Certificate holders

Subtype

DUAL CLIMA 9 HT PRO

Certificate Holder
Domusa Calefacción S.Coop.
Barrio San Esteban, S / N
20737 Errezil, Gipuzkoa
Spain
Registration number
037-1013-26
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
DUAL CLIMA 9 HT PRO
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

0,850 kg

Certification Date
10.07.2026
Testing basis
HP Keymark scheme rules rev. no. 15
Testing laboratory
SZU Brno, CZ
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

DUAL CLIMA 9 HT PRO
Configure model
Model name
DUAL CLIMA 9 HT PRO
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.39 kW

8.43 kW

El input

1.98 kW

2.74 kW

COP

4.74

3.08

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

2.18 kW

1.77 kW

Cooling capacity

7.61

9.12

EER

3.50

5.14

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.61 kW

9.12 kW

SEER

5.57

9.14

Pdc Tj = 35°C

7.61 kW

9.12 kW

EER Tj = 35°C

3.50

5.14

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

5.70 kW

6.80 kW

EER Tj = 30°C

4.51

7.06

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

3.59 kW

4.30 kW

EER Tj = 25°C

5.97

9.96

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

1.69 kW

2.01 kW

EER Tj = 20°C

9.87

16.04

Cdc Tj = 20 °C

0.900

0.960

Poff

8 W

8 W

PTO

14 W

14 W

PSB

8 W

8 W

PCK

0 W

0 W

Annual energy consumption Qce

794 kWh

598 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

153 %

Prated

7.07 kW

7.53 kW

SCOP

5.10

3.89

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.26 kW

6.66 kW

COP Tj = -7°C

3.15

2.46

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.75 kW

4.02 kW

COP Tj = +2°C

5.00

3.76

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

2.45 kW

2.52 kW

COP Tj = +7°C

6.59

5.15

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

2.99 kW

2.97 kW

COP Tj = 12°C

9.33

6.88

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

6.26 kW

6.66 kW

COP Tj = Tbiv

3.15

2.46

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.25 kW

5.26 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.84

2.07

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

14 W

14 W

PSB

8 W

8 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.82 kW

2.27 kW

Annual energy consumption Qhe

2878 kWh

3975 kWh