Certificate holders

Subtype

Buderus Logatherm M WLW-11/13/15 MBE+ AR

Certificate Holder
Bosch Thermotechnik GmbH (Buderus)
Sophienstraße 30-32
35576 Wetzlar
Germany
Registration number
011-1W1235
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Buderus Logatherm M WLW-11/13/15 MBE+ AR
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,700 kg

Certification Date
27.03.2026
Testing basis
HP KEYMARK certification scheme rules rev. 15
Testing laboratory
TÜV Rheinland Energy GmbH, DE
Generate PDF Export model CSV
  • Number of models 15

Models

WLW186i-11 MBE+ AR E
Configure model
Model name
WLW186i-11 MBE+ AR E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.64 kW

4.67 kW

El input

0.87 kW

1.59 kW

COP

5.35

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

186 %

Prated

10.2 kW

10.5 kW

SCOP

6.34

4.72

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.5 kW

COP Tj = +2°C

3.18

2.48

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

6.5 kW

7.12 kW

COP Tj = +7°C

5.95

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.5 kW

5.29 kW

COP Tj = 12°C

7.49

5.82

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.22 kW

10.5 kW

COP Tj = Tbiv

3.18

2.48

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.18

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2151 kWh

2970 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

143 %

Prated

11 kW

11 kW

SCOP

4.6

3.65

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

6.78 kW

6.58 kW

COP Tj = -7°C

3.87

3.08

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.18 kW

4.01 kW

COP Tj = +2°C

5.72

4.43

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.81 kW

4.67 kW

COP Tj = +7°C

6.66

5.37

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.51 kW

5.4 kW

COP Tj = 12°C

7.58

6.45

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.11 kW

8.9 kW

COP Tj = Tbiv

2.73

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.47 kW

7.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.53 kW

3.8 kW

Annual energy consumption Qhe

5891 kWh

7436 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.11

8.9

COP Tj = -15°C (if TOL<-20°C)

2.73

2.18

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

162 %

Prated

11 kW

11 kW

SCOP

5.4

4.12

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.83 kW

9.38 kW

COP Tj = -7°C

3.32

2.57

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.67 kW

5.84 kW

COP Tj = +2°C

5.41

4.09

Cdh Tj = +2 °C

0.99

1

Pdh Tj = +7°C

4.93 kW

4.73 kW

COP Tj = +7°C

6.82

5.19

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.65 kW

5.54 kW

COP Tj = 12°C

8.29

6.62

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.83 kW

9.38 kW

COP Tj = Tbiv

3.32

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.25 kW

10.12 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.33

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.75 kW

0.88 kW

Annual energy consumption Qhe

4209 kWh

5513 kWh

WLW186i-11 MBE+ AR TP70
Configure model
Model name
WLW186i-11 MBE+ AR TP70
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.64 kW

4.67 kW

El input

0.87 kW

1.59 kW

COP

5.35

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

186 %

Prated

10.2 kW

10.5 kW

SCOP

6.34

4.72

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.5 kW

COP Tj = +2°C

3.18

2.48

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

6.5 kW

7.12 kW

COP Tj = +7°C

5.95

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.5 kW

5.29 kW

COP Tj = 12°C

7.49

5.82

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.22 kW

10.5 kW

COP Tj = Tbiv

3.18

2.48

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.18

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2151 kWh

2970 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

143 %

Prated

11 kW

11 kW

SCOP

4.6

3.65

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

6.78 kW

6.58 kW

COP Tj = -7°C

3.87

3.08

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.18 kW

4.01 kW

COP Tj = +2°C

5.72

4.43

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.81 kW

4.67 kW

COP Tj = +7°C

6.66

5.37

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.51 kW

5.4 kW

COP Tj = 12°C

7.58

6.45

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.11 kW

8.9 kW

COP Tj = Tbiv

2.73

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.47 kW

7.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.53 kW

3.8 kW

Annual energy consumption Qhe

5891 kWh

7436 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.11

8.9

COP Tj = -15°C (if TOL<-20°C)

