj = Tbiv
2.77
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.40 kW
Annual energy consumption Qhe
2490 kWh
3406 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.28 kW
6.33 kW
El input
1.42 kW
2.29 kW
COP
4.41
2.77
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
251 %
176 %
Prated
8.00 kW
8.00 kW
SCOP
6.34
4.47
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.60 kW
7.90 kW
COP Tj = +2°C
2.80
2.25
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
5.20 kW
5.30 kW
COP Tj = +7°C
5.51
3.73
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
2.40 kW
2.10 kW
COP Tj = 12°C
8.33
5.94
Cdh Tj = +12 °C
0.94
0.95
Pdh Tj = Tbiv
7.60 kW
7.90 kW
COP Tj = Tbiv
2.80
2.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1685 kWh
2390 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
128 %
Prated
8 kW
8 kW
SCOP
4.27
3.29
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.7 kW
4.8 kW
COP Tj = -7°C
3.52
2.7
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.8 kW
3 kW
COP Tj = +2°C
5.27
4.04
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.1 kW
2.2 kW
COP Tj = +7°C
6.98
5.25
Cdh Tj = +7 °C
0.94
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.86
6.08
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
6.4 kW
6.2 kW
COP Tj = Tbiv
2.49
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.1
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.8 kW
3.1 kW
Annual energy consumption Qhe
4617 kWh
6002 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.4
6.1
COP Tj = -15°C (if TOL<-20°C)
2.49
1.97
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
144 %
Prated
8.00 kW
8.00 kW
SCOP
4.96
3.67
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.70 kW
6.80 kW
COP Tj = -7°C
3.03
2.24
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.90 kW
2.60 kW
COP Tj = +7°C
6.69
4.84
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
8.01
6.27
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
7.70 kW
6.80 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.70 kW
1.30 kW
Annual energy consumption Qhe
3334 kWh
4504 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.4 kW
4.09 kW
El input
0.68 kW
1.47 kW
COP
4.99
2.78
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
239 %
160 %
Prated
4 kW
4 kW
SCOP
6.04
4.08
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.9 kW
4 kW
COP Tj = +2°C
4.18
2.64
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.7 kW
2.4 kW
COP Tj = +7°C
5.62
3.56
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
1.7 kW
2.1 kW
COP Tj = 12°C
7.2
5.18
Cdh Tj = +12 °C
0.93
0.96
Pdh Tj = Tbiv
3.9 kW
4 kW
COP Tj = Tbiv
4.18
2.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.9 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.18
2.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
885 kWh
1309 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
122 %
Prated
4 kW
4 kW
SCOP
4.26
3.13
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.3 kW
2.3 kW
COP Tj = -7°C
3.64
2.64
Cdh Tj = -7 °C
0.97
0.98
Pdh Tj = +2°C
1.9 kW
2.1 kW
COP Tj = +2°C
5.08
3.71
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.18
4.66
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.1
5.6
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
3.5 kW
3.5 kW
COP Tj = Tbiv
2.63
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1 kW
1.1 kW
Annual energy consumption Qhe
2316 kWh
3147 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.2
3.2
COP Tj = -15°C (if TOL<-20°C)
2.83
2.07
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
141 %
Prated
4.00 kW
4.00 kW
SCOP
4.99
3.60
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.40 kW
3.60 kW
COP Tj = -7°C
3.22
2.38
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
2.40 kW
2.20 kW
COP Tj = +2°C
5.00
3.52
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.25
4.51
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
7.67
5.92
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
4.30 kW
4.40 kW
COP Tj = Tbiv
2.98
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.98
2.21
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1699 kWh
2298 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.6 kW
El input
1.04 kW
1.96 kW
COP
4.83
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
255 %
172 %
Prated
6 kW
6 kW
SCOP
6.45
4.38
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.6 kW
6.6 kW
COP Tj = +2°C
3.63
2.5
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.9 kW
3.9 kW
COP Tj = +7°C
5.64
3.73
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
1.8 kW
2.1 kW
COP Tj = 12°C
8.22
5.65
