4,500 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
26.89 kW
25.23 kW
El input
5.98 kW
8.54 kW
COP
4.50
2.95
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
209 %
159 %
Prated
44.39 kW
41.89 kW
SCOP
5.42
4.19
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
44.39 kW
41.89 kW
COP Tj = +2°C
3.84
2.72
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
28.54 kW
26.93 kW
COP Tj = +7°C
4.87
3.61
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
12.68 kW
11.97 kW
COP Tj = 12°C
6.31
5.12
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
44.39 kW
41.89 kW
COP Tj = Tbiv
3.84
2.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.39 kW
41.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.84
2.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
10939 kWh
13370 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
213 %
163 %
Prated
44.39 kW
41.89 kW
SCOP
5.54
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
26.87 kW
25.35 kW
COP Tj = -7°C
5.08
3.83
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
16.35 kW
15.43 kW
COP Tj = +2°C
6.01
4.71
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
11.49 kW
11.45 kW
COP Tj = +7°C
6.54
5.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
11.48 kW
11.45 kW
COP Tj = 12°C
6.13
5.26
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
44.39 kW
41.89 kW
COP Tj = Tbiv
3.84
2.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.39 kW
41.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.84
2.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
19763 kWh
24167 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
155 %
Prated
44.39 kW
41.89 kW
SCOP
5.29
4.09
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
39.27 kW
37.05 kW
COP Tj = -7°C
4.16
2.95
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
23.90 kW
22.55 kW
COP Tj = +2°C
5.23
4.07
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
15.37 kW
14.50 kW
COP Tj = +7°C
6.08
4.83
Cdh Tj = +7 °C
0.990
1.000
Pdh Tj = 12°C
11.48 kW
11.44 kW
COP Tj = 12°C
6.31
5.17
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
44.39 kW
41.89 kW
COP Tj = Tbiv
3.84
2.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
44.39 kW
41.89 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.84
2.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
17334 kWh
21183 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
35.91 kW
33.53 kW
El input
6.11 kW
8.74 kW
COP
5.87
3.84
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
309 %
223 %
Prated
60.14 kW
57.04 kW
SCOP
7.93
5.76
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
60.14 kW
57.04 kW
COP Tj = +2°C
4.88
3.65
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
38.66 kW
36.67 kW
COP Tj = +7°C
6.93
4.87
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
17.18 kW
16.30 kW
COP Tj = 12°C
9.71
7.22
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
60.14 kW
57.04 kW
COP Tj = Tbiv
4.88
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
60.14 kW
57.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.88
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
10131 kWh
13222 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
319 %
228 %
Prated
60.14 kW
57.04 kW
SCOP
8.17
5.90
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
36.40 kW
34.52 kW
COP Tj = -7°C
7.30
5.17
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
22.16 kW
21.01 kW
COP Tj = +2°C
9.17
6.55
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
14.24 kW
13.51 kW
COP Tj = +7°C
10.12
7.71
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
14.97 kW
14.85 kW
COP Tj = 12°C
9.25
7.47
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
60.14 kW
57.04 kW
COP Tj = Tbiv
4.88
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
60.14 kW
57.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.88
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
18151 kWh
23833 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
297 %
217 %
Prated
60.14 kW
57.04 kW
SCOP
7.63
5.62
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
53.20 kW
50.46 kW
COP Tj = -7°C
5.35
3.99
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
32.38 kW
30.71 kW
COP Tj = +2°C
7.61
5.54
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
20.82 kW
19.74 kW
COP Tj = +7°C
9.23
6.77
Cdh Tj = +7 °C
0.990
1.000
Pdh Tj = 12°C
15.04 kW
14.82 kW
COP Tj = 12°C
9.68
7.32
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
60.14 kW
57.04 kW
COP Tj = Tbiv
4.88
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
60.14 kW
57.04 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.88
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
16276 kWh
20986 kWh