2.73

2.18

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

162 %

Prated

11 kW

11 kW

SCOP

5.4

4.12

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.83 kW

9.38 kW

COP Tj = -7°C

3.32

2.57

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.67 kW

5.84 kW

COP Tj = +2°C

5.41

4.09

Cdh Tj = +2 °C

0.99

1

Pdh Tj = +7°C

4.93 kW

4.73 kW

COP Tj = +7°C

6.82

5.19

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.65 kW

5.54 kW

COP Tj = 12°C

8.29

6.62

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.83 kW

9.38 kW

COP Tj = Tbiv

3.32

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.25 kW

10.12 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.33

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.75 kW

0.88 kW

Annual energy consumption Qhe

4209 kWh

5513 kWh

WLW186i-11 MBE+ AR E W
Configure model
Model name
WLW186i-11 MBE+ AR E W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.64 kW

4.67 kW

El input

0.87 kW

1.59 kW

COP

5.35

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

186 %

Prated

10.2 kW

10.5 kW

SCOP

6.34

4.72

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.5 kW

COP Tj = +2°C

3.18

2.48

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

6.5 kW

7.12 kW

COP Tj = +7°C

5.95

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.5 kW

5.29 kW

COP Tj = 12°C

7.49

5.82

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.22 kW

10.5 kW

COP Tj = Tbiv

3.18

2.48

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.18

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2151 kWh

2970 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

143 %

Prated

11 kW

11 kW

SCOP

4.6

3.65

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

6.78 kW

6.58 kW

COP Tj = -7°C

3.87

3.08

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.18 kW

4.01 kW

COP Tj = +2°C

5.72

4.43

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.81 kW

4.67 kW

COP Tj = +7°C

6.66

5.37

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.51 kW

5.4 kW

COP Tj = 12°C

7.58

6.45

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.11 kW

8.9 kW

COP Tj = Tbiv

2.73

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.47 kW

7.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.53 kW

3.8 kW

Annual energy consumption Qhe

5891 kWh

7436 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.11

8.9

COP Tj = -15°C (if TOL<-20°C)

2.73

2.18

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

162 %

Prated

11 kW

11 kW

SCOP

5.4

4.12

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.83 kW

9.38 kW

COP Tj = -7°C

3.32

2.57

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.67 kW

5.84 kW

COP Tj = +2°C

5.41

4.09

Cdh Tj = +2 °C

0.99

1

Pdh Tj = +7°C

4.93 kW

4.73 kW

COP Tj = +7°C

6.82

5.19

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.65 kW

5.54 kW

COP Tj = 12°C

8.29

6.62

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.83 kW

9.38 kW

COP Tj = Tbiv

3.32

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.25 kW

10.12 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.33

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.75 kW

0.88 kW

Annual energy consumption Qhe

4209 kWh

5513 kWh

WLW186i-11 MBE+ AR TP70 W
Configure model
Model name
WLW186i-11 MBE+ AR TP70 W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.64 kW

4.67 kW

El input

0.87 kW

1.59 kW

COP

5.35

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

186 %

Prated

10.2 kW

10.5 kW

SCOP

6.34

4.72

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.5 kW

COP Tj = +2°C

3.18

2.48

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

6.5 kW

7.12 kW

COP Tj = +7°C

5.95

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.5 kW

5.29 kW

COP Tj = 12°C

7.49

5.82

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.22 kW

10.5 kW

COP Tj = Tbiv

3.18

2.48

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.18

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2151 kWh

2970 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

143 %

Prated

11 kW

11 kW

SCOP

4.6

3.65

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

6.78 kW

6.58 kW

COP Tj = -7°C

3.87

3.08

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.18 kW

4.01 kW

COP Tj = +2°C

5.72

4.43

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.81 kW

4.67 kW

COP Tj = +7°C

6.66

5.37

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.51 kW

5.4 kW

COP Tj = 12°C

7.58

6.45

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.11 kW

8.9 kW

COP Tj = Tbiv

2.73

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.47 kW

7.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.53 kW

3.8 kW

Annual energy consumption Qhe

5891 kWh

7436 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.11

8.9

COP Tj = -15°C (if TOL<-20°C)