Cdh Tj = +12 °C
0.92
0.96
Pdh Tj = Tbiv
5.8 kW
6.6 kW
COP Tj = Tbiv
3.8
2.5
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.5
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0 kW
Annual energy consumption Qhe
1244 kWh
1889 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
129 %
Prated
6 kW
6 kW
SCOP
4.37
3.3
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.6 kW
3.6 kW
COP Tj = -7°C
3.64
2.74
Cdh Tj = -7 °C
0.98
0.99
Pdh Tj = +2°C
2 kW
2.2 kW
COP Tj = +2°C
5.29
4
Cdh Tj = +2 °C
0.96
0.97
Pdh Tj = +7°C
2 kW
2.1 kW
COP Tj = +7°C
6.57
4.95
Cdh Tj = +7 °C
0.95
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.48
5.83
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
5.1 kW
5 kW
COP Tj = Tbiv
2.5
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.34 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.19
1.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.7 kW
2 kW
Annual energy consumption Qhe
3386 kWh
4476 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.8
5
COP Tj = -15°C (if TOL<-20°C)
2.7
2.04
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
143 %
Prated
6.00 kW
6.00 kW
SCOP
4.98
3.64
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.00 kW
5.50 kW
COP Tj = -7°C
3.20
2.28
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.10 kW
3.10 kW
COP Tj = +2°C
4.85
3.56
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.00 kW
2.10 kW
COP Tj = +7°C
6.41
4.73
Cdh Tj = +7 °C
0.900
1.000
Pdh Tj = 12°C
1.80 kW
2.20 kW
COP Tj = 12°C
8.00
5.94
Cdh Tj = +12 °C
0.900
1.000
Pdh Tj = Tbiv
6.00 kW
5.80 kW
COP Tj = Tbiv
2.77
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.00 kW
5.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.02
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.40 kW
Annual energy consumption Qhe
2490 kWh
3406 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.28 kW
6.33 kW
El input
1.42 kW
2.29 kW
COP
4.41
2.77
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
251 %
176 %
Prated
8.00 kW
8.00 kW
SCOP
6.34
4.47
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.60 kW
7.90 kW
COP Tj = +2°C
2.80
2.25
Cdh Tj = +2 °C
0.99
1
Pdh Tj = +7°C
5.20 kW
5.30 kW
COP Tj = +7°C
5.51
3.73
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
2.40 kW
2.10 kW
COP Tj = 12°C
8.33
5.94
Cdh Tj = +12 °C
0.94
0.95
Pdh Tj = Tbiv
7.60 kW
7.90 kW
COP Tj = Tbiv
2.80
2.25
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.80
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1685 kWh
2390 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
33 dB(A)
33 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
128 %
Prated
8 kW
8 kW
SCOP
4.27
3.29
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.7 kW
4.8 kW
COP Tj = -7°C
3.52
2.7
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
2.8 kW
3 kW
COP Tj = +2°C
5.27
4.04
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
2.1 kW
2.2 kW
COP Tj = +7°C
6.98
5.25
Cdh Tj = +7 °C
0.94
0.96
Pdh Tj = 12°C
1.7 kW
1.6 kW
COP Tj = 12°C
7.86
6.08
Cdh Tj = +12 °C
0.93
0.94
Pdh Tj = Tbiv
6.4 kW
6.2 kW
COP Tj = Tbiv
2.49
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.1
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.8 kW
3.1 kW
Annual energy consumption Qhe
4617 kWh
6002 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.4
6.1
COP Tj = -15°C (if TOL<-20°C)
2.49
1.97
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
144 %
Prated
8.00 kW
8.00 kW
SCOP
4.96
3.67
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.70 kW
6.80 kW
COP Tj = -7°C
3.03
2.24
Cdh Tj = -7 °C
1
1
Pdh Tj = +2°C
4.20 kW
4.40 kW
COP Tj = +2°C
4.81
3.58
Cdh Tj = +2 °C
1
1
Pdh Tj = +7°C
2.90 kW
2.60 kW
COP Tj = +7°C
6.69
4.84
Cdh Tj = +7 °C
1
1
Pdh Tj = 12°C
1.70 kW
2.20 kW
COP Tj = 12°C
8.01
6.27
Cdh Tj = +12 °C
0.9
1
Pdh Tj = Tbiv
7.70 kW
6.80 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1
1
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.70 kW
1.30 kW
Annual energy consumption Qhe
3334 kWh
4504 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.40 kW
4.09 kW
El input
0.70 kW
1.49 kW
COP
4.83
2.74
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
145 %
Prated
4.00 kW
4.00 kW
SCOP
5.29
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.90 kW
3.96 kW
COP Tj = +2°C
4.08
2.61
Cdh Tj = +2 °C
0.960
0.980
Pdh Tj = +7°C
2.70 kW
2.37 kW
COP Tj = +7°C
5.38
3.45
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
1.67 kW
2.06 kW
COP Tj = 12°C
6.62
4.92
Cdh Tj = +12 °C
0.900
0.920
Pdh Tj = Tbiv
3.90 kW
3.96 kW
COP Tj = Tbiv
4.08
2.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.90 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.960
