Mikrofill RenewAIR R290 RA-ASHP-R290-012

Certificate Holder
Dutypoint Ltd
Quedgeley West Business Park, Brtistol Road
Gl24 PA Gloucester
United Kingdom
Registration number
ICIM-PDC-000419
Certification Body
ICIM S.p.A.
Subtype title
Mikrofill RenewAIR R290 RA-ASHP-R290-012
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,000 kg

Certification Date
07.09.2026
Testing basis
V12
Generate PDF Export model CSV
  • Number of models 1

Models

Mikrofill RenewAIR R290 RA-ASHP-R290-012
Configure model
Model name
Mikrofill RenewAIR R290 RA-ASHP-R290-012
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

12.60 kW

11.61 kW

El input

2.61 kW

3.60 kW

COP

4.83

3.22

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

3.74 kW

Cooling capacity

10.67

EER

2.85

EN 14825

+7°C/+12°C

Pdesignc

10.67 kW

SEER

4.72

Pdc Tj = 35°C

10.67 kW

EER Tj = 35°C

2.85

Cdc Tj = 35 °C

1.000

Pdc Tj = 30°C

8.17 kW

EER Tj = 30°C

4.04

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

5.10 kW

EER Tj = 25°C

5.26

Cdc Tj = 25 °C

1.000

Pdc Tj = 20°C

4.31 kW

EER Tj = 20°C

6.63

Cdc Tj = 20 °C

0.966

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

1356 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

185 %

143 %

Prated

9.00 kW

10.00 kW

SCOP

4.71

3.65

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.10 kW

8.60 kW

COP Tj = -7°C

2.85

2.27

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

4.50 kW

4.85 kW

COP Tj = +2°C

4.48

3.44

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

3.30 kW

3.50 kW

COP Tj = +7°C

6.71

5.03

Cdh Tj = +7 °C

0.955

0.968

Pdh Tj = 12°C

3.70 kW

4.20 kW

COP Tj = 12°C

8.10

6.66

Cdh Tj = +12 °C

0.952

0.970

Pdh Tj = Tbiv

8.10 kW

8.60 kW

COP Tj = Tbiv

2.85

2.27

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.90 kW

8.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

2.05

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

75 °C

75 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.10 kW

1.70 kW

Annual energy consumption Qhe

3994 kWh

5480 kWh