Certificate holders

Subtype

Thermia Mega E M 400V

Certificate Holder
Thermia
Snickaregatan 1
Arvika
Sweden
Registration number
012-C700191 / Issue 2
Certification Body
RISE CERT
Subtype title
Thermia Mega E M 400V
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R454B
Mass of Refrigerant

4,500 kg

Certification Date
17.06.2024
Testing basis
EN 14511:2022, EN 14825:2022, EN 12102:2022
Testing laboratory
RISE Research Institutes of Sweden
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

Thermia Mega E M 400V
Configure model
Model name
Thermia Mega E M 400V
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

26.89 kW

25.23 kW

El input

5.98 kW

8.54 kW

COP

4.50

2.95

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

159 %

Prated

44.39 kW

41.89 kW

SCOP

5.42

4.19

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

44.39 kW

41.89 kW

COP Tj = +2°C

3.84

2.72

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

28.54 kW

26.93 kW

COP Tj = +7°C

4.87

3.61

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

12.68 kW

11.97 kW

COP Tj = 12°C

6.31

5.12

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

44.39 kW

41.89 kW

COP Tj = Tbiv

3.84

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.39 kW

41.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.84

2.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

10939 kWh

13370 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

213 %

163 %

Prated

44.39 kW

41.89 kW

SCOP

5.54

4.27

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

26.87 kW

25.35 kW

COP Tj = -7°C

5.08

3.83

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

16.35 kW

15.43 kW

COP Tj = +2°C

6.01

4.71

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

11.49 kW

11.45 kW

COP Tj = +7°C

6.54

5.24

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

11.48 kW

11.45 kW

COP Tj = 12°C

6.13

5.26

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

44.39 kW

41.89 kW

COP Tj = Tbiv

3.84

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.39 kW

41.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.84

2.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

19763 kWh

24167 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

204 %

155 %

Prated

44.39 kW

41.89 kW

SCOP

5.29

4.09

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

39.27 kW

37.05 kW

COP Tj = -7°C

4.16

2.95

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

23.90 kW

22.55 kW

COP Tj = +2°C

5.23

4.07

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

15.37 kW

14.50 kW

COP Tj = +7°C

6.08

4.83

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

11.48 kW

11.44 kW

COP Tj = 12°C

6.31

5.17

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

44.39 kW

41.89 kW

COP Tj = Tbiv

3.84

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.39 kW

41.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.84

2.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

17334 kWh

21183 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

35.91 kW

33.53 kW

El input

6.11 kW

8.74 kW

COP

5.87

3.84

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

309 %

223 %

Prated

60.14 kW

57.04 kW

SCOP

7.93

5.76

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

60.14 kW

57.04 kW

COP Tj = +2°C

4.88

3.65

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

38.66 kW

36.67 kW

COP Tj = +7°C

6.93

4.87

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

17.18 kW

16.30 kW

COP Tj = 12°C

9.71

7.22

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

60.14 kW

57.04 kW

COP Tj = Tbiv

4.88

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

60.14 kW

57.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.88

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

10131 kWh

13222 kWh

Colder Climate

EN 14825

Low temperature

Medium temperature

ηs

319 %

228 %

Prated

60.14 kW

57.04 kW

SCOP

8.17

5.90

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

36.40 kW

34.52 kW

COP Tj = -7°C

7.30

5.17

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

22.16 kW

21.01 kW

COP Tj = +2°C

9.17

6.55

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

14.24 kW

13.51 kW

COP Tj = +7°C

10.12

7.71

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

14.97 kW

14.85 kW

COP Tj = 12°C

9.25

7.47

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

60.14 kW

57.04 kW

COP Tj = Tbiv

4.88

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

60.14 kW

57.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.88

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

18151 kWh

23833 kWh

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

297 %

217 %

Prated

60.14 kW

57.04 kW

SCOP

7.63

5.62

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

53.20 kW

50.46 kW

COP Tj = -7°C

5.35

3.99

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

32.38 kW

30.71 kW

COP Tj = +2°C

7.61

5.54

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

20.82 kW

19.74 kW

COP Tj = +7°C

9.23

6.77

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

15.04 kW

14.82 kW

COP Tj = 12°C

9.68

7.32

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

60.14 kW

57.04 kW

COP Tj = Tbiv

4.88

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

60.14 kW

57.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.88

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

16276 kWh

20986 kWh