4,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
50.00 kW
50.00 kW
El input
11.56 kW
16.56 kW
COP
4.31
3.03
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
141 %
Prated
50.00 kW
50.00 kW
SCOP
4.69
3.59
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
44.57 kW
44.42 kW
COP Tj = -7°C
2.93
2.12
Cdh Tj = -7 °C
0.997
0.998
Pdh Tj = +2°C
27.69 kW
27.55 kW
COP Tj = +2°C
4.64
3.48
Cdh Tj = +2 °C
0.993
0.995
Pdh Tj = +7°C
18.08 kW
17.92 kW
COP Tj = +7°C
5.86
4.88
Cdh Tj = +7 °C
0.987
0.989
Pdh Tj = 12°C
21.31 kW
19.56 kW
COP Tj = 12°C
8.62
6.56
Cdh Tj = +12 °C
0.984
0.987
Pdh Tj = Tbiv
44.57 kW
44.42 kW
COP Tj = Tbiv
2.93
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
38.45 kW
36.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.997
0.998
WTOL
75 °C
75 °C
Poff
25 W
25 W
PTO
39 W
39 W
PSB
25 W
25 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
11.60 kW
13.50 kW
Annual energy consumption Qhe
22028 kWh
28753 kWh