0,520 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.20 kW
10.23 kW
El input
1.27 kW
3.49 kW
COP
4.87
2.93
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
159 %
Prated
11.34 kW
10.23 kW
SCOP
5.39
4.18
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.34 kW
10.23 kW
COP Tj = +2°C
4.19
2.93
Cdh Tj = +2 °C
0.994
0.995
Pdh Tj = +7°C
7.29 kW
6.58 kW
COP Tj = +7°C
5.25
3.82
Cdh Tj = +7 °C
0.988
0.990
Pdh Tj = 12°C
3.24 kW
2.92 kW
COP Tj = 12°C
6.03
4.99
Cdh Tj = +12 °C
0.970
0.972
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2811 kWh
3269 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
163 %
Prated
11.34 kW
10.23 kW
SCOP
5.58
4.28
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.87 kW
6.19 kW
COP Tj = -7°C
5.46
4.00
Cdh Tj = -7 °C
0.986
0.989
Pdh Tj = +2°C
4.18 kW
3.77 kW
COP Tj = +2°C
5.96
4.70
Cdh Tj = +2 °C
0.977
0.979
Pdh Tj = +7°C
3.16 kW
2.72 kW
COP Tj = +7°C
6.03
4.85
Cdh Tj = +7 °C
0.968
0.970
Pdh Tj = 12°C
3.13 kW
2.72 kW
COP Tj = 12°C
5.80
4.86
Cdh Tj = +12 °C
0.969
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.43 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.944
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5007 kWh
5896 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
160 %
Prated
11.34 kW
10.23 kW
SCOP
5.40
4.19
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.03 kW
9.05 kW
COP Tj = -7°C
4.57
3.36
Cdh Tj = -7 °C
0.992
0.994
Pdh Tj = +2°C
6.11 kW
5.51 kW
COP Tj = +2°C
5.53
4.30
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.93 kW
3.54 kW
COP Tj = +7°C
6.01
4.71
Cdh Tj = +7 °C
0.976
0.978
Pdh Tj = 12°C
3.15 kW
2.70 kW
COP Tj = 12°C
5.94
4.77
Cdh Tj = +12 °C
0.968
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4337 kWh
5046 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
13.85 kW
13.46 kW
El input
2.93 kW
3.76 kW
COP
4.73
3.58
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
262 %
204 %
Prated
13.85 kW
13.46 kW
SCOP
6.76
5.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.85 kW
13.46 kW
COP Tj = +2°C
4.73
3.58
Cdh Tj = +2 °C
0.994
0.997
Pdh Tj = +7°C
8.90 kW
8.65 kW
COP Tj = +7°C
6.95
4.71
Cdh Tj = +7 °C
0.987
0.994
Pdh Tj = 12°C
3.96 kW
3.82 kW
COP Tj = 12°C
7.33
6.69
Cdh Tj = +12 °C
0.969
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2738 kWh
3394 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
274 %
218 %
Prated
13.85 kW
13.46 kW
SCOP
7.06
5.65
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.38 kW
8.15 kW
COP Tj = -7°C
7.20
5.08
Cdh Tj = -7 °C
0.986
0.993
Pdh Tj = +2°C
5.10 kW
4.96 kW
COP Tj = +2°C
7.47
6.36
Cdh Tj = +2 °C
0.976
0.986
Pdh Tj = +7°C
3.45 kW
3.82 kW
COP Tj = +7°C
7.33
6.80
Cdh Tj = +7 °C
0.964
0.979
Pdh Tj = 12°C
3.58 kW
3.82 kW
COP Tj = 12°C
7.34
6.84
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4834 kWh
5868 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
209 %
Prated
13.85 kW
13.46 kW
SCOP
6.88
5.42
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.25 kW
11.91 kW
COP Tj = -7°C
5.73
4.02
Cdh Tj = -7 °C
0.992
0.996
Pdh Tj = +2°C
7.46 kW
7.25 kW
COP Tj = +2°C
7.28
5.38
Cdh Tj = +2 °C
0.985
0.992
Pdh Tj = +7°C
4.79 kW
4.66 kW
COP Tj = +7°C
7.41
6.57
Cdh Tj = +7 °C
0.974
0.985
Pdh Tj = 12°C
3.52 kW
3.82 kW
COP Tj = 12°C
7.33
6.74
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4160 kWh
5134 kWh
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.20 kW
10.23 kW
El input
1.27 kW
3.49 kW
COP
4.87
2.93
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
159 %
