1,250 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
12.00 kW
El input
2.50 kW
4.00 kW
COP
4.80
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
257 %
180 %
Prated
12.50 kW
12.50 kW
SCOP
6.51
4.58
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.50 kW
12.50 kW
COP Tj = +2°C
3.45
2.40
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.04 kW
8.04 kW
COP Tj = +7°C
5.80
3.90
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.30 kW
4.20 kW
COP Tj = 12°C
8.20
6.00
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.50 kW
12.50 kW
COP Tj = Tbiv
3.45
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.50 kW
12.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.45
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2549 kWh
3631 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
143 %
Prated
12.00 kW
12.00 kW
SCOP
4.90
3.65
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.62 kW
10.62 kW
COP Tj = -7°C
2.95
2.15
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.46 kW
6.46 kW
COP Tj = +2°C
4.83
3.60
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.15 kW
4.20 kW
COP Tj = +7°C
6.50
4.88
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.15 kW
4.20 kW
COP Tj = 12°C
8.00
5.95
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.62 kW
10.62 kW
COP Tj = Tbiv
2.95
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.62 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.46
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.40 kW
0.50 kW
Annual energy consumption Qhe
5051 kWh
6784 kWh