2.73

2.18

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

162 %

Prated

11 kW

11 kW

SCOP

5.4

4.12

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.83 kW

9.38 kW

COP Tj = -7°C

3.32

2.57

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.67 kW

5.84 kW

COP Tj = +2°C

5.41

4.09

Cdh Tj = +2 °C

0.99

1

Pdh Tj = +7°C

4.93 kW

4.73 kW

COP Tj = +7°C

6.82

5.19

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.65 kW

5.54 kW

COP Tj = 12°C

8.29

6.62

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.83 kW

9.38 kW

COP Tj = Tbiv

3.32

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.25 kW

10.12 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.33

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.75 kW

0.88 kW

Annual energy consumption Qhe

4209 kWh

5513 kWh

WLW186i-13 MBE+ AR E
Configure model
Model name
WLW186i-13 MBE+ AR E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.4 kW

4.67 kW

El input

1 kW

1.59 kW

COP

5.4

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

187 %

Prated

11 kW

12 kW

SCOP

6.32

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.12 kW

11.68 kW

COP Tj = +2°C

2.99

2.37

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.01 kW

7.58 kW

COP Tj = +7°C

5.9

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.32 kW

COP Tj = 12°C

7.56

5.95

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.12 kW

11.68 kW

COP Tj = Tbiv

2.99

2.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

11.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2327 kWh

3370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

142 %

Prated

13 kW

13 kW

SCOP

4.5

3.61

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.7 kW

8.1 kW

COP Tj = -7°C

3.75

2.99

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.86 kW

4.67 kW

COP Tj = +2°C

5.68

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.83 kW

4.69 kW

COP Tj = +7°C

6.75

5.48

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.52 kW

5.41 kW

COP Tj = 12°C

7.63

6.5

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.86 kW

10.69 kW

COP Tj = Tbiv

2.51

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.06 kW

8.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.11

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.94 kW

4.19 kW

Annual energy consumption Qhe

7116 kWh

8869 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.86

10.69

COP Tj = -15°C (if TOL<-20°C)

2.51

2.04

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

162 %

Prated

13 kW

13 kW

SCOP

5.37

4.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.81 kW

11.47 kW

COP Tj = -7°C

3.09

2.45

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.70 kW

6.79 kW

COP Tj = +2°C

5.39

4.11

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.04 kW

4.85 kW

COP Tj = +7°C

7.03

5.35

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.82 kW

5.67 kW

COP Tj = 12°C

8.38

6.70

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.81 kW

11.47 kW

COP Tj = Tbiv

3.09

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.40 kW

12.06 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

0.94 kW

Annual energy consumption Qhe

5005 kWh

6502 kWh

WLW186i-13 MBE+ AR TP70
Configure model
Model name
WLW186i-13 MBE+ AR TP70
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.4 kW

4.67 kW

El input

1 kW

1.59 kW

COP

5.4

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

187 %

Prated

11 kW

12 kW

SCOP

6.32

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.12 kW

11.68 kW

COP Tj = +2°C

2.99

2.37

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.01 kW

7.58 kW

COP Tj = +7°C

5.9

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.32 kW

COP Tj = 12°C

7.56

5.95

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.12 kW

11.68 kW

COP Tj = Tbiv

2.99

2.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

11.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2327 kWh

3370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

142 %

Prated

13 kW

13 kW

SCOP

4.5

3.61

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.7 kW

8.1 kW

COP Tj = -7°C

3.75

2.99

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.86 kW

4.67 kW

COP Tj = +2°C

5.68

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.83 kW

4.69 kW

COP Tj = +7°C

6.75

5.48

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.52 kW

5.41 kW

COP Tj = 12°C

7.63

6.5

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.86 kW

10.69 kW

COP Tj = Tbiv

2.51

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.06 kW

8.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.11

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.94 kW

4.19 kW

Annual energy consumption Qhe

7116 kWh

8869 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.86

10.69

COP Tj = -15°C (if TOL<-20°C)