Prated
11.34 kW
10.23 kW
SCOP
5.39
4.18
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.34 kW
10.23 kW
COP Tj = +2°C
4.19
2.93
Cdh Tj = +2 °C
0.994
0.995
Pdh Tj = +7°C
7.29 kW
6.58 kW
COP Tj = +7°C
5.25
3.82
Cdh Tj = +7 °C
0.988
0.990
Pdh Tj = 12°C
3.24 kW
2.92 kW
COP Tj = 12°C
6.03
4.99
Cdh Tj = +12 °C
0.970
0.972
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2811 kWh
3269 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
163 %
Prated
11.34 kW
10.23 kW
SCOP
5.58
4.28
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.87 kW
6.19 kW
COP Tj = -7°C
5.46
4.00
Cdh Tj = -7 °C
0.986
0.989
Pdh Tj = +2°C
4.18 kW
3.77 kW
COP Tj = +2°C
5.96
4.70
Cdh Tj = +2 °C
0.977
0.979
Pdh Tj = +7°C
3.16 kW
2.72 kW
COP Tj = +7°C
6.03
4.85
Cdh Tj = +7 °C
0.968
0.970
Pdh Tj = 12°C
3.13 kW
2.72 kW
COP Tj = 12°C
5.80
4.86
Cdh Tj = +12 °C
0.969
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.43 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.944
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5007 kWh
5896 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
160 %
Prated
11.34 kW
10.23 kW
SCOP
5.40
4.19
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.03 kW
9.05 kW
COP Tj = -7°C
4.57
3.36
Cdh Tj = -7 °C
0.992
0.994
Pdh Tj = +2°C
6.11 kW
5.51 kW
COP Tj = +2°C
5.53
4.30
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.93 kW
3.54 kW
COP Tj = +7°C
6.01
4.71
Cdh Tj = +7 °C
0.976
0.978
Pdh Tj = 12°C
3.15 kW
2.70 kW
COP Tj = 12°C
5.94
4.77
Cdh Tj = +12 °C
0.968
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4337 kWh
5046 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
13.85 kW
13.46 kW
El input
2.93 kW
3.76 kW
COP
4.73
3.58
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
262 %
204 %
Prated
13.85 kW
13.46 kW
SCOP
6.76
5.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.85 kW
13.46 kW
COP Tj = +2°C
4.73
3.58
Cdh Tj = +2 °C
0.994
0.997
Pdh Tj = +7°C
8.90 kW
8.65 kW
COP Tj = +7°C
6.95
4.71
Cdh Tj = +7 °C
0.987
0.994
Pdh Tj = 12°C
3.96 kW
3.82 kW
COP Tj = 12°C
7.33
6.69
Cdh Tj = +12 °C
0.969
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2738 kWh
3394 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
274 %
218 %
Prated
13.85 kW
13.46 kW
SCOP
7.06
5.65
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.38 kW
8.15 kW
COP Tj = -7°C
7.20
5.08
Cdh Tj = -7 °C
0.986
0.993
Pdh Tj = +2°C
5.10 kW
4.96 kW
COP Tj = +2°C
7.47
6.36
Cdh Tj = +2 °C
0.976
0.986
Pdh Tj = +7°C
3.45 kW
3.82 kW
COP Tj = +7°C
7.33
6.80
Cdh Tj = +7 °C
0.964
0.979
Pdh Tj = 12°C
3.58 kW
3.82 kW
COP Tj = 12°C
7.34
6.84
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4834 kWh
5868 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
209 %
Prated
13.85 kW
13.46 kW
SCOP
6.88
5.42
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.25 kW
11.91 kW
COP Tj = -7°C
5.73
4.02
Cdh Tj = -7 °C
0.992
0.996
Pdh Tj = +2°C
7.46 kW
7.25 kW
COP Tj = +2°C
7.28
5.38
Cdh Tj = +2 °C
0.985
0.992
Pdh Tj = +7°C
4.79 kW
4.66 kW
COP Tj = +7°C
7.41
6.57
Cdh Tj = +7 °C
0.974
0.985
Pdh Tj = 12°C
3.52 kW
3.82 kW
COP Tj = 12°C
7.33
6.74
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4160 kWh
5134 kWh
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.20 kW
10.23 kW
El input
1.27 kW
3.49 kW
COP
4.87
2.93
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
159 %
Prated
11.34 kW
10.23 kW
SCOP
5.39
4.18
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.34 kW
10.23 kW
COP Tj = +2°C
4.19
2.93
Cdh Tj = +2 °C
0.994
0.995
Pdh Tj = +7°C
