1,280 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.13 kW
10.12 kW
El input
2.00 kW
3.20 kW
COP
5.06
3.17
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
53 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
145 %
Prated
12.87 kW
12.55 kW
SCOP
5.07
3.69
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.39 kW
11.10 kW
COP Tj = -7°C
3.13
2.39
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.00 kW
6.77 kW
COP Tj = +2°C
5.00
3.71
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.70 kW
5.07 kW
COP Tj = +7°C
6.78
4.71
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.62 kW
6.10 kW
COP Tj = 12°C
9.21
6.22
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.39 kW
11.10 kW
COP Tj = Tbiv
3.13
2.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.26 kW
10.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.74
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
16 W
16 W
PSB
15 W
15 W
PCK
50 W
50 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.61 kW
1.66 kW
Annual energy consumption Qhe
5244 kWh
7018 kWh