Certificate holders

Subtype

MONOBLOC ACTIVE 2 AOWD 10X

Certificate Holder
Eurofred S.A.
Marqués de Sentmenat, 97
08029 Barcelona
Spain
Registration number
041-K010-21
Certification Body
BRE
Subtype title
MONOBLOC ACTIVE 2 AOWD 10X
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,000 kg

Certification Date
17.06.2026
Testing basis
Heat Pump Keymark Scheme Rules Rev 15
Testing laboratory
TÜV SÜD Certification and Testing Co., Ltd. Guangzhou Branch, CN
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

AOWD-2--MB-AT10
Configure model
Model name
AOWD-2--MB-AT10
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.48 kW

9.17 kW

El input

2.30 kW

3.21 kW

COP

4.56

2.86

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

184 %

143 %

Prated

11.62 kW

11.83 kW

SCOP

4.67

3.66

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.28 kW

10.47 kW

COP Tj = -7°C

2.97

2.31

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.30 kW

6.43 kW

COP Tj = +2°C

4.48

3.49

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.58 kW

4.33 kW

COP Tj = +7°C

6.50

5.09

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

5.33 kW

5.16 kW

COP Tj = 12°C

8.31

6.65

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.28 kW

10.47 kW

COP Tj = Tbiv

2.97

2.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.79 kW

9.99 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.59

2.08

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

11 W

11 W

PTO

12 W

12 W

PSB

11 W

11 W

PCK

83 W

83 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.83 kW

1.85 kW

Annual energy consumption Qhe

5144 kWh

6679 kWh

AOWD-2--MB-AT10T
Configure model
Model name
AOWD-2--MB-AT10T
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.72 kW

9.67 kW

El input

2.13 kW

3.12 kW

COP

4.57

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

141 %

Prated

11.63 kW

11.71 kW

SCOP

4.71

3.60

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.29 kW

10.36 kW

COP Tj = -7°C

2.99

2.28

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.30 kW

6.45 kW

COP Tj = +2°C

4.54

3.45

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.25 kW

COP Tj = +7°C

6.37

4.93

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.87 kW

5.03 kW

COP Tj = 12°C

8.09

6.40

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.29 kW

10.36 kW

COP Tj = Tbiv

2.99

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.71 kW

9.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.68

2.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

75 °C

75 °C

Poff

10 W

10 W

PTO

12 W

12 W

PSB

10 W

10 W

PCK

48 W

48 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.92 kW

1.82 kW

Annual energy consumption Qhe

5105 kWh

6718 kWh