3,150 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.10 kW
38.00 kW
El input
9.80 kW
13.10 kW
COP
4.10
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.20 kW
Cooling capacity
28.90
EER
3.14
EN 14825
+7°C/+12°C
Pdesignc
28.90 kW
SEER
4.86
Pdc Tj = 35°C
28.90 kW
EER Tj = 35°C
3.14
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
21.20 kW
EER Tj = 30°C
4.14
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
17.80 kW
EER Tj = 25°C
5.29
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
18.70 kW
EER Tj = 20°C
6.29
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
3565 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
130 %
Prated
36.00 kW
37.00 kW
SCOP
4.19
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
32.10 kW
32.50 kW
COP Tj = -7°C
2.64
1.84
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
20.10 kW
18.70 kW
COP Tj = +2°C
4.00
3.30
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
12.80 kW
13.10 kW
COP Tj = +7°C
5.61
4.54
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
16.90 kW
15.80 kW
COP Tj = 12°C
6.94
5.75
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
32.10 kW
32.50 kW
COP Tj = Tbiv
2.64
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
33.10 kW
31.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.43
1.63
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
78 °C
78 °C
Poff
45 W
45 W
PTO
45 W
45 W
PSB
41 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.90 kW
5.70 kW
Annual energy consumption Qhe
17869 kWh
22802 kWh