8,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.20 kW
48.30 kW
El input
12.20 kW
18.02 kW
COP
4.11
2.68
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
11.69 kW
Cooling capacity
36.30
EER
3.11
EN 14825
+7°C/+12°C
Pdesignc
36.30 kW
SEER
4.72
Pdc Tj = 35°C
36.30 kW
EER Tj = 35°C
3.11
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
26.80 kW
EER Tj = 30°C
3.93
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
21.65 kW
EER Tj = 25°C
5.00
Cdc Tj = 25 °C
0.990
Pdc Tj = 20°C
23.94 kW
EER Tj = 20°C
6.45
Cdc Tj = 20 °C
0.990
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
4614 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
127 %
Prated
44.00 kW
44.00 kW
SCOP
4.28
3.24
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
39.00 kW
38.70 kW
COP Tj = -7°C
2.58
1.71
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
24.60 kW
23.30 kW
COP Tj = +2°C
4.21
3.23
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
24.10 kW
23.10 kW
COP Tj = +7°C
5.60
4.51
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
24.80 kW
27.00 kW
COP Tj = 12°C
7.05
5.69
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
39.00 kW
38.70 kW
COP Tj = Tbiv
2.58
1.71
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
36.40 kW
36.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.31
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
58 °C
58 °C
Poff
35 W
41 W
PTO
32 W
40 W
PSB
35 W
41 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.60 kW
8.00 kW
Annual energy consumption Qhe
21164 kWh
28117 kWh