1,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.60 kW
11.61 kW
El input
2.61 kW
3.60 kW
COP
4.83
3.22
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
3.74 kW
Cooling capacity
10.67
EER
2.85
EN 14825
+7°C/+12°C
Pdesignc
10.67 kW
SEER
4.72
Pdc Tj = 35°C
10.67 kW
EER Tj = 35°C
2.85
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
8.17 kW
EER Tj = 30°C
4.04
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
5.10 kW
EER Tj = 25°C
5.26
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
4.31 kW
EER Tj = 20°C
6.63
Cdc Tj = 20 °C
0.966
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
1356 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
59 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
143 %
Prated
9.00 kW
10.00 kW
SCOP
4.71
3.65
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.10 kW
8.60 kW
COP Tj = -7°C
2.85
2.27
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.50 kW
4.85 kW
COP Tj = +2°C
4.48
3.44
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
3.30 kW
3.50 kW
COP Tj = +7°C
6.71
5.03
Cdh Tj = +7 °C
0.955
0.968
Pdh Tj = 12°C
3.70 kW
4.20 kW
COP Tj = 12°C
8.10
6.66
Cdh Tj = +12 °C
0.952
0.970
Pdh Tj = Tbiv
8.10 kW
8.60 kW
COP Tj = Tbiv
2.85
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
8.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
1.70 kW
Annual energy consumption Qhe
3994 kWh
5480 kWh