2.51

2.04

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

162 %

Prated

13 kW

13 kW

SCOP

5.37

4.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.81 kW

11.47 kW

COP Tj = -7°C

3.09

2.45

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.70 kW

6.79 kW

COP Tj = +2°C

5.39

4.11

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.04 kW

4.85 kW

COP Tj = +7°C

7.03

5.35

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.82 kW

5.67 kW

COP Tj = 12°C

8.38

6.70

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.81 kW

11.47 kW

COP Tj = Tbiv

3.09

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.40 kW

12.06 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

0.94 kW

Annual energy consumption Qhe

5005 kWh

6502 kWh

WLW186i-13 MBE+ AR E W
Configure model
Model name
WLW186i-13 MBE+ AR E W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.4 kW

4.67 kW

El input

1 kW

1.59 kW

COP

5.4

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

187 %

Prated

11 kW

12 kW

SCOP

6.32

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.12 kW

11.68 kW

COP Tj = +2°C

2.99

2.37

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.01 kW

7.58 kW

COP Tj = +7°C

5.9

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.32 kW

COP Tj = 12°C

7.56

5.95

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.12 kW

11.68 kW

COP Tj = Tbiv

2.99

2.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

11.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2327 kWh

3370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

142 %

Prated

13 kW

13 kW

SCOP

4.5

3.61

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.7 kW

8.1 kW

COP Tj = -7°C

3.75

2.99

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.86 kW

4.67 kW

COP Tj = +2°C

5.68

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.83 kW

4.69 kW

COP Tj = +7°C

6.75

5.48

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.52 kW

5.41 kW

COP Tj = 12°C

7.63

6.5

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.86 kW

10.69 kW

COP Tj = Tbiv

2.51

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.06 kW

8.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.11

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.94 kW

4.19 kW

Annual energy consumption Qhe

7116 kWh

8869 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.86

10.69

COP Tj = -15°C (if TOL<-20°C)

2.51

2.04

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

162 %

Prated

13 kW

13 kW

SCOP

5.37

4.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.81 kW

11.47 kW

COP Tj = -7°C

3.09

2.45

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.70 kW

6.79 kW

COP Tj = +2°C

5.39

4.11

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.04 kW

4.85 kW

COP Tj = +7°C

7.03

5.35

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.82 kW

5.67 kW

COP Tj = 12°C

8.38

6.70

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.81 kW

11.47 kW

COP Tj = Tbiv

3.09

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.40 kW

12.06 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

0.94 kW

Annual energy consumption Qhe

5005 kWh

6502 kWh

WLW186i-13 MBE+ AR TP70 W
Configure model
Model name
WLW186i-13 MBE+ AR TP70 W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.4 kW

4.67 kW

El input

1 kW

1.59 kW

COP

5.4

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

187 %

Prated

11 kW

12 kW

SCOP

6.32

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.12 kW

11.68 kW

COP Tj = +2°C

2.99

2.37

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.01 kW

7.58 kW

COP Tj = +7°C

5.9

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.32 kW

COP Tj = 12°C

7.56

5.95

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.12 kW

11.68 kW

COP Tj = Tbiv

2.99

2.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

11.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2327 kWh

3370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

142 %

Prated

13 kW

13 kW

SCOP

4.5

3.61

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.7 kW

8.1 kW

COP Tj = -7°C

3.75

2.99

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.86 kW

4.67 kW

COP Tj = +2°C

5.68

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.83 kW

4.69 kW

COP Tj = +7°C

6.75

5.48

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.52 kW

5.41 kW

COP Tj = 12°C

7.63

6.5

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.86 kW

10.69 kW

COP Tj = Tbiv

2.51

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.06 kW

8.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.11

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.94 kW

4.19 kW

Annual energy consumption Qhe

7116 kWh

8869 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.86

10.69

COP Tj = -15°C (if TOL<-20°C)

