1,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
9.00 kW
El input
1.84 kW
3.03 kW
COP
4.90
2.97
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
8.80 kW
Cooling capacity
2.83
EER
3.11
EN 14825
+7°C/+12°C
Pdesignc
8.00 kW
SEER
4.12
Pdc Tj = 35°C
8.00 kW
EER Tj = 35°C
3.19
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
5.89 kW
EER Tj = 30°C
3.91
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
3.79 kW
EER Tj = 25°C
4.25
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
1.68 kW
EER Tj = 20°C
5.13
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
679 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
10.00 kW
8.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
4.80 kW
COP Tj = -7°C
3.44
2.80
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.80 kW
4.50 kW
COP Tj = +2°C
5.26
3.78
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.60
5.14
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.20 kW
COP Tj = 12°C
8.03
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
8.40 kW
6.50 kW
COP Tj = Tbiv
2.70
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.50 kW
7.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
0.30 kW
Annual energy consumption Qhe
5725 kWh
6057 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.40
6.50
COP Tj = -15°C (if TOL<-20°C)
2.70
1.96
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
140 %
Prated
9.00 kW
9.00 kW
SCOP
4.96
3.57
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.00 kW
8.00 kW
COP Tj = -7°C
3.04
2.33
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.90 kW
4.90 kW
COP Tj = +2°C
4.93
3.46
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.40 kW
5.10 kW
COP Tj = +7°C
6.26
4.48
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.19
6.02
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
2.90
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3747 kWh
5208 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
9.00 kW
El input
1.84 kW
3.03 kW
COP
4.90
2.97
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
8.80 kW
Cooling capacity
2.83
EER
3.11
EN 14825
+7°C/+12°C
Pdesignc
8.00 kW
SEER
4.12
Pdc Tj = 35°C
8.00 kW
EER Tj = 35°C
3.19
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
5.89 kW
EER Tj = 30°C
3.91
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
3.79 kW
EER Tj = 25°C
4.25
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
1.68 kW
EER Tj = 20°C
5.13
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
679 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
10.00 kW
8.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
4.80 kW
COP Tj = -7°C
3.44
2.80
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.80 kW
4.50 kW
COP Tj = +2°C
5.26
3.78
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.60
5.14
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.20 kW
COP Tj = 12°C
8.03
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
8.40 kW
6.50 kW
COP Tj = Tbiv
2.70
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.50 kW
7.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
0.30 kW
Annual energy consumption Qhe
5725 kWh
6057 kWh
Pdh Tj = -15°C (if TOL<-20°C)
8.40
6.50
COP Tj = -15°C (if TOL<-20°C)
2.70
1.96
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
140 %
Prated
9.00 kW
9.00 kW
SCOP
4.96
3.57
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.00 kW
8.00 kW
COP Tj = -7°C
3.04
2.33
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.90 kW
4.90 kW
COP Tj = +2°C
4.93
3.46
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.40 kW
5.10 kW
COP Tj = +7°C
6.26
4.48
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.19
6.02
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
2.90
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
3747 kWh
5208 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.53 kW
4.05 kW
COP
4.78
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
10.70 kW
Cooling capacity
3.99
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
10.00 kW
SEER
4.44
Pdc Tj = 35°C
10.00 kW
EER Tj = 35°C
2.87
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
7.37 kW
EER Tj = 30°C
3.96
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
4.74 kW
EER Tj = 25°C
4.86
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.11 kW
EER Tj = 20°C
5.68
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
789 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.67
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.67
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
11.00 kW
9.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
6.70 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.80 kW
4.30 kW
COP Tj = +2°C
5.32
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.69
5.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.14
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
7.30 kW
COP Tj = Tbiv
2.70
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
6289 kWh
6801 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
7.30
COP Tj = -15°C (if TOL<-20°C)
2.70
2.15
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
140 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.58
Tbiv
