1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.89 kW
17.10 kW
El input
3.46 kW
5.06 kW
COP
4.88
3.38
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
58 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
157 %
Prated
17.35 kW
17.22 kW
SCOP
5.15
4.01
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.34 kW
15.23 kW
COP Tj = -7°C
3.32
2.56
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.44 kW
9.29 kW
COP Tj = +2°C
5.02
3.88
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.17 kW
6.01 kW
COP Tj = +7°C
6.59
5.15
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.57 kW
5.24 kW
COP Tj = 12°C
9.07
7.21
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
15.34 kW
15.23 kW
COP Tj = Tbiv
3.32
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.02 kW
16.13 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.94
2.32
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
80 °C
80 °C
Poff
16 W
16 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
45 W
45 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.32 kW
1.09 kW
Annual energy consumption Qhe
6957 kWh
8870 kWh