2.51

2.04

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

162 %

Prated

13 kW

13 kW

SCOP

5.37

4.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.81 kW

11.47 kW

COP Tj = -7°C

3.09

2.45

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.70 kW

6.79 kW

COP Tj = +2°C

5.39

4.11

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.04 kW

4.85 kW

COP Tj = +7°C

7.03

5.35

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.82 kW

5.67 kW

COP Tj = 12°C

8.38

6.70

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.81 kW

11.47 kW

COP Tj = Tbiv

3.09

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.40 kW

12.06 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

0.94 kW

Annual energy consumption Qhe

5005 kWh

6502 kWh

WLW186i-15 MBE+ AR E
Configure model
Model name
WLW186i-15 MBE+ AR E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.39 kW

5.15 kW

El input

1.19 kW

1.72 kW

COP

5.38

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

247 %

188 %

Prated

12.5 kW

13 kW

SCOP

6.25

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.48 kW

13.21 kW

COP Tj = +2°C

2.88

2.29

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.98 kW

8.29 kW

COP Tj = +7°C

5.78

4.18

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.33 kW

COP Tj = 12°C

7.58

6.03

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.48 kW

13.21 kW

COP Tj = Tbiv

2.88

2.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.48 kW

13.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

2.29

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2671 kWh

3645 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

138 %

Prated

15 kW

15 kW

SCOP

4.33

3.54

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.93 kW

9.23 kW

COP Tj = -7°C

3.56

2.87

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.76 kW

5.57 kW

COP Tj = +2°C

5.53

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.85 kW

4.71 kW

COP Tj = +7°C

6.85

5.59

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.53 kW

5.42 kW

COP Tj = 12°C

7.67

6.56

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.21 kW

12.08 kW

COP Tj = Tbiv

2.38

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.25 kW

9.4 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.75 kW

5.6 kW

Annual energy consumption Qhe

8532 kWh

10455 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.21

12.08

COP Tj = -15°C (if TOL<-20°C)

2.38

1.93

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

157 %

Prated

15 kW

15 kW

SCOP

5.02

3.99

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.98 kW

12.81 kW

COP Tj = -7°C

2.93

2.34

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.99 kW

7.73 kW

COP Tj = +2°C

4.90

3.93

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.15 kW

5.03 kW

COP Tj = +7°C

6.92

5.34

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.64 kW

5.52 kW

COP Tj = 12°C

8.32

6.54

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.98 kW

12.81 kW

COP Tj = Tbiv

2.93

2.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.83 kW

13.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.17 kW

1.42 kW

Annual energy consumption Qhe

6168 kWh

7769 kWh

WLW186i-15 MBE+ AR TP70
Configure model
Model name
WLW186i-15 MBE+ AR TP70
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.39 kW

5.15 kW

El input

1.19 kW

1.72 kW

COP

5.38

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

247 %

188 %

Prated

12.5 kW

13 kW

SCOP

6.25

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.48 kW

13.21 kW

COP Tj = +2°C

2.88

2.29

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.98 kW

8.29 kW

COP Tj = +7°C

5.78

4.18

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.33 kW

COP Tj = 12°C

7.58

6.03

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.48 kW

13.21 kW

COP Tj = Tbiv

2.88

2.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.48 kW

13.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

2.29

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2671 kWh

3645 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

138 %

Prated

15 kW

15 kW

SCOP

4.33

3.54

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.93 kW

9.23 kW

COP Tj = -7°C

3.56

2.87

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.76 kW

5.57 kW

COP Tj = +2°C

5.53

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.85 kW

4.71 kW

COP Tj = +7°C

6.85

5.59

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.53 kW

5.42 kW

COP Tj = 12°C

7.67

6.56

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.21 kW

12.08 kW

COP Tj = Tbiv

2.38

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.25 kW

9.4 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.75 kW

5.6 kW

Annual energy consumption Qhe

8532 kWh

10455 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.21

12.08

COP Tj = -15°C (if TOL<-20°C)

