0,680 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.20 kW
7.60 kW
El input
2.20 kW
3.00 kW
COP
3.80
2.56
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
38 dB(A)
44 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173 %
136 %
Prated
5.70 kW
5.70 kW
SCOP
4.39
3.48
Tbiv
-7 °C
-7 °C
TOL
-15 °C
-15 °C
Pdh Tj = -7°C
3.71 kW
3.69 kW
COP Tj = -7°C
3.21
2.47
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
2.15 kW
2.03 kW
COP Tj = +2°C
4.90
3.87
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.03 kW
1.98 kW
COP Tj = +7°C
6.11
5.08
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.36 kW
2.34 kW
COP Tj = 12°C
7.64
6.92
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
3.71 kW
3.69 kW
COP Tj = Tbiv
3.22
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.82 kW
3.82 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.95
1.59
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
21 W
21 W
PTO
21 W
21 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
5.70 kW
5.70 kW
Annual energy consumption Qhe
3201 kWh
4042 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.82
3.82
COP Tj = -15°C (if TOL<-20°C)
1.95
1.59
Cdh Tj = -15 °C
1.000
1.000
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
38 dB(A)
44 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
134 %
Prated
4.70 kW
4.50 kW
SCOP
4.52
3.42
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.38 kW
4.04 kW
COP Tj = -7°C
2.87
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
2.50 kW
2.60 kW
COP Tj = +2°C
4.46
3.30
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.01 kW
1.93 kW
COP Tj = +7°C
5.83
4.51
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
2.37 kW
2.31 kW
COP Tj = 12°C
7.61
6.48
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
4.38 kW
4.43 kW
COP Tj = Tbiv
2.87
1.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.84 kW
4.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.66
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
0 W
0 W
PTO
21 W
21 W
PSB
0 W
0 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.86 kW
0.00 kW
Annual energy consumption Qhe
2150 kWh
2715 kWh