1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.79 kW
16.99 kW
El input
3.56 kW
5.23 kW
COP
4.71
3.25
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
156 %
Prated
16.51 kW
16.54 kW
SCOP
5.13
3.97
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.61 kW
14.63 kW
COP Tj = -7°C
3.13
2.45
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
8.93 kW
8.97 kW
COP Tj = +2°C
5.08
3.89
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.73 kW
5.85 kW
COP Tj = +7°C
6.66
5.14
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.22 kW
5.91 kW
COP Tj = 12°C
9.25
7.41
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.61 kW
14.63 kW
COP Tj = Tbiv
3.13
2.45
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.34 kW
15.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
2.14
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
80 °C
80 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.18 kW
1.24 kW
Annual energy consumption Qhe
6649 kWh
8596 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.79 kW
16.96 kW
El input
3.57 kW
5.28 kW
COP
4.70
3.21
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
205 %
156 %
Prated
16.90 kW
16.69 kW
SCOP
5.17
3.97
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
14.95 kW
14.77 kW
COP Tj = -7°C
3.13
2.46
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.18 kW
9.00 kW
COP Tj = +2°C
5.06
3.87
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
5.93 kW
6.12 kW
COP Tj = +7°C
6.98
5.13
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.18 kW
5.82 kW
COP Tj = 12°C
9.26
7.36
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.95 kW
14.77 kW
COP Tj = Tbiv
3.13
2.44
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.00 kW
15.71 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.77
2.18
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.899
WTOL
80 °C
80 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.90 kW
0.98 kW
Annual energy consumption Qhe
6729 kWh
8692 kWh