2.38

1.93

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

157 %

Prated

15 kW

15 kW

SCOP

5.02

3.99

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.98 kW

12.81 kW

COP Tj = -7°C

2.93

2.34

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.99 kW

7.73 kW

COP Tj = +2°C

4.90

3.93

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.15 kW

5.03 kW

COP Tj = +7°C

6.92

5.34

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.64 kW

5.52 kW

COP Tj = 12°C

8.32

6.54

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.98 kW

12.81 kW

COP Tj = Tbiv

2.93

2.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.83 kW

13.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.17 kW

1.42 kW

Annual energy consumption Qhe

6168 kWh

7769 kWh

WLW186i-15 MBE+ AR E W
Configure model
Model name
WLW186i-15 MBE+ AR E W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.39 kW

5.15 kW

El input

1.19 kW

1.72 kW

COP

5.38

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

247 %

188 %

Prated

12.5 kW

13 kW

SCOP

6.25

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.48 kW

13.21 kW

COP Tj = +2°C

2.88

2.29

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.98 kW

8.29 kW

COP Tj = +7°C

5.78

4.18

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.33 kW

COP Tj = 12°C

7.58

6.03

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.48 kW

13.21 kW

COP Tj = Tbiv

2.88

2.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.48 kW

13.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

2.29

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2671 kWh

3645 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

138 %

Prated

15 kW

15 kW

SCOP

4.33

3.54

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.93 kW

9.23 kW

COP Tj = -7°C

3.56

2.87

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.76 kW

5.57 kW

COP Tj = +2°C

5.53

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.85 kW

4.71 kW

COP Tj = +7°C

6.85

5.59

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.53 kW

5.42 kW

COP Tj = 12°C

7.67

6.56

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.21 kW

12.08 kW

COP Tj = Tbiv

2.38

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.25 kW

9.4 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.75 kW

5.6 kW

Annual energy consumption Qhe

8532 kWh

10455 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.21

12.08

COP Tj = -15°C (if TOL<-20°C)

2.38

1.93

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

157 %

Prated

15 kW

15 kW

SCOP

5.02

3.99

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.98 kW

12.81 kW

COP Tj = -7°C

2.93

2.34

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.99 kW

7.73 kW

COP Tj = +2°C

4.90

3.93

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.15 kW

5.03 kW

COP Tj = +7°C

6.92

5.34

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.64 kW

5.52 kW

COP Tj = 12°C

8.32

6.54

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.98 kW

12.81 kW

COP Tj = Tbiv

2.93

2.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.83 kW

13.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.17 kW

1.42 kW

Annual energy consumption Qhe

6168 kWh

7769 kWh

WLW186i-15 MBE+ AR TP70 W
Configure model
Model name
WLW186i-15 MBE+ AR TP70 W
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.39 kW

5.15 kW

El input

1.19 kW

1.72 kW

COP

5.38

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

247 %

188 %

Prated

12.5 kW

13 kW

SCOP

6.25

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.48 kW

13.21 kW

COP Tj = +2°C

2.88

2.29

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.98 kW

8.29 kW

COP Tj = +7°C

5.78

4.18

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.33 kW

COP Tj = 12°C

7.58

6.03

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.48 kW

13.21 kW

COP Tj = Tbiv

2.88

2.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.48 kW

13.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

2.29

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2671 kWh

3645 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

138 %

Prated

15 kW

15 kW

SCOP

4.33

3.54

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.93 kW

9.23 kW

COP Tj = -7°C

3.56

2.87

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.76 kW

5.57 kW

COP Tj = +2°C

5.53

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.85 kW

4.71 kW

COP Tj = +7°C

6.85

5.59

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.53 kW

5.42 kW

COP Tj = 12°C

7.67

6.56

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.21 kW

12.08 kW

COP Tj = Tbiv

2.38

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.25 kW

9.4 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.75 kW

5.6 kW

Annual energy consumption Qhe

8532 kWh

10455 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.21

12.08

COP Tj = -15°C (if TOL<-20°C)