7.29 kW
6.58 kW
COP Tj = +7°C
5.25
3.82
Cdh Tj = +7 °C
0.988
0.990
Pdh Tj = 12°C
3.24 kW
2.92 kW
COP Tj = 12°C
6.03
4.99
Cdh Tj = +12 °C
0.970
0.972
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2811 kWh
3269 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
163 %
Prated
11.34 kW
10.23 kW
SCOP
5.58
4.28
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.87 kW
6.19 kW
COP Tj = -7°C
5.46
4.00
Cdh Tj = -7 °C
0.986
0.989
Pdh Tj = +2°C
4.18 kW
3.77 kW
COP Tj = +2°C
5.96
4.70
Cdh Tj = +2 °C
0.977
0.979
Pdh Tj = +7°C
3.16 kW
2.72 kW
COP Tj = +7°C
6.03
4.85
Cdh Tj = +7 °C
0.968
0.970
Pdh Tj = 12°C
3.13 kW
2.72 kW
COP Tj = 12°C
5.80
4.86
Cdh Tj = +12 °C
0.969
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.43 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.944
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5007 kWh
5896 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
160 %
Prated
11.34 kW
10.23 kW
SCOP
5.40
4.19
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.03 kW
9.05 kW
COP Tj = -7°C
4.57
3.36
Cdh Tj = -7 °C
0.992
0.994
Pdh Tj = +2°C
6.11 kW
5.51 kW
COP Tj = +2°C
5.53
4.30
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.93 kW
3.54 kW
COP Tj = +7°C
6.01
4.71
Cdh Tj = +7 °C
0.976
0.978
Pdh Tj = 12°C
3.15 kW
2.70 kW
COP Tj = 12°C
5.94
4.77
Cdh Tj = +12 °C
0.968
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4337 kWh
5046 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
13.85 kW
13.46 kW
El input
2.93 kW
3.76 kW
COP
4.73
3.58
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
262 %
204 %
Prated
13.85 kW
13.46 kW
SCOP
6.76
5.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.85 kW
13.46 kW
COP Tj = +2°C
4.73
3.58
Cdh Tj = +2 °C
0.994
0.997
Pdh Tj = +7°C
8.90 kW
8.65 kW
COP Tj = +7°C
6.95
4.71
Cdh Tj = +7 °C
0.987
0.994
Pdh Tj = 12°C
3.96 kW
3.82 kW
COP Tj = 12°C
7.33
6.69
Cdh Tj = +12 °C
0.969
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2738 kWh
3394 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
274 %
218 %
Prated
13.85 kW
13.46 kW
SCOP
7.06
5.65
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.38 kW
8.15 kW
COP Tj = -7°C
7.20
5.08
Cdh Tj = -7 °C
0.986
0.993
Pdh Tj = +2°C
5.10 kW
4.96 kW
COP Tj = +2°C
7.47
6.36
Cdh Tj = +2 °C
0.976
0.986
Pdh Tj = +7°C
3.45 kW
3.82 kW
COP Tj = +7°C
7.33
6.80
Cdh Tj = +7 °C
0.964
0.979
Pdh Tj = 12°C
3.58 kW
3.82 kW
COP Tj = 12°C
7.34
6.84
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4834 kWh
5868 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
209 %
Prated
13.85 kW
13.46 kW
SCOP
6.88
5.42
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.25 kW
11.91 kW
COP Tj = -7°C
5.73
4.02
Cdh Tj = -7 °C
0.992
0.996
Pdh Tj = +2°C
7.46 kW
7.25 kW
COP Tj = +2°C
7.28
5.38
Cdh Tj = +2 °C
0.985
0.992
Pdh Tj = +7°C
4.79 kW
4.66 kW
COP Tj = +7°C
7.41
6.57
Cdh Tj = +7 °C
0.974
0.985
Pdh Tj = 12°C
3.52 kW
3.82 kW
COP Tj = 12°C
7.33
6.74
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4160 kWh
5134 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.20 kW
10.23 kW
El input
1.27 kW
3.49 kW
COP
4.87
2.93
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
159 %
Prated
11.34 kW
10.23 kW
SCOP
5.39
4.18
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
11.34 kW
10.23 kW
COP Tj = +2°C
4.19
2.93
Cdh Tj = +2 °C
0.994
0.995
Pdh Tj = +7°C
7.29 kW
6.58 kW
COP Tj = +7°C
5.25
3.82
Cdh Tj = +7 °C
0.988
0.990
Pdh Tj = 12°C
3.24 kW
2.92 kW
COP Tj = 12°C
6.03
4.99
Cdh Tj = +12 °C
0.970
0.972