-10 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
8.58 kW
COP Tj = -7°C
2.51
2.43
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.50 kW
6.08 kW
COP Tj = +2°C
4.53
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.12 kW
COP Tj = +7°C
6.18
4.95
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.40 kW
5.97 kW
COP Tj = 12°C
7.93
6.20
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
12.00 kW
8.66 kW
COP Tj = Tbiv
2.71
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.71
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.49 kW
Annual energy consumption Qhe
5416 kWh
6920 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.53 kW
4.05 kW
COP
4.78
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
10.70 kW
Cooling capacity
3.99
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
10.00 kW
SEER
4.44
Pdc Tj = 35°C
10.00 kW
EER Tj = 35°C
2.87
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
7.37 kW
EER Tj = 30°C
3.96
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
4.74 kW
EER Tj = 25°C
4.86
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.11 kW
EER Tj = 20°C
5.68
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
789 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.67
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.67
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
11.00 kW
9.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
6.70 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.80 kW
4.30 kW
COP Tj = +2°C
5.32
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.69
5.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.14
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
7.30 kW
COP Tj = Tbiv
2.70
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
6289 kWh
6801 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
7.30
COP Tj = -15°C (if TOL<-20°C)
2.70
2.15
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
140 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.58
Tbiv
-10 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
8.58 kW
COP Tj = -7°C
2.51
2.43
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.50 kW
6.08 kW
COP Tj = +2°C
4.53
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.12 kW
COP Tj = +7°C
6.18
4.95
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.40 kW
5.97 kW
COP Tj = 12°C
7.93
6.20
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
12.00 kW
8.66 kW
COP Tj = Tbiv
2.71
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.71
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.49 kW
Annual energy consumption Qhe
5416 kWh
6920 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.53 kW
4.05 kW
COP
4.78
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
10.70 kW
Cooling capacity
3.99
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
10.00 kW
SEER
4.44
Pdc Tj = 35°C
10.00 kW
EER Tj = 35°C
2.87
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
7.37 kW
EER Tj = 30°C
3.96
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
4.74 kW
EER Tj = 25°C
4.86
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.11 kW
EER Tj = 20°C
5.68
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
789 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.67
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.67
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
11.00 kW
9.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
6.70 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.80 kW
4.30 kW
COP Tj = +2°C
5.32
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.69
5.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.14
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
7.30 kW
COP Tj = Tbiv
2.70
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
6289 kWh
6801 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
7.30
COP Tj = -15°C (if TOL<-20°C)
2.70
2.15
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
140 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.58
Tbiv
-10 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.80 kW
8.58 kW
COP Tj = -7°C
3.04
2.43
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.70 kW
6.08 kW
COP Tj = +2°C
4.44
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.40 kW
5.12 kW
COP Tj = +7°C
5.80
4.95
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
5.97 kW
COP Tj = 12°C
6.81
6.20
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
12.00 kW
8.66 kW
COP Tj = Tbiv
2.90
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.49 kW
Annual energy consumption Qhe
5416 kWh
6920 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
96 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.53 kW
4.05 kW
COP
4.78
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
10.70 kW
Cooling capacity
3.99
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
10.00 kW
SEER
4.44
Pdc Tj = 35°C
10.00 kW
EER Tj = 35°C
2.87
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
7.37 kW
EER Tj = 30°C
3.96
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
4.74 kW
EER Tj = 25°C
4.86
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.11 kW
EER Tj = 20°C
5.68
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