2.38

1.93

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

157 %

Prated

15 kW

15 kW

SCOP

5.02

3.99

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.98 kW

12.81 kW

COP Tj = -7°C

2.93

2.34

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.99 kW

7.73 kW

COP Tj = +2°C

4.90

3.93

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.15 kW

5.03 kW

COP Tj = +7°C

6.92

5.34

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.64 kW

5.52 kW

COP Tj = 12°C

8.32

6.54

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.98 kW

12.81 kW

COP Tj = Tbiv

2.93

2.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.83 kW

13.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.17 kW

1.42 kW

Annual energy consumption Qhe

6168 kWh

7769 kWh

WLW-11 MBE+ AR
Configure model
Model name
WLW-11 MBE+ AR
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.64 kW

4.67 kW

El input

0.87 kW

1.59 kW

COP

5.35

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

186 %

Prated

10.2 kW

10.5 kW

SCOP

6.34

4.72

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.22 kW

10.5 kW

COP Tj = +2°C

3.18

2.48

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

6.5 kW

7.12 kW

COP Tj = +7°C

5.95

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.5 kW

5.29 kW

COP Tj = 12°C

7.49

5.82

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.22 kW

10.5 kW

COP Tj = Tbiv

3.18

2.48

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.22 kW

10.5 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.18

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2151 kWh

2970 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

143 %

Prated

11 kW

11 kW

SCOP

4.6

3.65

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

6.78 kW

6.58 kW

COP Tj = -7°C

3.87

3.08

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.18 kW

4.01 kW

COP Tj = +2°C

5.72

4.43

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.81 kW

4.67 kW

COP Tj = +7°C

6.66

5.37

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.51 kW

5.4 kW

COP Tj = 12°C

7.58

6.45

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.11 kW

8.9 kW

COP Tj = Tbiv

2.73

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.47 kW

7.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.74

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.53 kW

3.8 kW

Annual energy consumption Qhe

5891 kWh

7436 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.11

8.9

COP Tj = -15°C (if TOL<-20°C)

2.73

2.18

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

162 %

Prated

11 kW

11 kW

SCOP

5.4

4.12

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.83 kW

9.38 kW

COP Tj = -7°C

3.32

2.57

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.67 kW

5.84 kW

COP Tj = +2°C

5.41

4.09

Cdh Tj = +2 °C

0.99

1

Pdh Tj = +7°C

4.93 kW

4.73 kW

COP Tj = +7°C

6.82

5.19

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.65 kW

5.54 kW

COP Tj = 12°C

8.29

6.62

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

9.83 kW

9.38 kW

COP Tj = Tbiv

3.32

2.57

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.25 kW

10.12 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.33

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.75 kW

0.88 kW

Annual energy consumption Qhe

4209 kWh

5513 kWh

WLW-13 MBE+ AR
Configure model
Model name
WLW-13 MBE+ AR
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.4 kW