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2811 kWh
3269 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
163 %
Prated
11.34 kW
10.23 kW
SCOP
5.58
4.28
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
6.87 kW
6.19 kW
COP Tj = -7°C
5.46
4.00
Cdh Tj = -7 °C
0.986
0.989
Pdh Tj = +2°C
4.18 kW
3.77 kW
COP Tj = +2°C
5.96
4.70
Cdh Tj = +2 °C
0.977
0.979
Pdh Tj = +7°C
3.16 kW
2.72 kW
COP Tj = +7°C
6.03
4.85
Cdh Tj = +7 °C
0.968
0.970
Pdh Tj = 12°C
3.13 kW
2.72 kW
COP Tj = 12°C
5.80
4.86
Cdh Tj = +12 °C
0.969
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.43 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.944
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5007 kWh
5896 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
160 %
Prated
11.34 kW
10.23 kW
SCOP
5.40
4.19
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.03 kW
9.05 kW
COP Tj = -7°C
4.57
3.36
Cdh Tj = -7 °C
0.992
0.994
Pdh Tj = +2°C
6.11 kW
5.51 kW
COP Tj = +2°C
5.53
4.30
Cdh Tj = +2 °C
0.984
0.987
Pdh Tj = +7°C
3.93 kW
3.54 kW
COP Tj = +7°C
6.01
4.71
Cdh Tj = +7 °C
0.976
0.978
Pdh Tj = 12°C
3.15 kW
2.70 kW
COP Tj = 12°C
5.94
4.77
Cdh Tj = +12 °C
0.968
0.970
Pdh Tj = Tbiv
11.34 kW
10.23 kW
COP Tj = Tbiv
4.19
2.93
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.34 kW
10.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.19
2.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4337 kWh
5046 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
13.85 kW
13.46 kW
El input
2.93 kW
3.76 kW
COP
4.73
3.58
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
262 %
204 %
Prated
13.85 kW
13.46 kW
SCOP
6.76
5.30
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
13.85 kW
13.46 kW
COP Tj = +2°C
4.73
3.58
Cdh Tj = +2 °C
0.994
0.997
Pdh Tj = +7°C
8.90 kW
8.65 kW
COP Tj = +7°C
6.95
4.71
Cdh Tj = +7 °C
0.987
0.994
Pdh Tj = 12°C
3.96 kW
3.82 kW
COP Tj = 12°C
7.33
6.69
Cdh Tj = +12 °C
0.969
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2738 kWh
3394 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
274 %
218 %
Prated
13.85 kW
13.46 kW
SCOP
7.06
5.65
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
8.38 kW
8.15 kW
COP Tj = -7°C
7.20
5.08
Cdh Tj = -7 °C
0.986
0.993
Pdh Tj = +2°C
5.10 kW
4.96 kW
COP Tj = +2°C
7.47
6.36
Cdh Tj = +2 °C
0.976
0.986
Pdh Tj = +7°C
3.45 kW
3.82 kW
COP Tj = +7°C
7.33
6.80
Cdh Tj = +7 °C
0.964
0.979
Pdh Tj = 12°C
3.58 kW
3.82 kW
COP Tj = 12°C
7.34
6.84
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4834 kWh
5868 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
267 %
209 %
Prated
13.85 kW
13.46 kW
SCOP
6.88
5.42
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.25 kW
11.91 kW
COP Tj = -7°C
5.73
4.02
Cdh Tj = -7 °C
0.992
0.996
Pdh Tj = +2°C
7.46 kW
7.25 kW
COP Tj = +2°C
7.28
5.38
Cdh Tj = +2 °C
0.985
0.992
Pdh Tj = +7°C
4.79 kW
4.66 kW
COP Tj = +7°C
7.41
6.57
Cdh Tj = +7 °C
0.974
0.985
Pdh Tj = 12°C
3.52 kW
3.82 kW
COP Tj = 12°C
7.33
6.74
Cdh Tj = +12 °C
0.965
0.979
Pdh Tj = Tbiv
13.85 kW
13.46 kW
COP Tj = Tbiv
4.73
3.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.85 kW
13.46 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.73
3.58
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.997
WTOL
70 °C
70 °C
Poff
17 W
17 W
PTO
19 W
19 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4160 kWh
5134 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
123 %
COP
3.06
Heating up time
1:55 h:min
Standby power input
34.0 W
Reference hot water temperature
50.9 °C
Mixed water at 40°C
227 l