1,350 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.20 kW
15.10 kW
El input
3.38 kW
5.13 kW
COP
4.50
2.94
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
246 %
176 %
Prated
13.10 kW
13.80 kW
SCOP
6.23
4.48
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.97 kW
13.67 kW
COP Tj = +2°C
3.35
2.25
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
8.41 kW
8.87 kW
COP Tj = +7°C
5.31
3.80
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.29 kW
3.94 kW
COP Tj = 12°C
8.23
5.88
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
8.42 kW
8.87 kW
COP Tj = Tbiv
5.31
3.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.97 kW
13.67 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.13 kW
0.13 kW
Annual energy consumption Qhe
2811 kWh
4118 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
150 %
Prated
15.00 kW
13.00 kW
SCOP
4.77
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.27 kW
11.50 kW
COP Tj = -7°C
2.95
2.40
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.08 kW
7.00 kW
COP Tj = +2°C
4.40
3.64
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.19 kW
4.50 kW
COP Tj = +7°C
6.81
5.04
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.30 kW
4.00 kW
COP Tj = 12°C
9.95
7.65
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
13.27 kW
11.50 kW
COP Tj = Tbiv
2.95
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.50 kW
12.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
0.80 kW
Annual energy consumption Qhe
6492 kWh
7020 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.85
Heating up time
1:36 h:min
Standby power input
45.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
212 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.20 kW
13.90 kW
El input
3.02 kW
4.79 kW
COP
4.70
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
259 %
178 %
Prated
12.10 kW
13.70 kW
SCOP
6.56
4.53
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
12.00 kW
13.60 kW
COP Tj = +2°C
3.44
2.18
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.78 kW
8.83 kW
COP Tj = +7°C
5.84
3.91
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.23 kW
4.08 kW
COP Tj = 12°C
8.43
5.90
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.78 kW
8.83 kW
COP Tj = Tbiv
5.84
3.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
13.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.44
2.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.10 kW
0.10 kW
Annual energy consumption Qhe
2464 kWh
4037 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
150 %
Prated
14.50 kW
13.00 kW
SCOP
4.77
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.83 kW
11.50 kW
COP Tj = -7°C
2.98
2.40
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.81 kW
7.00 kW
COP Tj = +2°C
4.39
3.64
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.02 kW
4.50 kW
COP Tj = +7°C
6.80
5.04
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.30 kW
4.06 kW
COP Tj = 12°C
9.95
7.65
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
12.83 kW
11.50 kW
COP Tj = Tbiv
2.98
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.10 kW
12.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.40 kW
0.80 kW
Annual energy consumption Qhe
6275 kWh
7018 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.85
Heating up time
1:36 h:min
Standby power input
45.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
212 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
11.80 kW
El input
2.45 kW
4.03 kW
COP
4.90
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
254 %
174 %
Prated
11.30 kW
12.50 kW
SCOP
6.43
4.42
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.10 kW
12.30 kW
COP Tj = +2°C
3.59
2.31
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
7.26 kW
8.04 kW
COP Tj = +7°C
5.82
3.82
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.61 kW
3.57 kW
COP Tj = 12°C
8.30
5.70
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
7.26 kW
8.04 kW
COP Tj = Tbiv
5.82
3.82
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.10 kW
12.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.59
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.20 kW
0.20 kW
Annual energy consumption Qhe
2350 kWh
3775 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
150 %
Prated
13.20 kW
12.00 kW
SCOP
4.77
3.83
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.68 kW
10.62 kW
COP Tj = -7°C
2.99
2.40
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
7.11 kW
6.46 kW
COP Tj = +2°C
4.40
3.64
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.57 kW
4.15 kW
COP Tj = +7°C
6.77
5.04
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.30 kW
4.08 kW
COP Tj = 12°C
9.70
7.65
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.68 kW
10.62 kW
COP Tj = Tbiv
2.99
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.60 kW
11.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.07
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
20 W
20 W
PTO
30 W
30 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.60 kW
0.20 kW
Annual energy consumption Qhe
5712 kWh
6481 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.85
Heating up time
1:36 h:min
Standby power input
45.0 W
Reference hot water temperature
50.0 °C
Mixed water at 40°C
212 l