5,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50 kW
50 kW
El input
10.64 kW
15.15 kW
COP
4.7
3.3
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
80 dB(A)
80 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
247.7 %
189.3 %
Prated
50 kW
50 kW
SCOP
6.27
4.81
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
50 kW
48.86 kW
COP Tj = +2°C
3.42
2.6
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
32.41 kW
31.46 kW
COP Tj = +7°C
5.81
4.3
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.02 kW
14.04 kW
COP Tj = 12°C
8.05
6.36
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
32.41 kW
31.46 kW
COP Tj = Tbiv
5.81
4.3
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50 kW
48.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.42
2.6
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.14 kW
Annual energy consumption Qhe
10659 kWh
13898 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
80 dB(A)
80 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
138 %
Prated
50 kW
50 kW
SCOP
3.68
3.28
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
30.1 kW
30.33 kW
COP Tj = -7°C
3.45
2.85
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
17.98 kW
19.73 kW
COP Tj = +2°C
4.53
4.2
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.04 kW
12.35 kW
COP Tj = +7°C
6.63
5.69
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
7.83 kW
12.13 kW
COP Tj = 12°C
7.32
5.69
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
42.15 kW
40.33 kW
COP Tj = Tbiv
2.34
2.18
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
43.9 kW
50.54 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.6
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.1 kW
0 kW
Annual energy consumption Qhe
31231 kWh
35048 kWh
Pdh Tj = -15°C (if TOL<-20°C)
42.15
40.33
COP Tj = -15°C (if TOL<-20°C)
2.34
2.18
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
80 dB(A)
80 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
153 %
Prated
50 kW
50 kW
SCOP
4.7
3.9
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
45.18 kW
44.14 kW
COP Tj = -7°C
2.8
2.4
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
28.4 kW
28.61 kW
COP Tj = +2°C
4.49
3.86
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
17.57 kW
17.21 kW
COP Tj = +7°C
6.58
5.21
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
7.83 kW
12.09 kW
COP Tj = 12°C
7.59
6.24
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
45.18 kW
44.14 kW
COP Tj = Tbiv
2.8
2.4
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.39 kW
51.33 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.52
2.12
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
22051 kWh
26324 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
70 kW
70 kW
El input
17.5 kW
23.73 kW
COP
4
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
86.4 dB(A)
86.4 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
243.2 %
187.2 %
Prated
65 kW
65 kW
SCOP
6.15
4.75
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
63.03 kW
63.7 kW
COP Tj = +2°C
2.89
2.38
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
41.36 kW
41.07 kW
COP Tj = +7°C
5.5
4.13
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
18.37 kW
17.74 kW
COP Tj = 12°C
8.47
6.44
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
41.36 kW
41.07 kW
COP Tj = Tbiv
5.5
4.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
63.03 kW
63.7 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.89
2.38
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.97 kW
1.3 kW
Annual energy consumption Qhe
14110 kWh
18264 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
86.4 dB(A)
86.4 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
128 %
Prated
64 kW
64 kW
SCOP
3.95
3.52
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
39.69 kW
39.97 kW
COP Tj = -7°C
3.01
2.74
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
22.96 kW
24.38 kW
COP Tj = +2°C
4.45
3.8
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
14.53 kW
14.9 kW
COP Tj = +7°C
6.46
5.48
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
7.72 kW
12.15 kW
COP Tj = 12°C
7.43
5.45
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
52.33 kW
50.64 kW
COP Tj = Tbiv
2.1
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
43.9 kW
50.54 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.6
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
20.1 kW
13.46 kW
Annual energy consumption Qhe
42832 kWh
48107 kWh
Pdh Tj = -15°C (if TOL<-20°C)
52.33
50.64
COP Tj = -15°C (if TOL<-20°C)
2.1
2.04
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
86.4 dB(A)
86.4 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
147 %
Prated
65 kW
65 kW
SCOP
4.5
3.76
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
57.34 kW
57.95 kW
COP Tj = -7°C
2.48
2.13
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
34.71 kW
35.42 kW
COP Tj = +2°C
4.31
3.61
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
21.65 kW
21.58 kW
COP Tj = +7°C
6.59
5.36
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
9.79 kW
11.86 kW
COP Tj = 12°C
8.66
6.89
Cdh Tj = +12 °C
0.9
0.9
Pdh Tj = Tbiv
57.34 kW
57.95 kW
COP Tj = Tbiv
2.48
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.61 kW
64.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.36
1.95
WTOL
85 °C
85 °C
Poff
0.14 W
0.14 W
PTO
0.62 W
0.62 W
PSB
0.14 W
0.14 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.39 kW
0.54 kW
Annual energy consumption Qhe
29758 kWh
35694 kWh