789 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.67
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.67
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
11.00 kW
9.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
6.70 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.80 kW
4.30 kW
COP Tj = +2°C
5.32
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.69
5.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.14
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
7.30 kW
COP Tj = Tbiv
2.70
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
6289 kWh
6801 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
7.30
COP Tj = -15°C (if TOL<-20°C)
2.70
2.15
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
140 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.58
Tbiv
-10 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.80 kW
8.58 kW
COP Tj = -7°C
3.04
2.43
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.70 kW
6.08 kW
COP Tj = +2°C
4.44
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.40 kW
5.12 kW
COP Tj = +7°C
5.80
4.95
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
5.97 kW
COP Tj = 12°C
6.81
6.20
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
12.00 kW
8.66 kW
COP Tj = Tbiv
2.90
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.49 kW
Annual energy consumption Qhe
5416 kWh
6920 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
96 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.10 kW
12.00 kW
El input
2.53 kW
4.05 kW
COP
4.78
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
10.70 kW
Cooling capacity
3.99
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
10.00 kW
SEER
4.44
Pdc Tj = 35°C
10.00 kW
EER Tj = 35°C
2.87
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
7.37 kW
EER Tj = 30°C
3.96
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
4.74 kW
EER Tj = 25°C
4.86
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
2.11 kW
EER Tj = 20°C
5.68
Cdc Tj = 20 °C
1.000
Poff
10 W
PTO
0 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
789 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
256 %
171 %
Prated
9.00 kW
9.00 kW
SCOP
6.47
4.34
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
9.00 kW
9.00 kW
COP Tj = +2°C
3.67
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.80 kW
5.90 kW
COP Tj = +7°C
5.88
3.75
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.00 kW
COP Tj = 12°C
7.85
5.50
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
9.00 kW
COP Tj = Tbiv
3.67
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.00 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.67
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1859 kWh
2772 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
127 %
Prated
11.00 kW
9.00 kW
SCOP
4.31
3.26
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.70 kW
6.70 kW
COP Tj = -7°C
3.37
2.77
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
4.80 kW
4.30 kW
COP Tj = +2°C
5.32
3.73
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.50 kW
5.30 kW
COP Tj = +7°C
6.69
5.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
6.10 kW
COP Tj = 12°C
8.14
6.40
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.00 kW
7.30 kW
COP Tj = Tbiv
2.70
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
1.00 kW
Annual energy consumption Qhe
6289 kWh
6801 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.00
7.30
COP Tj = -15°C (if TOL<-20°C)
2.70
2.15
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
140 %
Prated
12.00 kW
12.00 kW
SCOP
4.58
3.58
Tbiv
-10 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.80 kW
8.58 kW
COP Tj = -7°C
3.04
2.43
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
6.70 kW
6.08 kW
COP Tj = +2°C
4.44
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.40 kW
5.12 kW
COP Tj = +7°C
5.80
4.95
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.30 kW
5.97 kW
COP Tj = 12°C
6.81
6.20
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
12.00 kW
8.66 kW
COP Tj = Tbiv
2.90
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
8.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.01
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
3.49 kW
Annual energy consumption Qhe
5416 kWh
6920 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
96 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
14.70 kW
El input
3.71 kW
5.40 kW
COP
4.31
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
12.20 kW
Cooling capacity
4.55
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
12.00 kW
SEER
4.77
Pdc Tj = 35°C
12.00 kW
EER Tj = 35°C
2.65
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
8.84 kW
EER Tj = 30°C
3.67
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
5.68 kW
EER Tj = 25°C
5.58
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
4.88 kW
EER Tj = 20°C
7.08
Cdc Tj = 20 °C
1.000
Poff
1 W
PTO
10 W
PSB
9 W
PCK
0 W
Annual energy consumption Qce
881 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
169 %
Prated
13.00 kW
10.00 kW
SCOP
6.20
4.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.00 kW
10.00 kW
COP Tj = +2°C
3.00
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
