4,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.20 kW
50.13 kW
El input
11.21 kW
15.76 kW
COP
4.48
3.18
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
145 %
Prated
49.81 kW
50.01 kW
SCOP
4.61
3.71
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
44.07 kW
44.24 kW
COP Tj = -7°C
2.91
2.21
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
27.38 kW
27.02 kW
COP Tj = +2°C
4.53
3.65
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
17.53 kW
17.40 kW
COP Tj = +7°C
5.90
4.86
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
16.79 kW
16.31 kW
COP Tj = 12°C
8.14
6.72
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
44.07 kW
44.24 kW
COP Tj = Tbiv
2.91
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
49.15 kW
50.03 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
24 W
24 W
PTO
24 W
24 W
PSB
24 W
24 W
PCK
225 W
225 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.67 kW
0.00 kW
Annual energy consumption Qhe
22314 kWh
27877 kWh