4.67 kW

El input

1 kW

1.59 kW

COP

5.4

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

250 %

187 %

Prated

11 kW

12 kW

SCOP

6.32

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.12 kW

11.68 kW

COP Tj = +2°C

2.99

2.37

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.01 kW

7.58 kW

COP Tj = +7°C

5.9

4.2

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.32 kW

COP Tj = 12°C

7.56

5.95

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.12 kW

11.68 kW

COP Tj = Tbiv

2.99

2.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

11.68 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2327 kWh

3370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

142 %

Prated

13 kW

13 kW

SCOP

4.5

3.61

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

7.7 kW

8.1 kW

COP Tj = -7°C

3.75

2.99

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

4.86 kW

4.67 kW

COP Tj = +2°C

5.68

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.83 kW

4.69 kW

COP Tj = +7°C

6.75

5.48

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.52 kW

5.41 kW

COP Tj = 12°C

7.63

6.5

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

10.86 kW

10.69 kW

COP Tj = Tbiv

2.51

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.06 kW

8.81 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.11

1.66

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.94 kW

4.19 kW

Annual energy consumption Qhe

7116 kWh

8869 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.86

10.69

COP Tj = -15°C (if TOL<-20°C)

2.51

2.04

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

212 %

162 %

Prated

13 kW

13 kW

SCOP

5.37

4.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.81 kW

11.47 kW

COP Tj = -7°C

3.09

2.45

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.70 kW

6.79 kW

COP Tj = +2°C

5.39

4.11

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.04 kW

4.85 kW

COP Tj = +7°C

7.03

5.35

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.82 kW

5.67 kW

COP Tj = 12°C

8.38

6.70

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

11.81 kW

11.47 kW

COP Tj = Tbiv

3.09

2.45

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.40 kW

12.06 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.60 kW

0.94 kW

Annual energy consumption Qhe

5005 kWh

6502 kWh

WLW-15 MBE+ AR
Configure model
Model name
WLW-15 MBE+ AR
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.39 kW

5.15 kW

El input

1.19 kW

1.72 kW

COP

5.38

2.99

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

247 %

188 %

Prated

12.5 kW

13 kW

SCOP

6.25

4.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.48 kW

13.21 kW

COP Tj = +2°C

2.88

2.29

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

7.98 kW

8.29 kW

COP Tj = +7°C

5.78

4.18

Cdh Tj = +7 °C

0.99

1

Pdh Tj = 12°C

5.51 kW

5.33 kW

COP Tj = 12°C

7.58

6.03

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.48 kW

13.21 kW

COP Tj = Tbiv

2.88

2.29

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.48 kW

13.21 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.88

2.29

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2671 kWh

3645 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

138 %

Prated

15 kW

15 kW

SCOP

4.33

3.54

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

8.93 kW

9.23 kW

COP Tj = -7°C

3.56

2.87

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.76 kW

5.57 kW

COP Tj = +2°C

5.53

4.5

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

4.85 kW

4.71 kW

COP Tj = +7°C

6.85

5.59

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.53 kW

5.42 kW

COP Tj = 12°C

7.67

6.56

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.21 kW

12.08 kW

COP Tj = Tbiv

2.38

1.93

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.25 kW

9.4 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.75 kW

5.6 kW

Annual energy consumption Qhe

8532 kWh

10455 kWh

Pdh Tj = -15°C (if TOL<-20°C)

12.21

12.08

COP Tj = -15°C (if TOL<-20°C)

2.38

1.93

Cdh Tj = -15 °C

1

1

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

31 dB(A)

31 dB(A)

Sound power level outdoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

157 %

Prated

15 kW

15 kW

SCOP

5.02

3.99

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.98 kW

12.81 kW

COP Tj = -7°C

2.93

2.34

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

7.99 kW

7.73 kW

COP Tj = +2°C

4.90

3.93

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

5.15 kW

5.03 kW

COP Tj = +7°C

6.92

5.34

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

5.64 kW

5.52 kW

COP Tj = 12°C

8.32

6.54

Cdh Tj = +12 °C

0.99

0.99

Pdh Tj = Tbiv

12.98 kW

12.81 kW

COP Tj = Tbiv

2.93

2.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.83 kW

13.58 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

75 °C

75 °C

Poff

17 W

17 W

PTO

6 W

6 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.17 kW

1.42 kW

Annual energy consumption Qhe

6168 kWh

7769 kWh