0,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.13 kW
6.07 kW
El input
1.14 kW
1.78 kW
COP
5.38
3.41
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
47 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
219 %
160 %
Prated
6.38 kW
6.28 kW
SCOP
5.56
4.09
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.65 kW
5.56 kW
COP Tj = -7°C
3.45
2.42
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.73 kW
3.67 kW
COP Tj = +2°C
5.48
4.07
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
2.40 kW
2.33 kW
COP Tj = +7°C
7.35
5.42
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
2.59 kW
2.34 kW
COP Tj = 12°C
10.49
7.35
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.65 kW
5.56 kW
COP Tj = Tbiv
3.43
2.42
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.82 kW
5.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.41
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
80 °C
80 °C
Poff
9 W
9 W
PTO
9 W
9 W
PSB
9 W
9 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.57 kW
0.40 kW
Annual energy consumption Qhe
2372 kWh
3177 kWh