Certificate holders

Subtype

Royalstar Heat pump 16KW

Certificate Holder
Hefei Royalstar Solar Energy Co. Ltd
Shuangfeng Economic Development Zone
231131 Changfeng County, Hefei City, Anhui Province
China
Registration number
011-1W1196
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Royalstar Heat pump 16KW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

1,150 kg

Certification Date
20.01.2026
Testing basis
HP KEYMARK certification scheme rules rev. 15
Testing laboratory
Intertek Testing Services Shenzhen LTD. Guangzhou Branch, CN
Generate PDF Export model CSV
  • Number of models 1

Models

RLKS-C16DII
Configure model
Model name
RLKS-C16DII
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

15.40 kW

El input

3.55 kW

5.10 kW

COP

4.51

3.02

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

194 %

146 %

Prated

13.70 kW

13.60 kW

SCOP

4.92

3.72

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.01 kW

11.94 kW

COP Tj = -7°C

3.05

2.22

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.46 kW

7.44 kW

COP Tj = +2°C

4.80

3.47

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

6.30 kW

6.03 kW

COP Tj = +7°C

6.47

4.90

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

7.13 kW

7.03 kW

COP Tj = 12°C

8.24

6.48

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

12.01 kW

11.94 kW

COP Tj = Tbiv

3.05

2.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.86 kW

12.96 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.93

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

75 °C

75 °C

Poff

13 W

13 W

PTO

13 W

13 W

PSB

13 W

13 W

PCK

45 W

45 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.84 kW

0.64 kW

Annual energy consumption Qhe

5695 kWh

7691 kWh