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1011 kWh
1446 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
116 %
Prated
4.00 kW
4.00 kW
SCOP
3.99
2.98
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.34 kW
2.29 kW
COP Tj = -7°C
3.52
2.57
Cdh Tj = -7 °C
0.950
0.960
Pdh Tj = +2°C
1.91 kW
2.14 kW
COP Tj = +2°C
4.82
3.58
Cdh Tj = +2 °C
0.910
0.940
Pdh Tj = +7°C
1.96 kW
2.08 kW
COP Tj = +7°C
5.80
4.46
Cdh Tj = +7 °C
0.900
0.930
Pdh Tj = 12°C
1.66 kW
1.55 kW
COP Tj = 12°C
6.53
5.21
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.51 kW
3.48 kW
COP Tj = Tbiv
2.59
1.92
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.14 kW
Annual energy consumption Qhe
2474 kWh
3309 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.25
3.19
COP Tj = -15°C (if TOL<-20°C)
2.77
2.05
Cdh Tj = -15 °C
0.970
0.980
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
133 %
Prated
4.10 kW
4.00 kW
SCOP
4.65
3.39
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.37 kW
3.63 kW
COP Tj = -7°C
3.16
2.35
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
2.42 kW
2.15 kW
COP Tj = +2°C
4.84
3.41
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
2.02 kW
2.14 kW
COP Tj = +7°C
5.92
4.34
Cdh Tj = +7 °C
0.910
0.930
Pdh Tj = 12°C
1.72 kW
2.19 kW
COP Tj = 12°C
7.11
5.66
Cdh Tj = +12 °C
0.900
0.920
Pdh Tj = Tbiv
4.30 kW
4.38 kW
COP Tj = Tbiv
2.94
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.94
2.19
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
33 W
33 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1822 kWh
2439 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.60 kW
El input
1.07 kW
1.98 kW
COP
4.71
2.83
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
160 %
Prated
6.00 kW
6.20 kW
SCOP
5.80
4.09
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.62 kW
6.58 kW
COP Tj = +2°C
3.56
2.48
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.92 kW
3.89 kW
COP Tj = +7°C
5.46
3.65
Cdh Tj = +7 °C
0.950
0.970
Pdh Tj = 12°C
1.77 kW
2.11 kW
COP Tj = 12°C
7.50
5.36
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
5.82 kW
6.58 kW
COP Tj = Tbiv
3.72
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.56
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.00 kW
Annual energy consumption Qhe
1382 kWh
2027 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
124 %
Prated
6.00 kW
6.00 kW
SCOP
4.16
3.19
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.60 kW
3.58 kW
COP Tj = -7°C
3.56
2.69
Cdh Tj = -7 °C
0.970
0.970
Pdh Tj = +2°C
2.00 kW
2.19 kW
COP Tj = +2°C
5.01
3.86
Cdh Tj = +2 °C
0.910
0.940
Pdh Tj = +7°C
2.01 kW
2.12 kW
COP Tj = +7°C
6.16
4.72
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.70 kW
1.57 kW
COP Tj = 12°C
6.86
5.42
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.07 kW
5.02 kW
COP Tj = Tbiv
2.47
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.35 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.16
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.65 kW
2.04 kW
Annual energy consumption Qhe
3559 kWh
4642 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.83
5.02
COP Tj = -15°C (if TOL<-20°C)
2.66
2.03
Cdh Tj = -15 °C
0.980
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
6.00 kW
6.00 kW
SCOP
4.69
3.49
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.01 kW
5.48 kW
COP Tj = -7°C
3.15
2.26
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
3.12 kW
3.10 kW
COP Tj = +2°C
4.69
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.99 kW
2.09 kW
COP Tj = +7°C
6.01
4.52
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.76 kW
2.16 kW
COP Tj = 12°C
7.32
5.62
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.04 kW
5.75 kW
COP Tj = Tbiv
2.73
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.04 kW
5.57 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.73
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.43 kW
Annual energy consumption Qhe
2643 kWh
3556 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.29 kW
6.33 kW
El input
1.46 kW
2.31 kW
COP
4.31
2.74
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
231 %
166 %
Prated
8.20 kW
8.00 kW
SCOP
5.85
4.22
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.62 kW
7.88 kW
COP Tj = +2°C
2.76
2.24
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.22 kW
5.30 kW
COP Tj = +7°C
5.35
3.68
Cdh Tj = +7 °C
0.960
0.980
Pdh Tj = 12°C
2.39 kW
2.15 kW
COP Tj = 12°C
7.77
5.62
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
7.62 kW
7.88 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.24
