Certificate holders

Subtype

ADAPT 2 S

Certificate Holder
KRONOTERM d.o.o.
Trnava 5e
3303 Gomilsko
Slovenia
Registration number
011-1W1275
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
ADAPT 2 S
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,400 kg

Certification Date
08.06.2026
Testing basis
HP KEYMARK certification scheme rules rev. 15
Testing laboratory
TÜV Rheinland Energy GmbH, DE
Generate PDF Export model CSV
  • Number of models 1

Models

ADAPT 2 S / HK 1F
Configure model
Model name
ADAPT 2 S / HK 1F
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.95 kW

8.04 kW

El input

1.57 kW

2.49 kW

COP

5.07

3.23

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.77 kW

1.08 kW

Cooling capacity

5.48

5.57

EER

3.10

5.14

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5.50 kW

5.50 kW

SEER

4.80

7.09

Pdc Tj = 35°C

5.48 kW

5.57 kW

EER Tj = 35°C

3.10

5.14

Cdc Tj = 35 °C

1.000

0.990

Pdc Tj = 30°C

4.05 kW

4.02 kW

EER Tj = 30°C

4.21

6.58

Cdc Tj = 30 °C

0.990

0.990

Pdc Tj = 25°C

2.57 kW

2.60 kW

EER Tj = 25°C

5.04

7.66

Cdc Tj = 25 °C

0.980

0.980

Pdc Tj = 20°C

1.58 kW

1.94 kW

EER Tj = 20°C

6.02

7.70

Cdc Tj = 20 °C

0.970

0.970

Poff

8 W

8 W

PTO

8 W

8 W

PSB

8 W

8 W

PCK

8 W

8 W

Annual energy consumption Qce

720 kWh

498 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

41 dB(A)

43 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

297 %

196 %

Prated

7.00 kW

7.00 kW

SCOP

7.57

5.00

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

7.71 kW

6.96 kW

COP Tj = +2°C

3.79

2.76

Cdh Tj = +2 °C

0.996

0.997

Pdh Tj = +7°C

4.48 kW

4.43 kW

COP Tj = +7°C

6.46

4.19

Cdh Tj = +7 °C

0.989

0.993

Pdh Tj = 12°C

2.08 kW

1.95 kW

COP Tj = 12°C

9.72

6.51

Cdh Tj = +12 °C

0.963

0.973

Pdh Tj = Tbiv

7.71 kW

6.96 kW

COP Tj = Tbiv

3.79

2.76

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.71 kW

6.96 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.79

2.76

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.997

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

8 W

8 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1248 kWh

1883 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

41 dB(A)

43 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

196 %

144 %

Prated

7.50 kW

7.50 kW

SCOP

4.98

3.68

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

4.46 kW

4.61 kW

COP Tj = -7°C

3.89

2.94

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

2.78 kW

2.78 kW

COP Tj = +2°C

6.26

4.47

Cdh Tj = +2 °C

0.980

0.987

Pdh Tj = +7°C

1.90 kW

1.88 kW

COP Tj = +7°C

8.59

6.14

Cdh Tj = +7 °C

0.964

0.974

Pdh Tj = 12°C

2.11 kW

1.94 kW

COP Tj = 12°C

10.22

8.03

Cdh Tj = +12 °C

0.961

0.967

Pdh Tj = Tbiv

6.16 kW

6.10 kW

COP Tj = Tbiv

2.84

2.19

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.05 kW

5.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.38

1.73

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.997

0.998

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

8 W

8 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.45 kW

2.07 kW

Annual energy consumption Qhe

3715 kWh

5028 kWh

Pdh Tj = -15°C (if TOL<-20°C)

6.16

6.10

COP Tj = -15°C (if TOL<-20°C)

2.84

2.19

Cdh Tj = -15 °C

0.996

0.997

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

41 dB(A)

43 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

233 %

160 %

Prated

6.50 kW

6.50 kW

SCOP

5.91

4.08

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.44 kW

5.73 kW

COP Tj = -7°C

3.51

2.50

Cdh Tj = -7 °C

0.995

0.997

Pdh Tj = +2°C

3.37 kW

3.45 kW

COP Tj = +2°C

5.75

3.93

Cdh Tj = +2 °C

0.986

0.991

Pdh Tj = +7°C

2.23 kW

2.24 kW

COP Tj = +7°C

7.85

5.31

Cdh Tj = +7 °C

0.972

0.981

Pdh Tj = 12°C

2.11 kW

1.91 kW

COP Tj = 12°C

10.22

7.42

Cdh Tj = +12 °C

0.961

0.969

Pdh Tj = Tbiv

6.48 kW

6.43 kW

COP Tj = Tbiv

3.07

2.19

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.48 kW

6.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.07

2.19

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.996

0.997

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

8 W

8 W

PSB

8 W

8 W

PCK

8 W

8 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2277 kWh

3295 kWh