8.40 kW
6.40 kW
COP Tj = +7°C
5.67
3.73
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.70 kW
COP Tj = 12°C
7.57
5.41
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
13.00 kW
10.00 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2803 kWh
3104 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
121 %
Prated
12.00 kW
12.00 kW
SCOP
4.28
3.10
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.30 kW
7.30 kW
COP Tj = -7°C
3.63
2.62
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.40 kW
4.40 kW
COP Tj = +2°C
5.09
3.68
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.10 kW
4.90 kW
COP Tj = +7°C
6.31
4.61
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.80 kW
COP Tj = 12°C
7.54
5.83
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.80 kW
9.80 kW
COP Tj = Tbiv
2.64
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.00 kW
3.50 kW
Annual energy consumption Qhe
6917 kWh
9556 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.80
9.80
COP Tj = -15°C (if TOL<-20°C)
2.64
1.89
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
133 %
Prated
13.00 kW
13.00 kW
SCOP
4.46
3.40
Tbiv
-7 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
9.50 kW
COP Tj = -7°C
2.63
2.31
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.00 kW
7.00 kW
COP Tj = +2°C
4.26
3.32
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
5.10 kW
4.86 kW
COP Tj = +7°C
6.32
4.83
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.71 kW
COP Tj = 12°C
7.78
6.15
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
11.50 kW
9.50 kW
COP Tj = Tbiv
2.63
2.49
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.10 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
1.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.90 kW
3.00 kW
Annual energy consumption Qhe
6018 kWh
7911 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
14.70 kW
El input
3.71 kW
5.40 kW
COP
4.31
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
12.20 kW
Cooling capacity
4.55
EER
2.68
EN 14825
+7°C/+12°C
Pdesignc
12.00 kW
SEER
4.77
Pdc Tj = 35°C
12.00 kW
EER Tj = 35°C
2.65
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
8.84 kW
EER Tj = 30°C
3.67
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
5.68 kW
EER Tj = 25°C
5.58
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
4.88 kW
EER Tj = 20°C
7.08
Cdc Tj = 20 °C
1.000
Poff
1 W
PTO
10 W
PSB
9 W
PCK
0 W
Annual energy consumption Qce
881 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
169 %
Prated
13.00 kW
10.00 kW
SCOP
6.20
4.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.00 kW
10.00 kW
COP Tj = +2°C
3.00
2.40
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
8.40 kW
6.40 kW
COP Tj = +7°C
5.67
3.73
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.70 kW
COP Tj = 12°C
7.57
5.41
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
13.00 kW
10.00 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.00 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2803 kWh
3104 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
121 %
Prated
12.00 kW
12.00 kW
SCOP
4.28
3.10
Tbiv
-15 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
7.30 kW
7.30 kW
COP Tj = -7°C
3.63
2.62
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
4.40 kW
4.40 kW
COP Tj = +2°C
5.09
3.68
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.10 kW
4.90 kW
COP Tj = +7°C
6.31
4.61
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.80 kW
COP Tj = 12°C
7.54
5.83
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
9.80 kW
9.80 kW
COP Tj = Tbiv
2.64
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.00 kW
8.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.00 kW
3.50 kW
Annual energy consumption Qhe
6917 kWh
9556 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.80
9.80
COP Tj = -15°C (if TOL<-20°C)
2.64
1.89
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
46 dB(A)
46 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
133 %
Prated
13.00 kW
13.00 kW
SCOP
4.46
3.40
Tbiv
-7 °C
-3 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
9.50 kW
COP Tj = -7°C
2.63
2.31
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.00 kW
7.00 kW
COP Tj = +2°C
4.26
3.32
Cdh Tj = +2 °C
0.990
1.000
Pdh Tj = +7°C
5.10 kW
4.86 kW
COP Tj = +7°C
6.32
4.83
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.80 kW
5.71 kW
COP Tj = 12°C
7.78
6.15
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
11.50 kW
9.50 kW
COP Tj = Tbiv
2.63
2.49
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.10 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.87
1.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
1 W
1 W
PTO
10 W
10 W
PSB
9 W
9 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.90 kW
3.00 kW
Annual energy consumption Qhe
6018 kWh
7911 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:06 h:min
Standby power input
31.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
94 %
COP
2.35
Heating up time
1:06 h:min
Standby power input
45.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.08
Heating up time
1:06 h:min
Standby power input
34.0 W
Reference hot water temperature
53.0 °C
Mixed water at 40°C
323 l