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1873 kWh
2533 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
162 %
125 %
Prated
8.00 kW
8.00 kW
SCOP
4.11
3.20
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.75 kW
4.83 kW
COP Tj = -7°C
3.46
2.67
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
2.85 kW
2.98 kW
COP Tj = +2°C
5.07
3.93
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
2.05 kW
2.16 kW
COP Tj = +7°C
6.53
5.00
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.74 kW
1.59 kW
COP Tj = 12°C
7.19
5.64
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.42 kW
6.23 kW
COP Tj = Tbiv
2.46
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
3.15 kW
Annual energy consumption Qhe
4793 kWh
6169 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.42
6.06
COP Tj = -15°C (if TOL<-20°C)
2.46
1.96
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
139 %
Prated
8.00 kW
8.00 kW
SCOP
4.75
3.55
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.66 kW
6.84 kW
COP Tj = -7°C
2.98
2.23
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
4.15 kW
4.35 kW
COP Tj = +2°C
4.71
3.53
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.87 kW
2.62 kW
COP Tj = +7°C
6.44
4.69
Cdh Tj = +7 °C
0.920
0.940
Pdh Tj = 12°C
1.73 kW
2.21 kW
COP Tj = 12°C
7.37
5.95
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
7.72 kW
6.84 kW
COP Tj = Tbiv
2.72
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.34 kW
6.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.61
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.66 kW
1.27 kW
Annual energy consumption Qhe
3477 kWh
4654 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.40 kW
4.09 kW
El input
0.70 kW
1.49 kW
COP
4.83
2.74
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
145 %
Prated
4.00 kW
4.00 kW
SCOP
5.29
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.90 kW
3.96 kW
COP Tj = +2°C
4.08
2.61
Cdh Tj = +2 °C
0.960
0.980
Pdh Tj = +7°C
2.70 kW
2.37 kW
COP Tj = +7°C
5.38
3.45
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
1.67 kW
2.06 kW
COP Tj = 12°C
6.62
4.92
Cdh Tj = +12 °C
0.900
0.920
Pdh Tj = Tbiv
3.90 kW
3.96 kW
COP Tj = Tbiv
4.08
2.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.90 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.08
2.61
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.960
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1011 kWh
1446 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
116 %
Prated
4.00 kW
4.00 kW
SCOP
3.99
2.98
Tbiv
-17 °C
-17 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
2.34 kW
2.29 kW
COP Tj = -7°C
3.52
2.57
Cdh Tj = -7 °C
0.950
0.960
Pdh Tj = +2°C
1.91 kW
2.14 kW
COP Tj = +2°C
4.82
3.58
Cdh Tj = +2 °C
0.910
0.940
Pdh Tj = +7°C
1.96 kW
2.08 kW
COP Tj = +7°C
5.80
4.46
Cdh Tj = +7 °C
0.900
0.930
Pdh Tj = 12°C
1.66 kW
1.55 kW
COP Tj = 12°C
6.53
5.21
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
3.51 kW
3.48 kW
COP Tj = Tbiv
2.59
1.92
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.96 kW
2.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.22
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.04 kW
1.14 kW
Annual energy consumption Qhe
2474 kWh
3309 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.25
3.19
COP Tj = -15°C (if TOL<-20°C)
2.77
2.05
Cdh Tj = -15 °C
0.970
0.980
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
133 %
Prated
4.10 kW
4.00 kW
SCOP
4.65
3.39
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.37 kW
3.63 kW
COP Tj = -7°C
3.16
2.35
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
2.42 kW
2.15 kW
COP Tj = +2°C
4.84
3.41
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
2.02 kW
2.14 kW
COP Tj = +7°C
5.92
4.34
Cdh Tj = +7 °C
0.910
0.930
Pdh Tj = 12°C
1.72 kW
2.19 kW
COP Tj = 12°C
7.11
5.66
Cdh Tj = +12 °C
0.900
0.920
Pdh Tj = Tbiv
4.30 kW
4.38 kW
COP Tj = Tbiv
2.94
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.30 kW
4.38 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.94
2.19
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.980
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
33 W
33 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1822 kWh
2439 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.01 kW
5.60 kW
El input
1.07 kW
1.98 kW
COP
4.71
2.83
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
160 %
Prated
6.00 kW
6.20 kW
SCOP
5.80
4.09
Tbiv
3 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
5.62 kW
6.58 kW
COP Tj = +2°C
3.56
2.48
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.92 kW
3.89 kW
COP Tj = +7°C
5.46
3.65
Cdh Tj = +7 °C
0.950
0.970
Pdh Tj = 12°C
