7,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
49.66 kW
49.76 kW
El input
11.07 kW
16.09 kW
COP
4.49
3.09
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
144 %
Prated
50.32 kW
50.65 kW
SCOP
4.58
3.66
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
44.51 kW
44.80 kW
COP Tj = -7°C
2.77
2.12
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
27.84 kW
27.29 kW
COP Tj = +2°C
4.58
3.60
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
17.80 kW
18.14 kW
COP Tj = +7°C
5.89
4.98
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
21.10 kW
21.07 kW
COP Tj = 12°C
7.96
6.59
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
44.51 kW
44.80 kW
COP Tj = Tbiv
2.77
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
50.19 kW
50.28 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.25
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
70 °C
70 °C
Poff
16 W
16 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.12 kW
0.36 kW
Annual energy consumption Qhe
22688 kWh
28578 kWh