2,000 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
10.42 kW
14.83 kW
El input
3.63 kW
5.05 kW
COP
4.25
2.94
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
141 %
Prated
18.00 kW
18.00 kW
SCOP
4.70
3.72
Tbiv
-17 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
15.60 kW
14.70 kW
COP Tj = -7°C
4.73
3.60
Pdh Tj = +2°C
15.70 kW
15.00 kW
COP Tj = +2°C
4.85
3.95
Pdh Tj = +7°C
15.80 kW
15.30 kW
COP Tj = +7°C
4.84
4.21
Pdh Tj = 12°C
15.80 kW
15.50 kW
COP Tj = 12°C
4.49
4.35
Pdh Tj = Tbiv
15.50 kW
14.60 kW
COP Tj = Tbiv
4.58
3.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.40 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.41
2.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
60 W
60 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.60 kW
3.40 kW
Annual energy consumption Qhe
9454 kWh
11893 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
138 %
Prated
18.00 kW
18.00 kW
SCOP
4.57
3.65
Tbiv
-6 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.40 kW
6.00 kW
COP Tj = -7°C
4.52
3.16
Pdh Tj = +2°C
15.60 kW
14.80 kW
COP Tj = +2°C
4.70
3.72
Pdh Tj = +7°C
15.70 kW
15.10 kW
COP Tj = +7°C
4.82
4.01
Pdh Tj = 12°C
15.80 kW
15.40 kW
COP Tj = 12°C
4.73
4.27
Pdh Tj = Tbiv
15.50 kW
14.60 kW
COP Tj = Tbiv
4.55
3.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.40 kW
14.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.41
2.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
60 W
60 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.60 kW
3.40 kW
Annual energy consumption Qhe
8134 kWh
10194 kWh