1.77 kW
2.11 kW
COP Tj = 12°C
7.50
5.36
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
5.82 kW
6.58 kW
COP Tj = Tbiv
3.72
2.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.62 kW
6.58 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.56
2.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.38 kW
0.00 kW
Annual energy consumption Qhe
1382 kWh
2027 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
163 %
124 %
Prated
6.00 kW
6.00 kW
SCOP
4.16
3.19
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
3.60 kW
3.58 kW
COP Tj = -7°C
3.56
2.69
Cdh Tj = -7 °C
0.970
0.970
Pdh Tj = +2°C
2.00 kW
2.19 kW
COP Tj = +2°C
5.01
3.86
Cdh Tj = +2 °C
0.910
0.940
Pdh Tj = +7°C
2.01 kW
2.12 kW
COP Tj = +7°C
6.16
4.72
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.70 kW
1.57 kW
COP Tj = 12°C
6.86
5.42
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.07 kW
5.02 kW
COP Tj = Tbiv
2.47
2.03
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.35 kW
3.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.16
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.65 kW
2.04 kW
Annual energy consumption Qhe
3559 kWh
4642 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.83
5.02
COP Tj = -15°C (if TOL<-20°C)
2.66
2.03
Cdh Tj = -15 °C
0.980
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
136 %
Prated
6.00 kW
6.00 kW
SCOP
4.69
3.49
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.01 kW
5.48 kW
COP Tj = -7°C
3.15
2.26
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
3.12 kW
3.10 kW
COP Tj = +2°C
4.69
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.99 kW
2.09 kW
COP Tj = +7°C
6.01
4.52
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.76 kW
2.16 kW
COP Tj = 12°C
7.32
5.62
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.04 kW
5.75 kW
COP Tj = Tbiv
2.73
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.04 kW
5.57 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.73
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.980
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.43 kW
Annual energy consumption Qhe
2643 kWh
3556 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.29 kW
6.33 kW
El input
1.46 kW
2.31 kW
COP
4.31
2.74
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
231 %
166 %
Prated
8.20 kW
8.00 kW
SCOP
5.85
4.22
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.62 kW
7.88 kW
COP Tj = +2°C
2.76
2.24
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.22 kW
5.30 kW
COP Tj = +7°C
5.35
3.68
Cdh Tj = +7 °C
0.960
0.980
Pdh Tj = 12°C
2.39 kW
2.15 kW
COP Tj = 12°C
7.77
5.62
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
7.62 kW
7.88 kW
COP Tj = Tbiv
2.76
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.62 kW
7.88 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.24
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1873 kWh
2533 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
162 %
125 %
Prated
8.00 kW
8.00 kW
SCOP
4.11
3.20
Tbiv
-15 °C
-14 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
4.75 kW
4.83 kW
COP Tj = -7°C
3.46
2.67
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
2.85 kW
2.98 kW
COP Tj = +2°C
5.07
3.93
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
2.05 kW
2.16 kW
COP Tj = +7°C
6.53
5.00
Cdh Tj = +7 °C
0.900
0.920
Pdh Tj = 12°C
1.74 kW
1.59 kW
COP Tj = 12°C
7.19
5.64
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
6.42 kW
6.23 kW
COP Tj = Tbiv
2.46
2.01
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
4.85 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.75 kW
3.15 kW
Annual energy consumption Qhe
4793 kWh
6169 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.42
6.06
COP Tj = -15°C (if TOL<-20°C)
2.46
1.96
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
139 %
Prated
8.00 kW
8.00 kW
SCOP
4.75
3.55
Tbiv
-8 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.66 kW
6.84 kW
COP Tj = -7°C
2.98
2.23
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
4.15 kW
4.35 kW
COP Tj = +2°C
4.71
3.53
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.87 kW
2.62 kW
COP Tj = +7°C
6.44
4.69
Cdh Tj = +7 °C
0.920
0.940
Pdh Tj = 12°C
1.73 kW
2.21 kW
COP Tj = 12°C
7.37
5.95
Cdh Tj = +12 °C
0.900
0.910
Pdh Tj = Tbiv
7.72 kW
6.84 kW
COP Tj = Tbiv
2.72
2.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.34 kW
6.73 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.61
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
35 W
35 W
PSB
33 W
33 W
PCK
1 W
1 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.66 kW
1.27 kW
Annual energy consumption Qhe
3477 kWh
4654 kWh